Johnson Controls SNE110L
Building automation controller
The L suffix matters when expanding an existing site. Release 11.0 supports ten BACnet/IP devices on the SNE110L, compared with 100 on the SNE1100. Johnson Controls specifies the ADS-Lite-A parent server and identifies selected sales regions. For a UK or US project, confirm regional availability before ordering.
Compatibility
Compatible with Edge over BACnet/IP
The SNE exposes BACnet objects on the building network. Edge can collect measurements that the controls contractor has made available on the engine.
Obtain one accessible object and its source from the commissioned Metasys point list.
Connect it with
For points exposed by the commissioned SNE
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| M4-SNE110L0-0 and M4-SNE110L1-0 | BACnet/IP on Ethernet with one MS/TP field bus. | Johnson Controls identifies M4-SNE110L1-0 as the Release 11.0 replacement for M4-SNE110L0-0. BTL listing 30658-1 covers both order codes at firmware 11.0.0.1516. |
Specifications
The following limits apply to Metasys Release 11.0. Count existing devices and planned additions before allocating capacity.1
Interface
Documented measurements and integration boundaries for SNE110L.
- Ask for the object identifier and Units of the energy or power reading already displayed in Metasys. Point instances are assigned in the site project.
- If the contractor supplies an object on the field device itself, record that device’s identity and routed network separately from objects hosted by the SNE.
Assessment
SNE110L serving project-defined BACnet objects.
- InteroperabilityWell supported
- The BTL listing includes BACnet/IP and the two named hardware variants.3
- AccuracyNot yet assessed
- Measurement accuracy depends on the instrument behind the object.2
- SecurityNot yet assessed
- The site owner controls access to the engine and the building network.1
- ReliabilityNot yet assessed
- The listing records tested protocol capabilities.3
- RuggednessNot yet assessed
- Confirm the environment of the installed control panel.1
- ScalabilitySupported with conditions
- Release 11.0 allows 110 devices across integrations, subject to individual trunk limits.1
- LifecycleSupported with conditions
- The model table identifies the replacement order code for the earlier hardware.1
Setup
-
Identify the installed order code, software release, engine Device instance and meter tag.
-
Read Present_Value and Units on one exported analog measurement.
Compare its value and timestamp with the same reading in Metasys. Check that a power value in kW has not been labelled as energy in kWh.
-
Check the ADS-Lite-A parent server and ten-device BACnet/IP limit on the L variant.
Sources
- Metasys System Configuration Guide 11.0, SNE series network engines (opens in a new tab)
- SNE/SNC protocol implementation statement for firmware 11.0 (opens in a new tab) (PDF)
- BTL listing 30658-1, firmware 11.0.0.1516 (opens in a new tab) (PDF)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.