An air handling unit drawing often shows the controller and the ductwork on separate sheets. Bring them together before ordering sensors. Mark the outdoor air intake, return and supply ducts, filters and coils. Ask the controls contractor which of the required measurements already appear as readable objects in the building controller.
Choose the measurement and position
- Ventilation demand. The 22DTM duct sensor measures CO₂, temperature and humidity. A return-duct reading represents mixed air from the rooms served by that return. For a complaint about one meeting room, use a room measurement as well.
- Moisture across a coil. The 22DTH duct sensor provides temperature and humidity. Relative humidity changes when air temperature changes, even at the same moisture content. To assess moisture removal, use consistent humidity quantities and record both upstream and downstream conditions.
- Outdoor reference. The 22UTH outdoor sensor has a weather and radiant heat shield. Record its position relative to the intake and exhaust. A sensor beside an exhaust outlet can describe a different air stream from the one entering the unit.
- Filter loading. The 22ADP differential pressure sensor measures the pressure difference between taps. Select a range that covers the filter’s expected clean and final pressure drop. Compare trends at similar fan duty so a higher airflow is not mistaken for a dirty filter.
The Dwyer Magnesense MSX Pro-Comms offers a pascal reading at AI 2. Record the -COM option, pressure span and high and low taps for each filter on the schedule.
Look for a measurement on the existing controller
For a small air handling unit, the Distech ECB-203 can accept a duct pressure transducer. For a two-pipe fan coil, check the room sensor or input on the ECB-103. Ask for the equipment tag and the object that publishes the reading.
At the terminal, the ECB-VAV supports fan-powered and dual-duct applications, while the ECB-VAVS serves cooling-only and reheat boxes. Both have an onboard flow sensor. Keep the terminal airflow separate from the differential pressure measured across an air handling unit filter.
For a rooftop unit serving several VAV zones, the KMC FlexStat BAC-120063CW-ZEC can provide discharge-air temperature. Ask for the discharge sensor object on the FlexStat and identify each SimplyVAV zone separately. The optional static pressure feedback requires a fitted sensor.
Specify what the contractor will hand over
For each point, ask for the sensor suffix, physical location, BACnet Device instance, object identifier, unit and one local reference reading. Object numbers vary across product families. For example, Belimo assigns relative humidity to Analog Input 1 in the field sensor interface and Analog Input 2 in the 22RTH room sensor.
Where the readings already exist in the controller, check one export before pricing new hardware. For new MS/TP devices, include the power supply, probe or pressure tubing, existing trunk capacity and route to the IP network. Include the number of units, points per unit and desired trend interval in the project enquiry.