Measurlogic DTS DC
Power and energy meter
For a DC feeder, obtain the voltage range, grounding arrangement and current transducer signal. The DTS DC3 can use shunts or Hall-effect transducers. A battery or generation circuit also needs a documented sign convention so charge and discharge are reported consistently.
Compatibility
Compatible with Edge over BACnet/IP or routed MS/TP
Measurlogic offers Ethernet and serial BACnet versions. Edge reads an Ethernet meter directly or reaches a serial meter through the site BACnet router.
The DC object example is for the V2.0U Ethernet map. Obtain the DC-specific object schedule for a serial meter.
Connect it with
For a meter commissioned for BACnet MS/TP
- BACnet
- Edge
- Platforms
For a meter commissioned for BACnet/IP
- Wired
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| DTS DC ordering options | Verify the DC voltage range, shunt or Hall-effect signal and direction convention on the installed unit. | BTL listing 30593 covers the SB serial ordering pattern at firmware 3.0a-1.0300. Match the full suffix and firmware for a project submittal. |
Interface
Documented measurements and integration boundaries for DTS DC.
- On an Ethernet meter matching map V2.0U, Analog Output 5501 reports DC voltage in V and Analog Output 5525 reports DC power in W. These are measurement objects read through Present_Value.
Assessment
DTS DC monitoring using the installed communications option.
- InteroperabilityWell supported
- The BTL listing identifies a defined serial order pattern and tested firmware.3
- AccuracySupported with conditions
- Check the DC voltage range, shunt or Hall-effect signal and direction convention against the site requirements.1
- SecurityNot yet assessed
- Confirm the approved network route with the operator.1
- ReliabilitySupported with conditions
- Match the Device object identity and interface option before assigning readings to a circuit.2
- RuggednessNot yet assessed
- Confirm the enclosure and installation environment for the ordered meter.1
- ScalabilitySupported with conditions
- Each meter on the trunk needs a distinct MAC address and network-wide Device instance.2
- LifecycleSupported with conditions
- Retain the complete model code and fitted measurement options in the replacement schedule.1
Setup
-
Match the serial number and connected feeder to the operator’s point list.
Record the DC voltage range, shunt or Hall-effect signal and direction convention.
-
For a meter matching Ethernet map V2.0U, read Present_Value on Analog Output 5501 and compare volts with the local DC bus indication.
Check AO 5525 against DC power in watts at the same time.
-
Record the observed object type, instance, engineering unit and time with the reference reading.
Sources
- DTS DC specifications and ordering options (opens in a new tab)
- DTS BACnet MS/TP ML map, revision R23A (opens in a new tab) (PDF)
- BTL 30593, DTS serial meter ordering patterns and firmware (opens in a new tab) (PDF)
- DTS BACnet/IP map, version 2.0U (opens in a new tab) (PDF)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.