LOYTEC LDALI-ME201-U / LDALI-ME202-U / LDALI-ME204-U
Lighting automation controller
For a lighting retrofit, identify the DALI channel and group that serve each area. The three controllers have different channel counts and bus supply ratings. Their BACnet energy accumulators report estimates for groups or channels.
Compatibility
Compatible with Edge over BACnet/IP
Edge reads commissioned objects from the controller on BACnet/IP. A controller operating on MS/TP needs an IP route.
Check the configured network mode and obtain the object schedule. For a BACnet/SC installation, identify a site-provided BACnet/IP route for collection.
Connect it with
For a commissioned BACnet/IP interface
- BACnet
- Edge
- Platforms
For a controller on a serial trunk
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| LDALI-ME201-U | 1 DALI channel. | Guaranteed built-in bus supply of 230 mA per channel. Match the channel assignment to the lighting schedule. |
| LDALI-ME202-U | 2 DALI channels. | Guaranteed built-in bus supply of 230 mA per channel. Match the channel assignment to the lighting schedule. |
| LDALI-ME204-U | 4 DALI channels. | Guaranteed built-in bus supply of 116 mA per channel. Match the channel assignment to the lighting schedule. |
Interface
Documented measurements and integration boundaries for LDALI-ME201-U / LDALI-ME202-U / LDALI-ME204-U.
- The accumulator represents estimated energy for a DALI group or channel. Record its units, membership and time interval. For measured consumption, identify a circuit meter covering the same lighting load.
- A supported illuminance sensor can expose lux through an Analog Input. Keep the sensor location with the reading so a corridor sensor is compared with the correct area.
Assessment
LDALI-ME201-U and LDALI-ME202-U and LDALI-ME204-U over BACnet/IP or routed MS/TP.
- InteroperabilityWell supported
- Listing 31461 covers this controller family at firmware 8.6.2
- AccuracySupported with conditions
- The accumulator represents estimated energy for a DALI group or channel. Record its units, membership and time interval. For measured consumption, identify a circuit meter covering the same lighting load.1
- SecurityNot yet assessed
- The site network mode and access arrangements depend on the installation.1
- ReliabilityNot yet assessed
- The BTL listing documents protocol conformance.2
- RuggednessNot yet assessed
- Confirm installation conditions for the controller enclosure.1
- ScalabilitySupported with conditions
- The datasheet specifies 64 luminaires per DALI channel.1
- LifecycleNot yet assessed
- The datasheet identifies the individual order codes.1
Setup
-
Choose one occupied lighting area and identify its channel, group and commissioned sensor object.
-
Read Present_Value and Units from the lux Analog Input.
Compare it with the same sensor value in the commissioning interface under steady lighting.
-
For a consumption quote, record which areas have circuit meters and which offer only the controller estimate.