Measurlogic DTS DC

Power and energy meter

For a DC feeder, obtain the voltage range, grounding arrangement and current transducer signal. The DTS DC3 can use shunts or Hall-effect transducers. A battery or generation circuit also needs a documented sign convention so charge and discharge are reported consistently.

Measurlogic DTS DC3. Angled view of the DTS DC3 variant.
  • BACnet MS/TP
  • BACnet/IP

Power and energy meter

Ask an engineer

Compatibility

Compatible with Edge over BACnet/IP or routed MS/TP

Measurlogic offers Ethernet and serial BACnet versions. Edge reads an Ethernet meter directly or reaches a serial meter through the site BACnet router.

The DC object example is for the V2.0U Ethernet map. Obtain the DC-specific object schedule for a serial meter.

Connect it with

Route into Edge

For a meter commissioned for BACnet MS/TP

  • BACnet
  • Edge
  • Platforms
Power and energy meter
Interface
Gateway
Edge
Output
DTS DCDTS DC MS/TP ML option
BACnet routerRoutes requests from Ethernet to the meter’s RS-485 segment.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Identify the serial trunk, router and Device instance. Photograph the meter label so the correct mapping accompanies the point schedule. The customer-platform output is optional; Edge remains the local system of record.

For a meter commissioned for BACnet/IP

  • Wired
  • Edge
  • Platforms
Power and energy meter
Interface
Gateway
Edge
Output
DTS DCDTS DC Ethernet option
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeProtocol client + point model
Customer platformMQTT · API · files
Ethernet
Protected Ethernet
Runs locally
Optional onward data
Read the commissioned BACnet/IP Device instance and record the object type and units reported by the installed interface. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
DTS DC ordering optionsVerify the DC voltage range, shunt or Hall-effect signal and direction convention on the installed unit.BTL listing 30593 covers the SB serial ordering pattern at firmware 3.0a-1.0300. Match the full suffix and firmware for a project submittal.

Interface

Documented measurements and integration boundaries for DTS DC.

  • On an Ethernet meter matching map V2.0U, Analog Output 5501 reports DC voltage in V and Analog Output 5525 reports DC power in W. These are measurement objects read through Present_Value.

Assessment

DTS DC monitoring using the installed communications option.

InteroperabilityWell supported
The BTL listing identifies a defined serial order pattern and tested firmware.3
AccuracySupported with conditions
Check the DC voltage range, shunt or Hall-effect signal and direction convention against the site requirements.1
SecurityNot yet assessed
Confirm the approved network route with the operator.1
ReliabilitySupported with conditions
Match the Device object identity and interface option before assigning readings to a circuit.2
RuggednessNot yet assessed
Confirm the enclosure and installation environment for the ordered meter.1
ScalabilitySupported with conditions
Each meter on the trunk needs a distinct MAC address and network-wide Device instance.2
LifecycleSupported with conditions
Retain the complete model code and fitted measurement options in the replacement schedule.1

Setup

  1. Match the serial number and connected feeder to the operator’s point list.

    Record the DC voltage range, shunt or Hall-effect signal and direction convention.

  2. For a meter matching Ethernet map V2.0U, read Present_Value on Analog Output 5501 and compare volts with the local DC bus indication.

    Check AO 5525 against DC power in watts at the same time.

  3. Record the observed object type, instance, engineering unit and time with the reference reading.