Janitza UMG 96RM-E

Panel-mounted power analyser

UMG 96RM-E is a panel power analyser with Ethernet, RS-485, external current-transformer inputs and additional residual-current monitoring. Its float and integer measurements already include the configured transformer ratios; applying a second ratio in Edge would overstate the readings.

Janitza UMG 96RM-E
  • Modbus TCP
  • Modbus RTU

Panel-mounted power analyser

Compatibility

Compatible through Modbus TCP or Modbus RTU

The manufacturer publishes the measurement register map and communication settings used by an Edge Modbus client.

UMG 96RM-E, using the June 2024 address list for firmware 3.01 onward and hardware release 104. Confirm installed revisions before using this map; UMG 96RM without the E suffix is a different interface scope.

Connect it with

Route into Edge

When the analyser is on the protected site network

  • Modbus
  • Edge
  • Platforms
Panel-mounted power analyser
Interface
Gateway
Edge
Output
UMG 96RM-EUMG 96RM-E Ethernet
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeEdge Modbus client
Customer platformMQTT · API · files
Modbus TCP
Protected Ethernet
Runs locally
Optional onward data
Use the configured analyser IP and Modbus TCP port 502. The manual separately lists port 8000 for Modbus RTU over Ethernet; that framing is not ordinary Modbus TCP. The customer-platform output is optional; Edge remains the local system of record.

When its RS-485 slave interface is used

  • Modbus
  • Edge
  • Platforms
Panel-mounted power analyser
Interface
Gateway
Edge
Output
UMG 96RM-EUMG 96RM-E RS-485
Isolated serial interfaceApproved RS-485-to-host adapter
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeEdge Modbus client
Customer platformMQTT · API · files
Modbus RTU · RS-485
Isolated serial
Runs locally
Optional onward data
Match the configured address and speed. The address list specifies 8 data bits, no parity, two stop bits transmitted by the meter, and one or two stop bits from the external device. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
UMG 96RM-EEthernet and RS-485; external 1 A / 5 A CT inputsUse this map only within its stated firmware and hardware scope.
230 V supply option90–277 V AC, 50/60 Hz, or 90–250 V DC nominal supply rangeVerify the actual auxiliary-supply label independently of the voltage measurement inputs.
24 V supply option24–90 V AC/DC nominal auxiliary supply rangeDo not infer the power-supply rating from the front panel model name alone.

Specifications

The analyser measures three-phase power through external current transformers. It also has residual-current inputs, configurable digital I/O, a local display and internal recording memory. A current-transformer input is not a direct load connection: select the transformer secondary and set the ratio before judging the displayed engineering values.2

Current inputs
External ../1 A or ../5 A current transformers2
Active energy accuracy
Class 0.5 with ../5 A transformers; Class 1 with ../1 A transformers, as stated in the manual2
Reactive energy
Class 22
Interfaces
Ethernet and RS-485 Modbus RTU; Ethernet web server2
Base register encoding
Big-endian; alternate little-endian address bank at base + 327681
Transformer scaling
FLOAT and integer values include configured ratios; SHORT values require the corresponding transformer factor1
Register update
200 ms, distinct from the selected network polling interval1
Installation
Panel mounted; -10 to +55 °C; IP40 front, IP20 rear, IP54 front with the specified seal2

Interface

Documented measurements and integration boundaries for UMG 96RM-E.

  • Phase-to-neutral and phase-to-phase voltage, phase currents and calculated neutral current.
  • Phase and total active, reactive and apparent power, power factor and frequency.
  • Energy counters in documented float or integer formats; retain their declared units.
  • Harmonics, averages, minimum/maximum values and time-stamped limits from the appropriate address blocks.
  • Residual-current measurements when the additional inputs and suitable transformers are actually installed.

Assessment

UMG 96RM-E, using the June 2024 address list for firmware 3.01 onward and hardware release 104. Confirm installed revisions before using this map; UMG 96RM without the E suffix is a different interface scope.

InteroperabilityWell supported
Published Ethernet/serial services and a versioned address list define functions, formats and alternate byte-order access.12
AccuracySupported with conditions
The manual states different active-energy classes for 5 A and 1 A CT secondaries and documents transformer-dependent measurements.12
SecurityLimited
A user password protects configuration access, but that does not establish encrypted or authenticated Modbus transport. Keep the measurement network controlled.2
ReliabilitySupported with conditions
The manual documents internal recording memory, a battery-backed clock and diagnostic functions; a client must still detect stale communications.2
RuggednessSupported with conditions
Panel protection and the -10 to +55 °C operating range are specified; rear terminals require a suitable enclosure.2
ScalabilitySupported with conditions
Ethernet and addressed serial access support multi-meter systems. The 200 ms register update does not imply every shared bus can poll that quickly.12
LifecycleSupported with conditions
The map identifies minimum firmware and hardware revisions, allowing an installation to retain a reproducible version contract.1

Setup

Read the manufacturer’s L1-N voltage address

The operating manual gives the FC03 request at decimal address 19000. Use the current address list to interpret its two-register FLOAT value.

Function
FC03 Read Holding Registers
PDU start
19000 decimal, 0x4A38; use the physical address directly
Length
2 registers, four data bytes
Decode
IEEE-754 float32, big-endian; V, multiplier 1, offset 0
Independent vector
A simulated 230.0 V value is 0x43660000, returned as words 0x4366, 0x0000.
Request PDU
03 4A 38 00 02; the client adds the TCP header or RTU address and CRC
Alternate bank
The map documents little-endian access at base + 32768. This example uses the normal base address and must not also select that bank.

Acceptance: The operating manual’s abbreviated reply illustration is not a complete consistent FLOAT frame; this guide uses its request and the address list’s data definition, with an independently calculated test vector. Confirm actual live voltage against the display before adding other measurements.

  1. Check the hardware, firmware and CTs

    Record the E suffix, hardware release and firmware. Match the June 2024 map scope, then check the configured current and voltage transformer ratios against the installed instruments. Never open an energised CT secondary to perform a communications check.

  2. Choose the transport explicitly

    For Ethernet, use Modbus TCP framing on port 502. Port 8000 is a separate RTU-over-Ethernet service. For RS-485, match the meter address and supported speed with 8 data bits and no parity; keep one master on the bus.

  3. Read the documented voltage address

    Read FC03, PDU address 19000 (0x4A38), length two registers. Decode big-endian IEEE-754 float32 in volts with multiplier 1. Use the independent vector below to test the software decoder.

  4. Avoid applying transformer ratios twice

    The float and integer lists already include the configured ratios. Use multiplier 1 for the documented float voltage/current units. The SHORT lists behave differently and require the corresponding ratio, so do not mix formats within an imported point definition.

  5. Compare fresh values and retain the map

    Compare phase voltage, current and total power with the display. Check signs and missing data before setting alarms. Keep the firmware, map revision and selected address bank with the point definitions and repeat these checks after replacement.

Common questions

Why is my current too high by the CT ratio?
Check whether the point comes from the FLOAT or integer address list. Those values already include the configured transformer ratios. Multiplying again in Edge double-scales the current. SHORT measurements require different treatment.1
Is port 8000 another Modbus TCP port?
The manual lists 502 for Modbus TCP and 8000 for Modbus RTU over Ethernet. These use different framing, so changing only the port in a TCP client does not make it an RTU-over-Ethernet client.2
Can this map be used on every UMG 96RM?
The referenced map is specifically for UMG 96RM-E, firmware 3.01 onward and hardware release 104. Match the installed variant and revision rather than assuming all 96RM products share interfaces and addresses.1