The BASRTP-B suits a site survey where the engineer has laptop power and Ethernet access to a serial meter trunk. USB powers the router. Meter data travels over Ethernet. A successful survey identifies the meter and points available for collection; continuous logging also needs an Ethernet route and power after the visit.
Compatibility
Compatible with Edge through routed BACnet/IP
Edge uses BACnet/IP on Ethernet. The BASRTP-B routes the request to the instrument on its MS/TP network.
Match the network number and serial rate to the controls schedule, then compare a known meter object with the operator display.
Connect it with
For a temporary survey
- Wired
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| BASRTP-B | Ethernet and EIA-485 for BACnet MS/TP | Check an existing MS/TP meter from Ethernet with a USB-powered portable router before specifying a permanent collector. |
Interface
Documented measurements and integration boundaries for BASRTP-B Portable BASrouter.
- Use a measurement from the field meter’s own object list. The router transports that reading; the instrument determines its units and accuracy.
Assessment
BACnet routing between Ethernet and an existing serial meter trunk.
- InteroperabilityWell supported
- Routes BACnet/IP requests to BACnet MS/TP devices.1
- AccuracyNot applicable
- The field instrument determines measurement accuracy.1
- SecurityNot yet assessed
- Site access controls require project-specific review.
- ReliabilitySupported with conditions
- Include a continuous 5 V USB supply for unattended use.1
- RuggednessSupported with conditions
- IP30 enclosure rated for operation from 0 to 60 °C.1
- ScalabilitySupported with conditions
- Size the trunk for the installed serial rate and polling interval. The supported rates range from 9.6 to 76.8 kbit/s.1
- LifecycleSupported with conditions
- The order code and datasheet revision identify the router for the commissioning record.1
Setup
-
Obtain the approved network numbers, serial rate and a known field device instance from the operator.
-
Read Present_Value and Units on a documented field object from the Ethernet side.
Compare both with the operator display for the same circuit.
-
Record the permanent power and network arrangements before pricing continuous monitoring.
Sources
- BASRTP-B Portable BASrouter datasheet, DS-BASRTPB3-AB3 (opens in a new tab) (PDF)
- Successful BASrouter installation and operation (opens in a new tab) (PDF)
Further reading
- GuideConnecting existing power meters to BACnet
- GuideBACnet routing and foreign devices
- GuideGateway for BACnet/IP monitoring
- GuideBASRT-B BASrouter
- GuideCrompton Integra 1630 meter options
- ManufacturerContemporary Controls devices
- ProtocolBACnet/IP building controllers
- CategoryBuilding and energy integration controllers
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.