DEIF AGC 150 Stand-alone

Generator set controller

AGC 150 Stand-alone is a non-synchronising controller for one generator set. DEIF publishes an exact datasheet, a Modbus server user manual and a separate current Modbus table. The interface supports read and write functions, so a monitoring deployment must explicitly allow only the required reads.

  • Modbus TCP
  • Modbus RTU

Generator set controller

Compatibility

Documented AGC 150 Modbus server

DEIF publishes an exact-model Modbus server manual for TCP and serial connections plus a versioned server table. Edge can act as a read-only Modbus client after the installed software version and current table are matched.

AGC 150 Stand-alone generator controller, datasheet 4921240619-F1 and Modbus server user manual 4189341435-D. This is the non-synchronising stand-alone variant, not AGC 150 Hybrid, ATS, Engine drive or an ASC controller. Use only read functions and the current DEIF table. Do not issue start, stop, breaker, mode, parameter or I/O writes.

Connect it with

Route into Edge

When the Ethernet service is enabled on a protected control network

  • Modbus
  • Edge
  • Platforms
Generator set controller
Interface
Gateway
Edge
Output
AGC 150 Stand-aloneAGC 150 Stand-alone
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeEdge Gateway
Customer platformMQTT · API · files
Modbus TCP
Protected Ethernet
Runs locally
Optional onward data
Use the configured controller address and Modbus TCP server. Build the point list from the current DEIF table for the installed software and restrict the client to read functions. The customer-platform output is optional; Edge remains the local system of record.

When an RS-485 port is assigned to the Modbus server

  • Modbus
  • Edge
  • Platforms
Generator set controller
Interface
Gateway
Edge
Output
AGC 150 Stand-aloneAGC 150 Stand-alone
Isolated serial interfaceApproved RS-485-to-host adapter
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeEdge Gateway
Customer platformMQTT · API · files
Modbus RTU · RS-485
Isolated serial
Runs locally
Optional onward data
Match the controller's serial settings and server address, use an isolated interface, and keep write function codes disabled in the client and network design. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
AGC 150 Stand-alone generatorEthernet, USB, two RS-485 ports, CAN A ECU and CAN B PMSUse the exact stand-alone Modbus server documents and installed software version.
AGC 150 Hybrid, ATS, Engine drive and marine variantsDifferent applications, I/O and documentationDo not reuse this model scope or table without exact variant evidence.
AGC 150 Remote DisplayDisplay accessory rather than the generator controllerConnect monitoring to the controller interface defined by DEIF, not to a similarly named display.

Specifications

The Modbus manual documents both reads and writes. Monitoring clients must use an allowlist of read-only table entries rather than exposing the complete server surface.23

Application
One genset in non-synchronising island, AMF or open-transition load take-over operation2
Modbus transports
Modbus TCP server and serial Modbus server on configured communications ports3
Read functions
Coils, discrete inputs, holding registers and input registers are documented; configurable read-only input-register area is available3
Write boundary
Single and multiple coil/register writes are documented by DEIF but excluded from this guide3
Communications
Ethernet, USB, two RS-485 ports and two CAN interfaces2
Supply and environment
8 to 36 V DC continuous; -40 to +70 °C operating range; IP65 front when installed with the supplied gasket2

Interface

Documented measurements and integration boundaries for AGC 150 Stand-alone.

  • Generator voltage, current, frequency, active power, reactive power, apparent power and power factor from current table entries.
  • Engine speed, run hours, battery voltage, oil pressure, coolant temperature and available ECU observations.
  • Controller mode, generator and mains status, breaker feedback, alarms and communication status as read-only observations.
  • Parameters, coils, outputs, start, stop and breaker commands exist in the broader server interface but remain outside this guide.

Assessment

AGC 150 Stand-alone with current DEIF Modbus server table and explicit read-only client policy; no operational writes.

InteroperabilityWell supported
DEIF publishes the exact controller datasheet, Modbus server manual, supported functions and a separate current address table.123
AccuracySupported with conditions
Three-phase measuring circuits and generator and engine values are documented; CT/VT setup and the current address table govern interpretation.23
SecurityLimited
Password levels and protected configuration are documented, but Modbus exposes write functions and does not establish encrypted or authenticated sessions.23
ReliabilitySupported with conditions
Supply, environmental, EMC, diagnostics and alarm functions are documented; client loading and recovery still require commissioning checks.2
RuggednessSupported with conditions
The datasheet publishes panel-front IP65, temperature, humidity, vibration, shock and installation limits.2
ScalabilitySupported with conditions
Two serial ports and Ethernet support several architecture choices, while address management and polling load remain site responsibilities.23
LifecycleWell supported
DEIF maintains an exact product documentation hub with versioned manuals, tables, certificates and configuration material.1

Setup

  1. Confirm the controller label says AGC 150 Stand-alone and record its application, software version and DEIF configuration archive.

    Obtain the current English Modbus server table from the cited documentation page.

  2. Have the generator engineer enable and assign one monitoring interface.

    Record TCP or serial settings and preserve the control owner's network and breaker design.

  3. Create a small read-only allowlist from the exact table revision.

    Exclude all write functions, coils or registers that can change mode, start state, breaker state, parameters or physical outputs.

  4. Read controller identity, operating mode and a small measurement set.

    Compare generator voltage, frequency, power and run state with the AGC display in a safe operating state.

  5. Test loss and restoration of communications without changing controller operation.

    A successful read proves the data path, not physical generator or breaker action.

Common questions

Is AGC 150 Stand-alone a synchronising controller?
No. DEIF describes this variant as a non-synchronising controller for one genset. Other AGC 150 variants need their own exact documentation.2
Why is there no worked register read here?
DEIF publishes the current address table as a separate versioned spreadsheet. This guide avoids freezing one register without binding the installed software and table revision together.13
Can Edge use Modbus to start the genset?
The protocol documents write functions, but this guide deliberately limits Edge to monitoring. Generator and breaker control require a separate engineered and physically witnessed acceptance process.23