Measurlogic DTS SMX
Power and energy meter
The SMX packages a line-powered meter in a NEMA 4X surface enclosure. For an outdoor plant or generation feeder, record the mounting location, cable entries and whether the report needs separate imported and exported energy.
Compatibility
Compatible with Edge over BACnet/IP or routed MS/TP
Measurlogic offers Ethernet and serial BACnet versions. Edge reads an Ethernet meter directly or reaches a serial meter through the site BACnet router.
The serial example applies to a label showing BACnet MS/TP ML. For other versions use the map corresponding to the installed interface.
Connect it with
For a meter commissioned for BACnet MS/TP
- BACnet
- Edge
- Platforms
For a meter commissioned for BACnet/IP
- Wired
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| DTS SMX ordering options | Verify the enclosure location, CT type and expected energy directions on the installed unit. | BTL listing 30593 covers the SB serial ordering pattern at firmware 3.0a-1.0300. Match the full suffix and firmware for a project submittal. |
Interface
Documented measurements and integration boundaries for DTS SMX.
- AI 7013 and AI 7014 are separate positive import and export totals in kWh. AI 7004 is net active energy.
Assessment
DTS SMX monitoring using the installed communications option.
- InteroperabilityWell supported
- The BTL listing identifies a defined serial order pattern and tested firmware.3
- AccuracySupported with conditions
- Check the enclosure location, CT type and expected energy directions against the site requirements.1
- SecurityNot yet assessed
- Confirm the approved network route with the operator.1
- ReliabilitySupported with conditions
- Match the Device object identity and interface option before assigning readings to a circuit.2
- RuggednessSupported with conditions
- Measurlogic specifies a NEMA 4X surface enclosure. Include the proposed location in the survey.1
- ScalabilitySupported with conditions
- Each meter on the trunk needs a distinct MAC address and network-wide Device instance.2
- LifecycleSupported with conditions
- Retain the complete model code and fitted measurement options in the replacement schedule.1
Setup
-
Match the serial number and connected feeder to the operator’s point list.
Record the enclosure location, CT type and expected energy directions.
-
On the ML serial version described in R23A, compare the change in AI 7013 with imported kWh over the same interval, then check AI 7014 during a known export interval if the site generates.
-
Record the observed object type, instance, engineering unit and time with the reference reading.
Sources
- DTS SMX specifications and ordering options (opens in a new tab)
- DTS BACnet MS/TP ML map, revision R23A (opens in a new tab) (PDF)
- BTL 30593, DTS serial meter ordering patterns and firmware (opens in a new tab) (PDF)
- DTS BACnet/IP map, version 2.0U (opens in a new tab) (PDF)
Further reading