Power and energy

Three-phase power calculator

Calculate balanced three-phase active, reactive and apparent power from line voltage, line current and power factor.

Calculate

Measured line values
V
A
Enter the magnitude from 0 to 1.

Worked example

Active power, total three-phase

 kW

Reactive power, total (inductive, lagging)
 kvar
Apparent power, total
 kVA
Phase angle

Balanced three-phase, from line-to-line voltage and line current.

Underlined figures are rounded. Select one to copy its full value.

Method and assumptions

Formula

S = √3 × VLL × IL; P = S × PF; Q = ±S × √(1 − PF²)

Balanced sinusoidal system. Use per-phase measurements for an unbalanced load.

Limits of this result

  • Confirm the source data, device datasheet and installation conditions before relying on the result.

Technical sources

  1. Calculation of electrical powers in Schneider Electric PMDsSchneider Electric · 7EN52-0464-00, 2022-03-18
  2. Electrical devices — electrotechnical formulasABB · 1SDC010001D0202