Johnson Controls SNE2200
Building automation controller
For an NAE55 replacement serving two field buses, request a separate device inventory for each bus. At Release 11.0 a trunk with third-party devices has a limit of 64. A lightly loaded second trunk does not increase capacity on the first.
Compatibility
Compatible with Edge over BACnet/IP
The SNE exposes BACnet objects on the building network. Edge can collect measurements that the controls contractor has made available on the engine.
Obtain one accessible object and its source from the commissioned Metasys point list.
Connect it with
For points exposed by the commissioned SNE
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| M4-SNE22000-0 and M4-SNE22001-0 | BACnet/IP on Ethernet with two MS/TP field buses. | Johnson Controls identifies M4-SNE22001-0 as the Release 11.0 replacement for M4-SNE22000-0. BTL listing 30658-1 covers both order codes at firmware 11.0.0.1516. |
Specifications
The following limits apply to Metasys Release 11.0. Count existing devices and planned additions before allocating capacity.1
Interface
Documented measurements and integration boundaries for SNE2200.
- Ask for the object identifier and Units of the energy or power reading already displayed in Metasys. Point instances are assigned in the site project.
- If the contractor supplies an object on the field device itself, record that device’s identity and routed network separately from objects hosted by the SNE.
Assessment
SNE2200 serving project-defined BACnet objects.
- InteroperabilityWell supported
- The BTL listing includes BACnet/IP and the two named hardware variants.3
- AccuracyNot yet assessed
- Measurement accuracy depends on the instrument behind the object.2
- SecurityNot yet assessed
- The site owner controls access to the engine and the building network.1
- ReliabilityNot yet assessed
- The listing records tested protocol capabilities.3
- RuggednessNot yet assessed
- Confirm the environment of the installed control panel.1
- ScalabilitySupported with conditions
- Release 11.0 allows 600 devices across integrations, subject to individual trunk limits.1
- LifecycleSupported with conditions
- The model table identifies the replacement order code for the earlier hardware.1
Setup
-
Identify the installed order code, software release, engine Device instance and meter tag.
-
Read Present_Value and Units on one exported analog measurement.
Compare its value and timestamp with the same reading in Metasys. Check that a power value in kW has not been labelled as energy in kWh.
-
Count the two field buses separately and identify which bus supplies each reading.
Sources
- Metasys System Configuration Guide 11.0, SNE series network engines (opens in a new tab)
- SNE/SNC protocol implementation statement for firmware 11.0 (opens in a new tab) (PDF)
- BTL listing 30658-1, firmware 11.0.0.1516 (opens in a new tab) (PDF)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.