Siemens SENTRON PAC3120
Power and energy meter
PAC3120 is a CT-connected panel meter with built-in RS-485. Read its literal Modbus offsets, configure the serial framing and verify the meter’s CT settings before collecting power and energy.
- Modbus RTU
Power and energy meter
Compatibility
Compatible through Modbus RTU
The manufacturer documents local measurement reads that can be configured in an Edge Modbus client.
PAC3120 covered by the July 2024 PAC3120/PAC3220 manual. PAC3220 uses built-in Ethernet and a different native connection path; MID variants and expansion modules require their own scope.
Connect it with
-
Modbus Interface ZMB-3XFrom €399 ex VAT Configure Modbus Interface
-
Gateway ZGW-20From €899 ex VAT Configure Gateway
For the exact RS-485 model identified below
- Modbus
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| PAC3120 | Native RS-485 Modbus RTU | Use its configured serial port and address. |
| PAC3220 | Native switched Ethernet; RS-485 is an expansion option | Use the separate PAC3220 guide for its built-in Modbus TCP path. |
Specifications
PAC3120 suits a panel where the collection network is already RS-485. Its local display lets the installer compare a read with the meter itself before enabling a larger map. External CT ratios and wiring topology belong to the measuring configuration; serial settings only determine whether the values can be transported. A successful reply therefore does not establish correct primary current or power direction.1
- Current inputs
- External 1 A or 5 A secondary CTs1
- Native communication
- RS-485 Modbus RTU1
- Factory serial settings
- Address 126, 19200 bit/s, 8 data bits, no parity, 2 stop bits1
- Voltage width
- Float32 across two registers; L1-N begins at offset 11
- Energy width and unit
- Double across four registers, Wh1
- Write protection
- Hardware write-protection switch; monitoring reads remain available1
Interface
Documented measurements and integration boundaries for SENTRON PAC3120.
- Phase voltages and currents as two-register Float values.
- Total active power at offset 65 in W and frequency at offset 55 in Hz.
- Demand and power factor, distinct from accumulated consumption.
- Import and export energy by tariff, with four-register Double counters in Wh.
Assessment
PAC3120 covered by the July 2024 PAC3120/PAC3220 manual. PAC3220 uses built-in Ethernet and a different native connection path; MID variants and expansion modules require their own scope.
- InteroperabilityWell supported
- The manual defines Modbus functions, literal offsets, lengths and serial settings.1
- AccuracySupported with conditions
- CT ratios and wiring mode affect primary measurements; Float and Double values have different lengths.1
- SecuritySupported with conditions
- Hardware write protection supports read-only monitoring after authorised configuration.1
- ReliabilitySupported with conditions
- The manual documents diagnostics and complete-value access requirements.1
- RuggednessSupported with conditions
- Panel installation and terminal protection must follow the order-code-specific installation requirements.1
- ScalabilitySupported with conditions
- Addressed RS-485 collection requires unique addresses and matching bus framing.1
- LifecycleNot yet assessed
- The July 2024 manual includes firmware and maintenance guidance; support duration is not established here.1
Setup
Read L1-N voltage over the serial path
The July 2024 table gives offset 1, Float, two registers. This example uses FC03.
- Request PDU
- 03 00 01 00 02
- Literal offset
- 1; quantity 2 registers, four data bytes
- Independent decoder example
- Ordered IEEE-754 bytes 43 66 00 00 represent 230.0 V.
- Transport
- Add the installed RTU unit address and CRC; the PDU does not include either.
Acceptance: The data bytes are synthetic and do not establish the meter’s returned word order. Accept the actual read after identity, full width and display comparison agree.
-
Record the model and measuring configuration
Record the PAC3120 order code, firmware, auxiliary supply and wiring topology. Configure the actual CT primary and secondary values before relying on current, power or energy.
-
Match serial settings
Read the installed address, baud rate and framing. For a factory-configured meter the manual gives address 126, 19200 bit/s and 8N2. Set the Edge client to the same values and give every meter a unique address.
-
Read a complete Float at its literal offset
Use FC03 at offset 1 for L1-N voltage, quantity 2. Do not subtract one from a field explicitly labelled offset and do not begin halfway through a multi-register value.
-
Verify ordering and measurement meaning
Compare the decoded voltage with the simultaneous display to establish the configured byte and word order. Then check phase current and signed power with the CT configuration and known load.
-
Keep energy and settings separate
Read the complete four-register Double energy counter and divide Wh by 1000 only when displaying kWh. Preserve tariff and import/export direction. Use the hardware write-protection switch after authorised setup where appropriate.
Common questions
- Does PAC3120 have the same Ethernet ports as PAC3220?
- No. PAC3120 has built-in RS-485. PAC3220 has the native Ethernet path; the shared manual does not make their ports interchangeable.12
- Why can reading offset 2 fail?
- Offset 2 is the second half of the L1-N Float that starts at 1. Siemens requires complete multi-register values; begin at the documented starting offset and read the whole width.1
- Why is the energy total a thousand times too large?
- The documented Double energy counters use Wh. Converting to kWh requires division by 1000, once, after the complete value has been decoded. Check tariff and direction as well as units.1
Sources
- PAC3120 / PAC3220 manual July 2024 (opens in a new tab) (PDF)
- PAC3120 and PAC3220 equipment manual, October 2019, L1V30425208F-01 (opens in a new tab) (PDF)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.











