Belimo 22UTH
Outdoor temperature and humidity sensor
The shielded 22UTH provides an outdoor reference for heating, cooling and humidity trends. Choose a representative location away from exhaust discharge and record its position so readings from different elevations can be compared.
Compatibility
Compatible with Edge through a BACnet router
Edge reads the sensor through a BACnet/IP-to-MS/TP router on the building network.
Belimo’s interface description covers firmware 2.3. Match the suffix and object to the installed sensor before adding the trend.
Connect it with
For an installed MS/TP segment
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| 22UTH-160X and 22UTH-560X | The 22UTH-160X has a weather and radiant heat shield, a 24 V AC/DC supply and two voltage outputs alongside BACnet MS/TP. | Record the sensor Device instance, router and serial network number in the point list. |
Interface
Documented measurements and integration boundaries for 22UTH.
- AI 0 reports temperature in the selected unit system. AI 1 is relative humidity in percent. Label both with the outdoor location so a mixed-air or return-air sensor cannot be mistaken for the weather reference.
Assessment
Read-only collection over the installed sensor network.
- InteroperabilityWell supported
- The PICS names the ordering variants and documents ReadProperty and ReadPropertyMultiple on MS/TP.1
- AccuracySupported with conditions
- The 22UTH-160X lists a temperature measuring range of −20 to 80 °C and a default humidity range of 0 to 100% RH.2
- SecurityNot yet assessed
- Ask the site controls owner which clients may reach the trunk.1
- ReliabilityNot yet assessed
- Record the most recent successful reading when supervising the sensor.1
- RuggednessSupported with conditions
- The weather and radiant heat shield is part of the 22UTH-160X assembly. Include it when specifying a replacement.2
- ScalabilitySupported with conditions
- Belimo specifies up to 32 nodes without a repeater. Include existing devices when checking capacity on a shared segment.1
- LifecycleSupported with conditions
- Record the model suffix and application software version with the point list. Field models share an object table with different available measurements.1
Setup
-
Match the sensor label and its physical location to the building point schedule.
Record the Device instance as well as the object instance.
-
Read Present_Value and Units for Analog Input 0.
Compare with a shaded reference thermometer at the sensor location after both readings settle. A weather station elsewhere is a poor commissioning reference.
-
Check Out_Of_Service for the selected object.
The shared interface table includes measurements available only on other sensor types.
Sources
- Sensor BACnet object list and PICS, application software 2.3 (opens in a new tab) (PDF)
- 22UTH-160X weather shield and sensor specifications (opens in a new tab)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.