Measurlogic DTS SMX

Power and energy meter

The SMX packages a line-powered meter in a NEMA 4X surface enclosure. For an outdoor plant or generation feeder, record the mounting location, cable entries and whether the report needs separate imported and exported energy.

Measurlogic DTS SMX. Closed panel enclosure with the display and three front buttons.
  • BACnet MS/TP
  • BACnet/IP

Power and energy meter

Ask an engineer

Compatibility

Compatible with Edge over BACnet/IP or routed MS/TP

Measurlogic offers Ethernet and serial BACnet versions. Edge reads an Ethernet meter directly or reaches a serial meter through the site BACnet router.

The serial example applies to a label showing BACnet MS/TP ML. For other versions use the map corresponding to the installed interface.

Connect it with

Route into Edge

For a meter commissioned for BACnet MS/TP

  • BACnet
  • Edge
  • Platforms
Power and energy meter
Interface
Gateway
Edge
Output
DTS SMXDTS SMX MS/TP ML option
BACnet routerRoutes requests from Ethernet to the meter’s RS-485 segment.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Identify the serial trunk, router and Device instance. Photograph the meter label so the correct mapping accompanies the point schedule. The customer-platform output is optional; Edge remains the local system of record.

For a meter commissioned for BACnet/IP

  • Wired
  • Edge
  • Platforms
Power and energy meter
Interface
Gateway
Edge
Output
DTS SMXDTS SMX Ethernet option
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeProtocol client + point model
Customer platformMQTT · API · files
Ethernet
Protected Ethernet
Runs locally
Optional onward data
Read the commissioned BACnet/IP Device instance and record the object type and units reported by the installed interface. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
DTS SMX ordering optionsVerify the enclosure location, CT type and expected energy directions on the installed unit.BTL listing 30593 covers the SB serial ordering pattern at firmware 3.0a-1.0300. Match the full suffix and firmware for a project submittal.

Interface

Documented measurements and integration boundaries for DTS SMX.

  • AI 7013 and AI 7014 are separate positive import and export totals in kWh. AI 7004 is net active energy.

Assessment

DTS SMX monitoring using the installed communications option.

InteroperabilityWell supported
The BTL listing identifies a defined serial order pattern and tested firmware.3
AccuracySupported with conditions
Check the enclosure location, CT type and expected energy directions against the site requirements.1
SecurityNot yet assessed
Confirm the approved network route with the operator.1
ReliabilitySupported with conditions
Match the Device object identity and interface option before assigning readings to a circuit.2
RuggednessSupported with conditions
Measurlogic specifies a NEMA 4X surface enclosure. Include the proposed location in the survey.1
ScalabilitySupported with conditions
Each meter on the trunk needs a distinct MAC address and network-wide Device instance.2
LifecycleSupported with conditions
Retain the complete model code and fitted measurement options in the replacement schedule.1

Setup

  1. Match the serial number and connected feeder to the operator’s point list.

    Record the enclosure location, CT type and expected energy directions.

  2. On the ML serial version described in R23A, compare the change in AI 7013 with imported kWh over the same interval, then check AI 7014 during a known export interval if the site generates.

  3. Record the observed object type, instance, engineering unit and time with the reference reading.