Janitza UMG 604-PRO
Power quality analyser
A DIN-rail analyser with four voltage and current inputs, Ethernet and configurable serial roles. Read its own measurements without confusing a Modbus server with a downstream gateway.
- Modbus RTU
Power quality analyser
Compatibility
Compatible through Modbus RTU
Janitza documents a local RS-485 measurement interface with the functions, address and data format used in this read-only setup.
UMG 604-PRO with the May 2024 user manual and August 2023 address list for firmware 5.028 and higher. The earlier UMG604 uses a different manual and is outside this guide. Worked commissioning uses the meter’s RS-485 server role, not its master or transparent-gateway role.
Connect it with
-
Modbus Interface ZMB-3XFrom €399 ex VAT Configure Modbus Interface
-
Gateway ZGW-20From €899 ex VAT Configure Gateway
For the analyser’s own documented server interface
- Modbus
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| UMG 604-PRO, firmware 5.028+ | DIN-rail analyser with RS-485 and Ethernet | This read uses its RS-485 server role. |
| UMG604 without PRO | Earlier product | Use its own firmware and documentation; no automatic template extension. |
| UMG604-PRO in master or gateway mode | A different communications role | Do not change the operating role on a working bus merely to run this example. |
Specifications
UMG 604-PRO is intended for 35 mm DIN-rail installation and provides four voltage and four current measurement inputs, a temperature input and digital I/O. Its two-button display and integrated Ethernet support a different operating arrangement from a large front-panel analyser. The manual describes local recording of transients longer than 50 microseconds as well as electrical measurements; polling an instantaneous power register does not retrieve those recorded transients.1
- Mounting
- 35 mm DIN rail1
- Measurement inputs
- Four voltage and four current inputs; one temperature input1
- Interfaces
- RS-485, RS-232 and Ethernet; Modbus TCP port 502 is documented1
- RS-485 operating modes
- 0: RTU server; 1: RTU master; 2: transparent gateway1
- Digital I/O
- Two digital inputs and two digital outputs1
- Recording boundary
- Manual describes transients longer than 50 µs; the worked read does not retrieve event records1
- Operating temperature
- -10 to +55 °C1
- Selected read
- FC04, literal address 19026, two-register Float in W2
- Byte-order banks
- Printed addresses use big-endian data; add 32768 for the little-endian copy.2
Interface
Documented measurements and integration boundaries for UMG 604-PRO.
- Instantaneous phase voltage and current with the configured measurement ratios.
- Signed active power and separately identified energy counters.
- Model-specific power-quality quantities, distinct from archived event records.
- A physical measurement channel and timestamp retained with every collected value.
Assessment
UMG 604-PRO with the May 2024 user manual and August 2023 address list for firmware 5.028 and higher. The earlier UMG604 uses a different manual and is outside this guide. Worked commissioning uses the meter’s RS-485 server role, not its master or transparent-gateway role.
- InteroperabilitySupported with conditions
- The model-specific manual and map define an open serial measurement path; firmware and interface role must match.12
- AccuracySupported with conditions
- The manual defines measurement inputs and capability boundaries. Transformer selection, variant and installation remain part of system accuracy.12
- SecurityNot yet assessed
- No authenticated or encrypted telemetry claim is established for this RS-485 path.12
- ReliabilityNot yet assessed
- Local recording is described, but continuous end-to-end collection and automatic historical backfill are not established.12
- RuggednessSupported with conditions
- The manual states an indoor/cabinet installation and -10 to +55 °C operating range; this is not an outdoor enclosure claim.12
Setup
Read total active power
The exact model’s address list places total active power at decimal 19026 as Float in W. The selected instantaneous float includes configured transformer factors.
- Read PDU
- 04 4A 52 00 02: FC04, address 19026, quantity 2.
- Synthetic decoder payload
- C4 BB 80 00 decodes as big-endian IEEE754 float32 to -1500.0 W.
- Alternate bank
- 19026 + 32768 = 51794 (0xCA52) gives the documented little-endian representation.
- Scaling
- Use the selected Float’s stated engineering unit. Do not apply the configured transformer ratio twice.
Acceptance: These bytes are an independent synthetic decoder example, not a device capture. Verify actual identity, complete response width, selected byte-order bank and agreement with the measurement reference before accepting the reading.
-
Identify the exact instrument
UMG 604-PRO with the May 2024 user manual and August 2023 address list for firmware 5.028 and higher. The earlier UMG604 uses a different manual and is outside this guide. Worked commissioning uses the meter’s RS-485 server role, not its master or transparent-gateway role.
-
Verify the measuring configuration
Check the installed voltage and current transformer ratios, wiring system and phase association. The selected instantaneous Float readings include transformer factors; do not transfer that assumption to every integer energy or alternate-format table.
-
Match the serial role and framing
Read the configured Modbus address, baud rate and serial framing. For UMG604-PRO, use the documented server role only if it matches the intended installation; do not reconfigure an existing master or gateway as a trial.
-
Read the complete documented quantity
Read FC04 at decimal 19026 (0x4A52), quantity 2, for total active power. Use the printed big-endian bank with a matching Float32 decoder. These are literal map addresses: do not subtract one.
-
Prove the measurement before expanding
Compare the result with the instrument or a suitable simultaneous reference. Check phase and power direction under a known operating condition, then add documented points with their own widths and units. Keep missing/stale readings separate from zero. Recorded events require a separate retrieval path.
Common questions
- Why can the correct serial address still fail?
- Check the RS-485 operating mode. The manual distinguishes RTU server, RTU master and transparent gateway. A client polling the analyser’s own values needs the server role used here; an existing master or gateway deployment needs its own integration plan.1
- Does the power value need the CT ratio again?
- The selected instantaneous Float entry includes the configured transformer factors. Validate those ratios on the device and do not multiply them a second time in Edge. Other formats and energy tables must be checked independently.1
- Can polling download the transient records?
- An ordinary instantaneous register read does not request the recorded event or transient history. Keep those separate from the read-only telemetry collection described here.1
- Why can a different format need different scaling?
- The map offers several representations. Its general notes distinguish instantaneous Float and short formats, while individual energy tables can add their own ratio and unit rules. Read the definition of the selected entry rather than multiplying every value by the CT ratio.2
Sources
- UMG 604-PRO user manual and technical data (opens in a new tab) (PDF)
- UMG 604-PRO Modbus address list and formulary (opens in a new tab) (PDF)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.











