Contemporary Controls BAScontrol22 and 22C
Building automation controller
For an existing panel, check the letter after 22 on the nameplate. A BASC-22R serves its own application points. A BASC-22CR can also collect readings from other BACnet devices. For a replacement enquiry, include the application backup and identify every remote reading the project depends on.
Compatibility
Compatible with Edge over BACnet/IP
Edge reads the controller’s commissioned objects using BACnet/IP over Ethernet.
Obtain the installed point schedule. For an upstream reading, verify the source device and the object exposed to Edge.
Connect it with
For a BASC-22R or BASC-22CR connected to the building Ethernet network
- Wired
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| BASC-22R | Two switched Ethernet ports, BACnet/IP server | Start with a physical channel or virtual point already exposed by the panel. |
| BASC-22CR | Two switched Ethernet ports, BACnet/IP client and server | Identify the remote device referenced by each network variable and its corresponding exported point. |
Interface
Documented measurements and integration boundaries for BAScontrol22 and 22C.
- A virtual Analog Value or Binary Value can represent application data. Record the point name, object type, instance and engineering unit from the commissioned panel.
- On a 22C, a network variable can take its reading from another BACnet device. Identify both the field object and the controller object offered to the collector.
Assessment
BAScontrol22 and 22C collection from the installed application.
- InteroperabilityWell supported
- The ordering code identifies the network interfaces and BACnet client capability.1
- AccuracySupported with conditions
- Identify the configured input and engineering unit before using it in a report.2
- SecurityNot yet assessed
- Confirm network access with the building operator.1
- ReliabilitySupported with conditions
- Compare a known point with the controller’s local channel reading.2
- RuggednessNot yet assessed
- Confirm the cabinet environment against the fitted controller specifications.1
- ScalabilitySupported with conditions
- The family has 22 physical channels and 24 virtual points. Count the application exports required by the project.1
- LifecycleSupported with conditions
- The manufacturer marks the original 22R and 22CR as discontinued and recommends BASC-22DR. Confirm the application and field wiring for the replacement.2
Setup
-
Obtain the panel order code, Device instance and one input or virtual point used by the operator.
-
Read Present_Value on the scheduled object.
Compare it with the same channel on the BAScontrol22 display page, recording the unit and time.
-
For a field device read by the application, compare its local value with the controller export and document the mapping and update interval.
Sources
- BAScontrol series network interfaces and firmware matrix (opens in a new tab)
- BAScontrol22 ordering and replacement information (opens in a new tab)
- BAScontrol22C client operation and replacement information (opens in a new tab)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.