Distributed energy

Generator remote monitoring

An independent meter proves what the generator carried, the controller says what it thought it was doing, and the fuel signal says how long it can keep going.

ZEM-65 Wireless 3-Phase Electricity Monitor
ZEM-65Electricity metering
ZMB-31 Modbus Interface
ZMB-31Modbus interface
ZGW-20 Gateway
ZGW-20Gateway with Edge
Measure
Generator output, run and fault states, fuel level, and the site connection it backs up
Rule
Monitoring only. Protection, transfer and safety stay with the generator's own controls
Sensors
ZEM-65, Class 0.5S metering with CTs sized for the alternator ZEM-63 datasheet (PDF, opens in a new tab)
On site
ZGW-20 Gateway, event history and alarms, with a standby generator energy monitoring record ZGW-20 datasheet (PDF, opens in a new tab)

A run signal is not proof of output

A run contact says the controller believes the set is running. Independent voltage, current and power say whether it actually carried load, and how much. Test regimes usually need both, because a healthy start that never took load is a common failure.

Hardware for a generator monitoring system

One meter on the alternator output, the controller if it will talk, and an analogue input for fuel.

If fuel level is monitored

ZMB-31 and ZIO-20 share one enclosure with different terminals inside, so the ordering code is what you specify.

What to measure around a generator

Measure outside the protection boundary. Everything here is read only, and nothing in it changes how the set behaves.

What to measure around a generatorThe meter goes on the generator's own output. Whether that is before or after the transfer equipment decides what the reading means. Grid connection Site board Solar PV inverter Battery and inverter Generator EV charging board Import is positive and export is negative, at the connection ZGW-20 GatewayEdge on site ZEM-65 · output ZMB-31 ZIO-20 ZEM-65 · site What to measure around a generatorThe meter goes on the generator's own output. Whether that is before or after the transfer equipment decides what the reading means. Grid connection Site board Solar PV Battery Generator EV charging ZGW-20 GatewayEdge on site ZEM-65 · output ZMB-31 ZIO-20 ZEM-65 · site
The meter goes on the generator's own output. Whether that is before or after the transfer equipment decides what the reading means.
Sensor positions for what to measure around a generator
PositionWhat it tells youReferenceSensor
Generator output Voltage, current, power and energy: what the set actually carried Say whether the measurement is before or after the transfer equipment ZEM-63 datasheet (PDF, opens in a new tab) ZEM-65 (on this page), output
Run, available and fault What the controller thought was happening, in its own words Map each state exactly: one common fault loses the diagnosis ZMB-3X datasheet (PDF, opens in a new tab) ZMB-31 (on this page)
Fuel level How long the set could keep running The transmitter's range and scaling, recorded with its calibration ZIO-2X datasheet (PDF, opens in a new tab) ZIO-20 (on this page)
Site connection Whether the site was on the grid or on the generator at the time The same sign convention as the generator meter ZEM-65 (on this page), site
  • Read only, by default. Acquiring controller data is not the same as commanding the set. A remote start or a demand-response command is a separate safety and operational design.

  • Freeze the controller's identity. Write down the controller model, its firmware and the register map version. A firmware change can move a register without warning.

Test records and alarms in Edge

The useful output is a record of every start, and what the set did during it.

A start that carried no load
A rule compares the run state with measured power, so a test that started and never loaded is visible rather than filed as a pass.
Fuel below its reserve
A limit rule on the fuel signal, with the reserve agreed with whoever refuels the tank.
A controller that goes quiet
A no-data rule on the controller's registers, because a silent controller during an outage is the worst time to find out.
The record leaves the site
Events and interval data export over MQTT or HTTP to whatever holds the maintenance record.

Commissioning checks

Run these during a planned test, with the person who maintains the set.

  • The measurement boundary is on the drawing

    Mark on the single-line diagram where the generator meter and the site meter sit.

    Pass when both are on the drawing, and it says which side of the transfer equipment each one is.

  • Electrical values agree with a reference

    During a loaded test run, compare the meter with an independent instrument.

    Pass when voltage, current and power agree within the instruments' accuracy.

  • The full sequence is exercised

    Walk through start, transfer, loaded run, return and stop while watching the states and the power.

    Pass when each state appears in the right order, with timestamps that match the observed events.

  • A lost connection is visible

    Disconnect the controller's serial link during a test.

    Pass when Edge reports the loss instead of repeating the last known state.

  • Nothing here can start the set

    Review the configuration for any write to the controller.

    Pass when the acquisition is read only, or any control has its own documented safety design.

What monitoring does not replace

Everything on this page sits outside the generator's own protection.

  • It does not replace generator, alternator, transfer-switch, fuel-system or life-safety protection.
  • A remote start or a demand-response command needs a site-specific safety and operational design, and the maintainer's agreement.
  • Fuel-consumption and efficiency conclusions need a calibrated fuel measurement over a matched electrical period.
  • A controller's own values are the controller's: they carry its calibration, not an independent one.

Sources and related guides

Sources

Related

  • Solar PV monitoring Application guide Independent AC metering at the inverter and the grid connection, inverter registers for context, and an energy balance that adds up.
  • Battery demand response Application guide Measure the connection and the battery separately, read state of charge and limits from the BMS, and record events at the resolution the programme wants.
  • Generator fuel-rate normalisation calculator Engineering tool Calculate generator fuel use per hour and per kWh, and the average load over a run.
  • Electrical load factor calculator Engineering tool Check how evenly a site uses its peak demand over a billing or reporting period.

Reviewed by EpiSensor Engineering on . Revision 4.

Prove what a generator carried, without touching it

We will check the register map, place the meter, and keep the whole thing outside the protection boundary.

Contact us