ComAp InteliLite 4 AMF 25

Single-generator AMF controller

InteliLite 4 AMF 25 manages one standby or prime-power generator. Its built-in isolated RS-485 port makes it a useful starting point for generator monitoring. Ethernet is an optional communication module, rather than a standard socket on every controller.

InteliLite 4 AMF 25 controller
  • Modbus RTU
  • Modbus TCP

Single-generator AMF controller

Compatibility

Documented Modbus RTU and TCP interface

Integrated RS-485 for Modbus RTU; optional Ethernet communication module for Modbus TCP

The AMF 25 has onboard RS-485. The AMF 20 needs a communication module for this serial path. Select modules by the controller order code, not by front-panel appearance.

Connect it with

Route into Edge

When the documented monitoring interface is fitted and configured

  • Modbus
  • Edge
  • Platforms
Single-generator AMF controller
Interface
Gateway
Edge
Output
InteliLite 4 AMF 25InteliLite 4 AMF 25
Isolated serial interfaceApproved RS-485-to-host adapter
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeEdge Gateway
Customer platformMQTT · API · files
Modbus RTU · RS-485
Isolated serial
Runs locally
Optional onward data
In InteliConfig, save the application file, select the monitoring port and export the configurable Modbus table. Keep the table with its value names, addresses, types and scaling beside the Edge point list. The customer-platform output is optional; Edge remains the local system of record.

When the documented monitoring interface is fitted and configured

  • Modbus
  • Edge
  • Platforms
Single-generator AMF controller
Interface
Gateway
Edge
Output
InteliLite 4 AMF 25InteliLite 4 AMF 25
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeEdge Gateway
Customer platformMQTT · API · files
Modbus TCP
Protected Ethernet
Runs locally
Optional onward data
In InteliConfig, save the application file, select the monitoring port and export the configurable Modbus table. Keep the table with its value names, addresses, types and scaling beside the Edge point list. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
InteliLite 4 AMF 25Integrated RS-485 for Modbus RTU; optional Ethernet communication module for Modbus TCPIn InteliConfig, save the application file, select the monitoring port and export the configurable Modbus table. Keep the table with its value names, addresses, types and scaling beside the Edge point list.

Specifications

The AMF 25 has onboard RS-485. The AMF 20 needs a communication module for this serial path. Select modules by the controller order code, not by front-panel appearance.12

Plant role
Single-generator AMF controller1
Monitoring and configuration
Integrated RS-485 for Modbus RTU; optional Ethernet communication module for Modbus TCP2
Model distinction
The AMF 25 has onboard RS-485. The AMF 20 needs a communication module for this serial path. Select modules by the controller order code, not by front-panel appearance.12
Panel protection
IP65 front panel and IP20 rear; standard operating temperature -20 to +70 °C.2

Interface

Documented measurements and integration boundaries for InteliLite 4 AMF 25.

  • Generator and mains voltage, frequency and three-phase electrical measurements
  • Engine operating state, run hours and ECU measurements available through the configured application
  • Alarm and breaker indication values in the exported Modbus table

Assessment

Integrated RS-485 for Modbus RTU; optional Ethernet communication module for Modbus TCP

InteroperabilitySupported with conditions
Integrated RS-485 for Modbus RTU; optional Ethernet communication module for Modbus TCP12
AccuracySupported with conditions
The documentation identifies electrical and operating measurements for this plant role. CT configuration and measurement location determine how those values are used.12
SecurityNot yet assessed
The cited documentation does not establish an authenticated, encrypted Edge monitoring connection.
ReliabilityNot yet assessed
The controller application distinguishes operating conditions and alarms. Retain communication availability alongside the plant readings.
RuggednessSupported with conditions
IP65 front panel and IP20 rear; standard operating temperature -20 to +70 °C.2
ScalabilityNot yet assessed
Assign one device identity per controller and keep generator, mains and busbar measurements separate.
LifecycleSupported with conditions
Retain the exact model documentation and configuration when replacing a controller or communication module.12

Setup

  1. In InteliConfig, save the application file, select the monitoring port and export the configurable Modbus table.

    Keep the table with its value names, addresses, types and scaling beside the Edge point list.

  2. Record CT ratios and the physical measurement location.

    Compare the first electrical values with the controller display before using them in totals or trends.

  3. Keep missing responses distinct from a stopped generator.

    Store communication availability beside running state so a disconnected cable does not look like healthy standby.

  4. Build a read-only point list for monitoring.

    Remote start, synchronisation and breaker operation require a separate control design with the existing panel interlocks and feedback.