Load factor calculator

Work out how evenly a site uses its peak demand over a billing or reporting period, from energy used and the peak interval demand.

Energy cost and demand Updated Free, no sign-up

You enter, in numbered orderCalculated

From the meter

Energy usedIn the periodPeak demandThe highest interval in the period

Energy used against the peak held all period

050100Peak 100 kWAverage 50 kW36,000 kWh used50% of the peak unusedkW0200400720 h

Period length

The filled block is the energy used and the dashed box the peak held for the whole period. The line is one profile with this energy and peak; the real shape comes from the interval data.

The average is the energy spread over the period

36,000 kWh720 h50

The load factor is the average over the peak

50 kW100 kW50

Peak capacity unused on average50

Type the energy, the peak and the period, or drag the peak and average lines.

Load factor

50%

Average demand
50 kW
Peak capacity unused on average
50%

For the entered period only. Compare periods that use the same demand interval.

How it’s calculated
  1. Pavg = E ÷ t=36,000 ÷ 720=50 kW
  2. Load factor = Pavg ÷ Ppeak × 100=50 ÷ 100 × 100=50%

36,000 kWh over 720 hours with a 100 kW peak is an average of 50 kW, a load factor of 50%.

Tip: A low load factor can reveal short, sharp peaks. Check whether reducing or shifting them has value under the site's tariff and operating constraints.

Example values
Period

Common periods

h
Energy and peak
kWh

The highest interval in the period

kW

How to calculate load factor

Load factor compares the energy a site actually used with the energy it would have used running at its peak demand the whole time. Divide the kWh by the peak kW times the hours in the period. A site that used 36,000 kWh in a 30-day month with a 100 kW peak averaged 50 kW, a load factor of 50%.

Load factor

LF = E ÷ (Ppeak × t) × 100

E is the energy in kWh, Ppeak the highest demand in kW and t the length of the period in hours. All three must cover the same period.

Average demand

Pavg = E ÷ t

Load factor is the average demand as a share of the peak: 50 kW average against a 100 kW peak is 50%.

Full-load hours

hours at peak = E ÷ Ppeak = (LF ÷ 100) × t

The same idea read the other way: how many hours at full peak would use the period’s energy. Over a year, 4,380 hours is a load factor of 50%.

Peak demand depends on the interval it is measured over. A 15-minute peak can be higher than a 30-minute peak when the load has short peaks; for steady load they can be equal. Compare load factors that use the same interval.

Load factor examples

An office over a 30-day month

36,000 kWh ÷ 720 h is an average of 50 kW. Against a 100 kW peak, the load factor is 50%: the building runs hard in working hours and lightly at night and at weekends.

Load factor 50 % Open in the calculator

A two-shift factory over a 31-day month

186,000 kWh over 744 hours averages 250 kW. With a 400 kW peak the load factor is 62.5%. If the peak comes from several large motors starting together, staggering them lowers the peak and the demand charge without changing the energy.

Load factor 62.5 % Open in the calculator

A site with a short, sharp peak

1,500,000 kWh in a year with a 650 kW peak is an average of 171.2 kW, a load factor of 26.34%. Most of the time the site uses a quarter of the capacity it pays for, which makes it a strong case for peak shaving or load shifting.

Load factor 26.34 % Open in the calculator

Load factor from annual full-load hours

Annual energy divided by the annual peak gives full-load hours. This table converts them to load factor and to average demand per 100 kW of peak.

Full-load hours per yearLoad factor (%)Average kW per 100 kW of peak
5005.75.7
1,00011.411.4
2,00022.822.8
3,00034.234.2
4,00045.745.7
5,00057.157.1
6,00068.568.5
7,00079.979.9
8,00091.391.3
8,760100.0100.0

Download this table (CSV)

Questions about load factor

What is a good load factor?

It depends on the site. Continuous processes and data centres often run above 70%. Offices and schools sit well below, because they are busy only part of the day. What matters is the trend and the cause of the peak.

Why does load factor matter?

Networks and tariffs charge for peak capacity as well as energy. A low load factor means paying for capacity that sits idle most of the time, and it often shows a peak that could be moved or trimmed.

How do I improve load factor?

Lower the peak rather than the energy: stagger large loads, shift flexible ones such as heating, cooling or charging away from the peak, or respond to demand signals. The demand response event calculator checks what a reduction delivered.

Which peak should I use?

The highest interval demand in the same period as the energy, measured the way your tariff measures it. The interval demand calculator turns interval kWh into kW.

Limits of this result

  • Confirm the source data, device datasheet and installation conditions before relying on the result.

Measure it continuously

Load factor needs a true peak. A ZEM records demand continuously, so the peak interval and what caused it are both on record.

Related guides