Chiller performance monitoring

Cooling output from a flow reading and a matched entering-and-leaving temperature pair, divided by the metered electrical input.

ZEM-65 Wireless 3-Phase Electricity Monitor
ZEM-65Electricity metering
ZIO-20 Analogue Signal Sensor
ZIO-20Flow input
ZGW-20 Gateway
ZGW-20Gateway with Edge
Measure
Chiller and pump electricity, chilled-water flow, entering and leaving water temperature
Calculate
Chiller COP and kW per ton, on the Gateway itself
Sensors
ZEM-65, Class 0.5S to IEC 62053-22, CTs calibrated with the meter Wireless 3-Phase Electricity Monitor datasheet
On site
ZGW-20 Gateway, calculated sensors and 1, 5, 15 or 30-second live stream Edge

Equipment COP or plant COP

Decide which electrical inputs belong inside the ratio before anything is installed. Both boundaries are valid, and they give different numbers for the same plant, so a comparison is only meaningful when both sides used the same one.

Equipment COP or plant COP
Equipment COPPlant COP
Electrical input The chiller onlyChiller, chilled-water and condenser-water pumps, tower fans
Answers How the machine is performingWhat the cooling actually costs
Meters One at the chiller supplyOne per pump or tower group as well

Hardware for a chiller COP measurement

One meter per electrical input inside your boundary, one flow measurement, and the water temperatures from the chiller's own controller.

If the chilled-water circuit already has a heat meter

What to measure on a chilled-water circuit

Four measurements make the ratio. Each one needs to be inside the same boundary and on the same clock as the others.

From field measurement to Edge

Each field signal reaches its named EpiSensor interface, reports through the site Gateway and is handled locally in Edge.

  • Wired
  • Zigbee
  • Edge
  • Platforms
Field measurement
Interface
Gateway
Local Edge
Optional output
Chiller supply
Pumps and tower fans
Chilled-water flow
Entering and leaving water
Chilled-water heat meter
ZEM-65Wireless 3-Phase Electricity Monitor
ZIO-20Analogue Signal Sensor
ZMB-31Modbus Interface
ZHM-21M-Bus Interface
ZGW-20Gateway
EdgeLocal data, monitoring and rules
Customer platformOptional onward data
Voltage + CT inputs
Zigbee mesh
4–20 mA input
Modbus RTU · RS-485
Wired M-Bus
Runs locally
Configured MQTTS / HTTPS
Customer platformOptional onward data
EdgeLocal data, monitoring and rules
ZGW-20Gateway
ZEM-65Voltage + CT inputs
Chiller supply
Pumps and tower fans
ZIO-204–20 mA input
Chilled-water flow
ZMB-31Modbus RTU · RS-485
Entering and leaving water
ZHM-21Wired M-Bus
Chilled-water heat meter
Configured MQTTS / HTTPS
Runs locally
Zigbee mesh
Sending data on to a customer platform is optional; Edge keeps working on site without one.
What to measure on a chilled-water circuit
PositionWhat it tells youReferenceSensor
Chiller supply The electrical input, and whether the machine is loaded or idling Class 0.5S metering, CTs sized for the supply Wireless 3-Phase Electricity Monitor datasheet ZEM-65 (on this page)
Pumps and tower fans The rest of the plant input, when the boundary is plant COP One meter per supply inside the boundary ZEM-65 (on this page), one per group
Chilled-water flow The volume flow the cooling calculation needs Transmitter range, zero and units read from its own configuration Analogue Signal Sensor datasheet ZIO-20 (on this page)
Entering and leaving water The temperature difference across the evaporator The chiller's own sensor pair, read over Modbus Modbus Interface datasheet ZMB-31 (on this page)
  • Do not read a small difference with surface probes. A 4 °C difference measured by two clamp-on probes carries more error than the result can stand. Use the chiller's matched pair, a heat meter, or immersion pockets.

  • Convert flow units once. Record whether the transmitter reports litres per second or cubic metres per hour, and convert once, in the calculation.

  • Use the glycol mix’s own heat capacity. A glycol mix has a lower specific heat capacity than water. Use the fluid's own values, from the supplier's data, at the operating temperature.

How to calculate chiller COP

Cooling output comes from flow and the matched entering-and-leaving water temperature pair. Divide it by the sum of every electrical input inside the chosen boundary, measured over the same interval.

Q = V × ρ × c × ΔT
COP = Q ÷ P
kW/ton = P ÷ (Q ÷ 3.5169)
Q
cooling output, kW
V
volume flow, litres per second
ρ
fluid density, kg per litre
c
specific heat capacity, kJ per kg per K
ΔT
entering minus leaving water temperature, K
P
electrical input inside the boundary, kW

Worked example

Water at 12.0 °C entering and 7.0 °C leaving, flowing at 18.0 litres per second, gives Q = 18.0 × 1.0 × 4.18 × 5.0 = 376 kW. With the chiller drawing 96 kW, COP = 3.9 and kW per ton = 0.90. One refrigeration ton is 3.5169 kW of cooling.

In Edge

Build it as a calculated sensor on the Gateway. Use the Expression operation with the flow, the two temperatures and the power as explicit inputs, guard the division, and set the stale-input threshold so the result is suppressed rather than calculated from an old reading.

Commissioning checks

A ratio is only as good as its inputs, so check the inputs first and the ratio last.

  • Each meter is on the supply you think it is

    Open and close one supply at a time, or step a known load, and watch which meter moves.

    Pass when every meter is named for the supply that changed, and the phase order is confirmed by a competent person.

  • The flow signal is scaled

    Compare the transmitter's own display or configuration with the value in Edge at two flows.

    Pass when both values agree in the same units, and 4 mA reads as the transmitter's zero rather than as zero flow.

  • The temperature pair is trustworthy

    Read entering and leaving temperature with the chiller off and the loop circulating.

    Pass when the difference is close to zero, and any offset is recorded and applied consistently.

  • Cooling and power share one interval

    Step the load or watch a stage change, and compare the timestamps of the flow, temperature and power readings.

    Pass when the inputs move together, and none lags by more than the calculation's reporting interval.

  • One interval by hand

    Take the raw values for a single interval and work the formula through on paper.

    Pass when the hand calculation matches the Edge result, and any difference is explained by rounding.

Limits of this measurement

An instantaneous ratio describes one operating point, under the conditions it was measured in.

  • It is not IPLV, NPLV, a seasonal figure or a certified rating-point result.
  • Sensor error dominates when the temperature difference is small: a 0.2 °C error on a 4 °C difference is 5 per cent of the answer.
  • A comparison between two periods means nothing unless the load, the entering condenser conditions and the boundary were the same.
  • Monitoring does not establish refrigerant charge, mechanical condition or compliance with any code.

Sources

  1. Purchasing energy-efficient electric chillers (opens in a new tab) (opens in a new tab) US Department of Energy FEMP
  2. Wireless 3-Phase Electricity Monitor datasheet (opens in a new tab) EpiSensor. Specifications, ranges and ordering codes.

Agree the chiller boundary before anything is ordered

An engineer can agree the boundary, size the meters and the CTs, and write the calculation with you.

Build this system