Honeywell CIPer Model 50

Building automation controller

Honeywell documents CIPer Model 50 as a Niagara 4 BACnet building controller, and it is compatible with EpiSensor Edge over BACnet/IP. Public user guide 31-00198-03 explains its separated Ethernet networks, serial-port roles, Panel Bus polling and measured load examples. Start with the commissioned network and one existing station value, then compare its unit and update timing before adding more points. Niagara and the controller application retain plant control.

  • BACnet/IP
  • BACnet MS/TP

Building automation controller

Ask an engineer

Compatibility

Compatible with EpiSensor Edge over BACnet/IP

Edge’s BACnet/IP client reads the objects the commissioned Niagara station exposes on the controller’s Ethernet network. Honeywell documents the BACnet B-BC profile and BACnet/IP and BACnet MS/TP transports, and user guide 31-00198-03 gives network and update-rate starting points. Object identifiers come from the installed station, not a factory point map. BACnet MS/TP is not an Edge route.

Use product data 31-00197-03 and user guide 31-00198-03, Rev 07-2021. Site check: record the installed order code, Niagara version and station identity, then compare one selected value with the Niagara point view. Keep the existing network, application and control configuration unchanged.

Connect it with

When the commissioned Niagara station exposes the required points as BACnet objects on Ethernet

  • BACnet
  • Edge
  • Platforms
Building automation controller
Interface
Gateway
Edge
Output
CIPer Model 50CIPer Model 50 BACnet/IP objects
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeEdge BACnet/IP client
Customer platformMQTT · API · files
BACnet/IP
Protected Ethernet
Runs locally
Optional onward data
Connect the Gateway to the approved internal network that carries the station’s BACnet/IP traffic on UDP port 47808; Honeywell excludes Internet exposure of that port. Read the station’s device and object identifiers, then compare one value, its unit and its update time with the Niagara point view. Edge reads only; Niagara keeps command priority. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
CIPer Model 50Honeywell publishes BACnet/IP, BACnet MS/TP, Niagara 4, 26 onboard I/O terminations and panel-bus expansion for plant-controller applications.Edge reads the station’s BACnet/IP objects on the commissioned Ethernet network. Object identifiers come from the installed station; compare a first value with the Niagara point view.
CIPer Model 30 and CIPer Model 10Separate CIPer controllers with different hardware, switching, I/O and application roles.Do not reuse the Model 50 identity, capacity or network assumptions for another CIPer model.
XL-500 and XL-800 retrofit installationsHoneywell describes Model 50 as able to reuse existing panel-bus I/O in retrofit work.Treat the retained field I/O, controller station and exposed BACnet objects as project evidence. Retrofit capability does not create a fixed object map.

Specifications

Honeywell identifies CIPer Model 50 as a Niagara 4 plant controller for multi-protocol applications, with a configurable display and expansion for up to 2,500 points.1234

Exact family
CIPer Model 50 plant controller; record the exact order code and hardware revision12
Framework
Niagara 412
Published BACnet transports
BACnet/IP and BACnet MS/TP1
Onboard I/O
26 terminations according to the product brochure2
Expansion statement
Up to 2,500 points; actual station capacity and exposed objects depend on licence, drivers, engineering and installed I/O1
Edge route
BACnet/IP client reading the station’s exposed objects; object identifiers and access settings come from the installed station1234

Interface

Documented measurements and integration boundaries for CIPer Model 50.

  • Potential room, plant, flow, temperature, pressure, energy and equipment-state observations depend on the commissioned Niagara station and BACnet object schedule.
  • Record each approved BACnet device and object identifier, object type, engineering unit, source sensor or meter, update behavior and quality indication.
  • Keep alarms, schedules, histories and derived values distinct from live physical measurements and preserve their Niagara source and time basis.
  • Setpoints, commandable objects, priority-array writes, overrides, alarm acknowledgements, schedules, logic, outputs and equipment commands remain outside this guide.

Assessment

CIPer Model 50 read over BACnet/IP by Edge’s BACnet/IP client, using selected commissioned station points and a read-only comparison; no control.

InteroperabilitySupported with conditions
Honeywell identifies the B-BC profile, BACnet/IP and BACnet MS/TP, and Edge reads BACnet/IP as a client. Object identities come from station engineering rather than a universal factory table.134
AccuracyNot yet assessed
The station can contain local, integrated and derived points, but the public sources do not state source accuracy, units or quality behavior for a project point.2
SecurityNot yet assessed
The manual limits BACnet to internal networks or VPN, and product data describes Niagara read/write user rights. Those user rights do not give an external BACnet client authenticated privileges.134
ReliabilityNot yet assessed
The user guide supplies 10s default Panel Bus polling, CPU-load guidance and example MS/TP update delays. Use these to judge freshness and load, and keep timestamps so a lost connection shows as stale data.234
RuggednessSupported with conditions
Honeywell identifies EN 60730-1, EN 60730-2-9, UL 60730 and UL 916 certifications, while installation ratings still require the exact hardware documentation.1
ScalabilitySupported with conditions
Honeywell states expansion for up to 2,500 points, but licences, drivers, network load and exposed objects bound the actual project.1
LifecycleSupported with conditions
Honeywell retains the product and controller-family material, but exact market availability, Niagara support and authorised service status must be checked for the installed unit.12

Setup

  1. Record the exact installed controller

    Record the order code, Niagara version, station name and licensed drivers. Use the actual network settings: the manual defaults are Ethernet 1 at 192.168.200.20/24 and Ethernet 2 at 192.168.201.20/24, on separated networks. They are identification clues, not addresses to impose on an existing site.

  2. Select one existing station point

    Open the existing Niagara graphical point view and select an identified physical temperature or meter reading. Record its station path, displayed value, unit and source. A synthetic 23.4 °C display means 23.4 °C, not a raw register needing another scale. If that point is already exposed over BACnet, retain its actual device/object identifiers and compare an external read with this same view. Ask for an export only when the station does not expose the required point.

  3. Protect the controls network

    Use the approved internal Ethernet network or VPN; Honeywell explicitly excludes Internet exposure of BACnet port 47808. RS485-1 is isolated, RS485-2 is not; each may already serve Panel Bus, BACnet MS/TP or Modbus. Preserve its assigned role and termination. Niagara user permissions are distinct from BACnet network access.

  4. Prove a small observation set

    Compare repeated readings against the station and physical source at the same time. Panel Bus Normal polling defaults to 10s, so a faster external poll cannot make its source fresher. The manual reports occasional MS/TP update delays in its example tests and recommends keeping CPU load below 80%. Inspect current load and point timing before expanding; these examples are not a universal external-client capacity.

Common questions

Can Edge monitor CIPer Model 50 over BACnet/IP?
Yes. Edge’s BACnet/IP client reads the objects the commissioned station exposes, and the public manuals provide a practical network and point-comparison starting point. Use the installed station’s object identities and compare a read with Niagara. A firmware-matched universal object schedule is not needed to start.134
Does the 2,500-point statement mean every point is available to Edge?
No. It is a controller expansion statement. The available BACnet objects depend on licence, installed drivers, station engineering, point exposure, network policy and the commissioned application.12
Can Edge write HVAC setpoints or schedules through this guide?
No. The CIPer controller and authorised BMS remain responsible for plant logic and command priority. This guide releases no write, override, alarm acknowledgement, schedule change or equipment command.2

Sources

  1. CIPer Model 50 Controller product page (opens in a new tab) Honeywell Building Automation
  2. CIPer Controllers product brochure 01-00112 (opens in a new tab) (PDF) Honeywell Building Automation
  3. CIPer Model 50 user guide 31-00198-03, Rev 07-2021 (opens in a new tab) (PDF) Honeywell Building Automation
  4. CIPer Model 50 product data 31-00197-03 (opens in a new tab) (PDF) Honeywell Building Automation

Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.