Siemens PXC4.E16.A

Building automation controller

For an existing 4–20 mA pressure transmitter, request the terminal number before pricing a new sensor or expansion module. The PXC4.E16.A has twelve universal I/O and four relay outputs onboard. Only U1, U2, U7 and U8 accept current measurement according to the station datasheet.

Siemens PXC4.E16.A automation station with network ports and upper terminal strip
  • BACnet/IP

Building automation controller

Ask an engineer

Compatibility

Compatible with Edge over BACnet/IP

Siemens documents BACnet/IP on the North American PXC4.E16.A station. Edge can collect application objects available over that network.

Confirm the full .A model code, Ethernet network mode and point list from the installed project.

Connect it with

For a commissioned BACnet/IP station

  • Wired
  • Edge
  • Platforms
Building automation controller
Interface
Gateway
Edge
Output
PXC4.E16.APXC4.E16.A application objects
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeProtocol client + point model
Customer platformMQTT · API · files
Ethernet
Protected Ethernet
Runs locally
Optional onward data
Record the station Device instance and the object type and instance assigned to the measurement by the project. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
PXC4.E16.ABACnet/IPv4 on Ethernet, 16 onboard I/O.Match the .A suffix before using the terminal schedule. Siemens publishes a separate specification for the PXC4.E16-2.
PXC4.E16.ABACnet building controller.BTL listing 31540 names the hardware at firmware V02.20.256.3.

Interface

Documented measurements and integration boundaries for PXC4.E16.A.

  • For a pressure transmitter, match its range to the configured current input and engineering units. A terminal number identifies the physical connection. The BACnet object instance comes from the project.

Assessment

PXC4.E16.A over BACnet/IP.

InteroperabilityWell supported
The listing identifies the documented model and firmware.3
AccuracyNot yet assessed
The measurement depends on the connected instrument and its programmed scaling.2
SecurityNot yet assessed
Confirm the permitted Ethernet network mode on site.2
ReliabilityNot yet assessed
The listing records tested BACnet services.3
RuggednessNot yet assessed
Identify the enclosure and plant-room location in the installation records.2
ScalabilitySupported with conditions
Siemens specifies physical I/O capacity separately from the configured application.2
LifecycleSupported with conditions
Use the full station order code when requesting hardware or service.2

Setup

  1. Record the station order code, Device instance and object schedule.

  2. Read Present_Value and Units from the analog object assigned to the transmitter.

    Compare the engineering value with a reference at the same pressure taps during steady operation.

  3. Retain the equipment tag, object identifier, unit and reference timestamp with the accepted point list.