Measurlogic DTS 307
Power and energy meter
The 307 is 1.38 inches wide. Its order options distinguish a self-powered four-wire installation from an externally powered meter for a three- or four-wire feeder. Record neutral availability and the panel supply along with the CT type.
Compatibility
Compatible with Edge over BACnet/IP or routed MS/TP
Measurlogic offers Ethernet and serial BACnet versions. Edge reads an Ethernet meter directly or reaches a serial meter through the site BACnet router.
The serial example applies to a label showing BACnet MS/TP ML. For other versions use the map corresponding to the installed interface.
Connect it with
For a meter commissioned for BACnet MS/TP
- BACnet
- Edge
- Platforms
For a meter commissioned for BACnet/IP
- Wired
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| DTS 307 ordering options | Verify the available rail space, supply and neutral connection on the installed unit. | BTL listing 30593 covers the SB serial ordering pattern at firmware 3.0a-1.0300. Match the full suffix and firmware for a project submittal. |
Interface
Documented measurements and integration boundaries for DTS 307.
- AI 5505 is the line-to-line voltage between phases one and two, in volts.
Assessment
DTS 307 monitoring using the installed communications option.
- InteroperabilityWell supported
- The BTL listing identifies a defined serial order pattern and tested firmware.3
- AccuracySupported with conditions
- Check the available rail space, supply and neutral connection against the site requirements.1
- SecurityNot yet assessed
- Confirm the approved network route with the operator.1
- ReliabilitySupported with conditions
- Match the Device object identity and interface option before assigning readings to a circuit.2
- RuggednessNot yet assessed
- Confirm the enclosure and installation environment for the ordered meter.1
- ScalabilitySupported with conditions
- Each meter on the trunk needs a distinct MAC address and network-wide Device instance.2
- LifecycleSupported with conditions
- Retain the complete model code and fitted measurement options in the replacement schedule.1
Setup
-
Match the serial number and connected feeder to the operator’s point list.
Record the available rail space, supply and neutral connection.
-
On the ML serial version described in R23A, compare AI 5505 with the existing phase-to-phase voltage indication for that feeder.
-
Record the observed object type, instance, engineering unit and time with the reference reading.
Sources
- DTS 307 specifications and ordering options (opens in a new tab)
- DTS BACnet MS/TP ML map, revision R23A (opens in a new tab) (PDF)
- BTL 30593, DTS serial meter ordering patterns and firmware (opens in a new tab) (PDF)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.











