ComAp InteliMains 210

Mains supervision controller

InteliMains 210 supervises the mains connection and associated switchgear in a generator installation. It belongs at the mains or tie-breaker part of the plant model. It does not replace the engine controller on each generating set.

InteliMains 210 controller
  • Modbus RTU
  • Modbus TCP

Mains supervision controller

Compatibility

Documented Modbus RTU and TCP interface

Integrated isolated RS-485; optional CM-Ethernet or CM-RS232-485 communication modules

The MCB, MGCB and BTB applications describe different breaker arrangements. ComAp identifies InteliMains 210 G2 as the successor to this discontinued model.

Connect it with

Route into Edge

When the documented monitoring interface is fitted and configured

  • Modbus
  • Edge
  • Platforms
Mains supervision controller
Interface
Gateway
Edge
Output
InteliMains 210InteliMains 210
Isolated serial interfaceApproved RS-485-to-host adapter
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeEdge Gateway
Customer platformMQTT · API · files
Modbus RTU · RS-485
Isolated serial
Runs locally
Optional onward data
Record the active MCB, MGCB or BTB application in InteliConfig. Export the Modbus table and label observations by the actual mains, group or bus-tie breaker position rather than applying generator names to every value. The customer-platform output is optional; Edge remains the local system of record.

When the documented monitoring interface is fitted and configured

  • Modbus
  • Edge
  • Platforms
Mains supervision controller
Interface
Gateway
Edge
Output
InteliMains 210InteliMains 210
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeEdge Gateway
Customer platformMQTT · API · files
Modbus TCP
Protected Ethernet
Runs locally
Optional onward data
Record the active MCB, MGCB or BTB application in InteliConfig. Export the Modbus table and label observations by the actual mains, group or bus-tie breaker position rather than applying generator names to every value. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
InteliMains 210Integrated isolated RS-485; optional CM-Ethernet or CM-RS232-485 communication modulesRecord the active MCB, MGCB or BTB application in InteliConfig. Export the Modbus table and label observations by the actual mains, group or bus-tie breaker position rather than applying generator names to every value.

Specifications

The MCB, MGCB and BTB applications describe different breaker arrangements. ComAp identifies InteliMains 210 G2 as the successor to this discontinued model.12

Plant role
Mains supervision controller1
Monitoring and configuration
Integrated isolated RS-485; optional CM-Ethernet or CM-RS232-485 communication modules2
Model distinction
The MCB, MGCB and BTB applications describe different breaker arrangements. ComAp identifies InteliMains 210 G2 as the successor to this discontinued model.12
Panel protection
IP65 front panel and IP20 rear; standard operating temperature -20 to +70 °C.2

Interface

Documented measurements and integration boundaries for InteliMains 210.

  • Mains electrical measurements and configured power quantities
  • Mains or bus-tie breaker position and controller mode
  • Mains supervision alarms and application-specific group status

Assessment

Integrated isolated RS-485; optional CM-Ethernet or CM-RS232-485 communication modules

InteroperabilitySupported with conditions
Integrated isolated RS-485; optional CM-Ethernet or CM-RS232-485 communication modules12
AccuracySupported with conditions
The documentation identifies electrical and operating measurements for this plant role. CT configuration and measurement location determine how those values are used.12
SecurityNot yet assessed
The cited documentation does not establish an authenticated, encrypted Edge monitoring connection.
ReliabilityNot yet assessed
The controller application distinguishes operating conditions and alarms. Retain communication availability alongside the plant readings.
RuggednessSupported with conditions
IP65 front panel and IP20 rear; standard operating temperature -20 to +70 °C.2
ScalabilityNot yet assessed
Assign one device identity per controller and keep generator, mains and busbar measurements separate.
LifecycleSupported with conditions
Retain the exact model documentation and configuration when replacing a controller or communication module.12

Setup

  1. Record the active MCB, MGCB or BTB application in InteliConfig.

    Export the Modbus table and label observations by the actual mains, group or bus-tie breaker position rather than applying generator names to every value.

  2. Record CT ratios and the physical measurement location.

    Compare the first electrical values with the controller display before using them in totals or trends.

  3. Keep missing responses distinct from a stopped generator.

    Store communication availability beside running state so a disconnected cable does not look like healthy standby.

  4. Build a read-only point list for monitoring.

    Remote start, synchronisation and breaker operation require a separate control design with the existing panel interlocks and feedback.