Lovato DME D330

Power and energy meter

DMED330 is a four-module meter for three-phase systems with or without neutral. It uses external CTs, an isolated serial interface and a programmable tariff input. Edge can read local electrical measurements over Modbus RTU; the standard DMED330 and the separate MID version must be identified correctly.

Lovato DME D330 DIN-rail meter and terminal arrangement
  • Modbus RTU

Power and energy meter

Ask an engineer

Compatibility

Compatible with EpiSensor Edge over Modbus RTU

Lovato documents the built-in serial interface, read functions, register lengths and integer scaling for DMED330.

Standard DMED330 with CT insertion. Use operating manual I444IGB09_22 and the DMED330 column of protocol I315IGB08_22. Confirm the installed code, firmware, CT ratio and wiring, then compare one read with the display before extending the poll.

Connect it with

For the built-in DMED330 serial interface

  • Modbus
  • Edge
  • Platforms
Power and energy meter
Interface
Gateway
Edge
Output
DME D330DMED330 RS-485 terminals
Isolated serial interfaceApproved RS-485-to-host adapter
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeModbus client + register map
Customer platformMQTT · API · files
Modbus RTU · RS-485
Isolated serial
Runs locally
Optional onward data
Set the actual node, speed, data format and stop bits from menu M07. Select Modbus RTU. Follow the manufacturer’s A/B/SG bus and termination arrangement and keep one master on each segment. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
DMED330CT-connected, non-expandable DIN-rail meter with isolated RS-485 and a tariff/control input.The serial port is built in; an external serial interface connects it to the Gateway.
DMED330MID / DMED310T2 / DMED320Separate ordering variants or models within the shared communications manual.Use the DMED330 applicability column and its scales. Do not infer MID approval or an Ethernet port from the family manual.

Specifications

Use the full I444 operating manual for settings and limits. I446 is the separate quick installation document still linked by Lovato. The meter is powered from its measurement voltages; its tariff input is a separate control circuit.13

Exact model
DMED330; standard CT model, distinct from DMED330MID.23
Current inputs
CT secondary configurable for 1 A or 5 A; rated current 5 A, maximum 6 A.1
Measurement supply
Rated 220–240 VAC L-N / 380–415 VAC L-L; operating range 187–264 VAC L-N / 323–456 VAC L-L, with or without neutral.1
Energy accuracy
Active energy class 0.5S to IEC/EN/BS 62053-22. CT and installation errors are additional.1
Serial configuration
M07 selects node, 1200–115200 bit/s, data format, one/two stop bits and protocol. Defaults are node 01, 9600 bit/s, 8N1 and Modbus RTU.1
Installation envelope
Four DIN modules, 71.6 mm wide; indoor −25 to +55 °C and humidity below 80%. Front IP40, terminals IP20; the manual requires an enclosure rated at least IP51.1

Interface

Documented measurements and integration boundaries for DME D330.

  • L1 voltage: printed 0002H, PDU 0001H, two unsigned registers divided by 100 for V. L1 current: printed 0008H, PDU 0007H, two unsigned registers divided by 10000 for A.
  • L2 active power: printed 0016H, PDU 0015H, two signed registers divided by 100 for W. Frequency: printed 0032H, PDU 0031H, two unsigned registers divided by 1000 for Hz on DMED330.
  • The table 4 energy totals, including import/export active energy at printed 1B20H/1B24H, use four registers each. Edge’s Modbus client does not read these 64-bit values. Keep those totals on the meter display instead of taking half a counter.

Assessment

Standard DMED330 on its built-in isolated serial port, using the DMED330 model column.

InteroperabilityWell supported
The public Modbus RTU table specifies read functions, address conversion, widths and model applicability for the built-in interface.12
AccuracySupported with conditions
CT ratio and wiring settings determine the electrical reading. The manual specifies class 0.5S active energy, but four-register energy totals exceed Edge’s Modbus read width.12
SecurityLimited
Two password levels protect settings and a programmable input can lock them. Plain Modbus RTU still needs restricted physical and network access; use a read-only monitoring configuration.12
ReliabilitySupported with conditions
Measurement voltages supply the device. The manual describes retained HI and maximum-demand values and an EEPROM configuration backup. Maintain the documented supply and installation conditions.1
RuggednessSupported with conditions
The manual specifies −25 to +55 °C, humidity below 80%, 15g shock and 0.7g vibration tests. Indoor installation needs an enclosure rated at least IP51 around the IP40 front/IP20 terminals.1
ScalabilitySupported with conditions
Selectable serial speed, unique node addressing and a documented repeater topology support multiple meters. The protocol caps a read at 80 registers; start with complete individual values and budget the bus load.12
LifecycleSupported with conditions
The full operating manual, quick installation guide and model-specific protocol remain published together. Local parameter backup and restore are documented; retain the installed CT and serial settings with the device record.13

Setup

Reproduce the manufacturer’s L2-power example

Protocol I315IGB08_22 pages 3–4 gives a complete FC04 request and answer; table 2 confirms the DMED330 signed two-word quantity.

Function
FC04 Read Input Registers
PDU address and length
0016H − 1 = 0015H = 21 decimal; 2 registers
Request PDU
04 00 15 00 02
Manufacturer example data
00 01 FB 00 → signed 129792 / 100 = 1297.92 W = 1.29792 kW
Acceptance
Compare with instantaneous L2 active power on the meter display, including the sign and unit.

Acceptance: These bytes reproduce Lovato’s documentation example, not an EpiSensor device capture. The RTU client adds its configured slave address and CRC. Do not reinterpret the integer as FLOAT32.

  1. Confirm the installed CT circuit

    Have the authorised installer check CT primary/secondary settings P01.01/P01.02 and connection type P01.05. Wiring changes require the isolation and CT-secondary short-circuiting precautions in the manufacturer’s manual.

  2. Match the serial parameters

    Read M07 parameters P07.01–P07.05 and match them in Edge. Use the RTU setting and an 8-bit data format; the manual reserves 7-bit formats for ASCII.

  3. Translate the table address once

    For L2 active power, printed address 0016H becomes PDU 0015H, decimal 21. Read two registers with FC04. The manual allows FC03 and FC04 for its measurement table; this check follows its FC04 example.

  4. Decode the signed value and compare

    Read the two words in the manufacturer’s order as one signed 32-bit integer. Divide by 100 for W, then by 1000 for kW. Compare with the simultaneous instantaneous L2-power display. Apply the DMED330 frequency divisor of 1000, not the 310/320 divisor of 100.

Common questions

Are I444 and I446 competing revisions?
They are different documents for DMED330. The product page links I444IGB09_22 as the full operating manual and I446IGB09_17 as the quick installation manual. Use I444 for the complete parameter and technical tables.13
Why is a frequency value ten times too large?
The shared map specifies Hz/100 for DMED310T2 and DMED320, but Hz/1000 for DMED330. Use the D330-specific scale and retain both words.2
Does the standard model establish billing approval?
The standard DMED330 and DMED330MID are distinct product identities. The standard model’s metering accuracy class does not establish the MID variant’s certification or acceptance of an Edge monitoring installation for billing.23