Contemporary Controls BASRTP-B Portable BASrouter

BACnet router

The BASRTP-B suits a site survey where the engineer has laptop power and Ethernet access to a serial meter trunk. USB powers the router. Meter data travels over Ethernet. A successful survey identifies the meter and points available for collection; continuous logging also needs an Ethernet route and power after the visit.

Contemporary Controls BASRTP-B portable BACnet router with Ethernet and MS/TP connections
  • BACnet/IP
  • BACnet MS/TP

BACnet router

Ask an engineer

Compatibility

Compatible with Edge through routed BACnet/IP

Edge uses BACnet/IP on Ethernet. The BASRTP-B routes the request to the instrument on its MS/TP network.

Match the network number and serial rate to the controls schedule, then compare a known meter object with the operator display.

Connect it with

For a temporary survey

  • Wired
  • Edge
  • Platforms
BACnet router
Interface
Gateway
Edge
Output
BASRTP-B Portable BASrouterField meter on MS/TP
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeProtocol client + point model
Customer platformMQTT · API · files
Ethernet
Protected Ethernet
Runs locally
Optional onward data
Allow for an Ethernet connection as well as the USB power cable. Record the field device instance, object and unit while on site. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
BASRTP-BEthernet and EIA-485 for BACnet MS/TPCheck an existing MS/TP meter from Ethernet with a USB-powered portable router before specifying a permanent collector.

Interface

Documented measurements and integration boundaries for BASRTP-B Portable BASrouter.

  • Use a measurement from the field meter’s own object list. The router transports that reading; the instrument determines its units and accuracy.

Assessment

BACnet routing between Ethernet and an existing serial meter trunk.

InteroperabilityWell supported
Routes BACnet/IP requests to BACnet MS/TP devices.1
AccuracyNot applicable
The field instrument determines measurement accuracy.1
SecurityNot yet assessed
Site access controls require project-specific review.
ReliabilitySupported with conditions
Include a continuous 5 V USB supply for unattended use.1
RuggednessSupported with conditions
IP30 enclosure rated for operation from 0 to 60 °C.1
ScalabilitySupported with conditions
Size the trunk for the installed serial rate and polling interval. The supported rates range from 9.6 to 76.8 kbit/s.1
LifecycleSupported with conditions
The order code and datasheet revision identify the router for the commissioning record.1

Setup

  1. Obtain the approved network numbers, serial rate and a known field device instance from the operator.

  2. Read Present_Value and Units on a documented field object from the Ethernet side.

    Compare both with the operator display for the same circuit.

  3. Record the permanent power and network arrangements before pricing continuous monitoring.