Cummins PowerCommand 3.3

Paralleling generator set controller

PowerCommand 3.3, also called PCC 3300, combines generator metering, protection and paralleling control. It is compatible with EpiSensor Edge over Modbus RTU: Cummins publishes the RS-485 interface and a detailed PC 3.x register map. Start with the voltage, frequency, power and running-time entries, compare them with the display, and leave the generator’s existing controls in place.

Cummins PowerCommand 3.3
  • Modbus RTU

Paralleling generator set controller

Ask an engineer

Compatibility

Compatible with EpiSensor Edge over Modbus RTU

Cummins connects PCC 3300 and PC 3.3 over Modbus RTU from the RS-485 connector on the generator set control board, and A029X159 issue 26, chapter 13, documents the PC 3.x measurements, scaling and unavailable-value codes for PCC3300 V1 and V2. Edge reads the RS-485 port through a ZMB-31 Modbus Interface or a Gateway serial interface.

Use A029X159 issue 26 (June 2020), chapter 13, as the starting map and compare the first reads with the installed HMI. Site check: record the controller’s existing Modbus address and serial settings before connecting. Read only: no generator, breaker, reset, synchronising, load-share or parameter writes.

Connect it with

When the RS-485 Modbus port on the generator set control board is available for monitoring

  • Modbus
  • Wireless
  • Edge
  • Platforms
Paralleling generator set controller
Interface
Gateway
Edge
Output
PowerCommand 3.3PowerCommand 3.3 RS-485 Modbus port
ZMB-31Modbus RTU to the EpiSensor wireless network
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeModbus client + register map
Customer platformMQTT · API · files
Modbus RTU · RS-485
EpiSensor wireless
Runs locally
Optional onward data
Connect a twisted pair from the RS-485 connector on the generator set control board to a ZMB-31 Modbus Interface or a Gateway serial interface, and ground the cable shield at one end only. Match the control’s Modbus address, baud rate and parity, and keep one Modbus master on the segment. Start with L1-N voltage 40018, total power 40034 and frequency 40044 from chapter 13. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
PowerCommand 3.3 and PCC 3300Cummins identifies PCC 3300 and PC 3.3 as Modbus RTU devices in the PowerCommand Cloud manual, wired from the RS-485 connector on the generator set control board.Edge reads the RS-485 port through a ZMB-31 Modbus Interface or a Gateway serial interface, using the PC 3.x rows of A029X159 issue 26.
PowerCommand 3.3 with Masterless Load DemandAn additional s-CAN network shares information among paralleled generator sets and can support automatic start and stop decisions for up to 16 sets.s-CAN is part of the Cummins controls architecture, not an Edge connection path. Do not attach monitoring equipment or infer command authority from the MLD feature.
Earlier PCC 3100, Detector and PowerCommand 1.x or 2.x controlsCummins treats these as separate controls or upgrade origins, with different communications requirements.Do not transfer a PCC 3300 identity, register assumption or wiring plan to another PowerCommand generation.

Specifications

Cummins describes PowerCommand 3.3 as an integrated generator set monitoring, metering and control system that also performs protection, governing, synchronising, load sharing and power transfer functions.13

Exact family
PowerCommand 3.3, also identified by Cummins as PCC 3300 or PC 3.3; hardware and software revision must be recorded2
Published external interface
Modbus interface; Cummins Cloud documentation connects PCC 3300 and PC 3.3 over Modbus RTU23
Control scope
Integrated voltage regulation, governing, protection, synchronising, load sharing, breaker and power-transfer functions depending on application13
MLD scope
Additional s-CAN information sharing and automatic load-demand operation for up to 16 paralleled generator sets1
Register map
A029X159 issue 26, chapter 13: PC 3.x holding registers, scaling, unavailable-value codes and reads of up to 40 contiguous registers4

Interface

Documented measurements and integration boundaries for PowerCommand 3.3.

  • Documented PC 3.x entries include L1-N voltage 40018 (unsigned, 1 V), total power 40034 (signed, 1 kW), and frequency 40044 (unsigned, Modbus-specific 0.1 Hz).
  • Engine running time spans 40070/40071, unsigned 32-bit, high word first, scaled by 0.1 seconds. The map also defines engine observations and fault/status entries; select the rows marked PC 3.x.
  • Controller mode, synchronising state, generator and utility breaker feedback, alarms and transfer status must remain observations only and must be traced to the commissioned application logic.
  • Remote start, stop, reset, breaker operation, synchronising, load sharing, voltage and frequency regulation, power setpoints, transfer and all parameter or output writes remain outside this guide.

Assessment

PowerCommand 3.3 or PCC 3300 read over RS-485 Modbus RTU with the PC 3.x map; no operational control.

InteroperabilitySupported with conditions
Cummins documents the RTU path and PC 3.x register definitions; commissioning must use the actual serial settings and applicable rows.234
AccuracySupported with conditions
The PC 3.x map specifies voltage, power, running time and data-quality codes, enabling explicit decoding and a local HMI comparison.124
SecurityNot yet assessed
The retained sources describe no authentication, encryption, client allow-listing or privilege separation on the controller’s Modbus interface. Keep the RS-485 segment inside the panel and the connection read only.2
ReliabilitySupported with conditions
The map distinguishes unavailable, sensor-range, network and component failure values. Communications loss and recovery still need a site check.124
RuggednessSupported with conditions
Cummins describes PowerCommand controls as designed for generator set environments. Take the environmental ratings from the installed control and generator set documentation.1
ScalabilitySupported with conditions
PC 3.x supports reads of up to 40 contiguous registers per request. Use small blocks and check response time before increasing the polling load.124
LifecycleSupported with conditions
Cummins publishes a detailed multi-controller map and upgrade information. Retain the used document revision with the site point list.234

Setup

  1. Record the exact control identity

    Photograph the generator set and controller nameplates. Record the generator model and serial number, PCC 3300 hardware and software revision, HMI revision, application mode and installed communications option.

  2. Use the published PC 3.x map

    A029X159 issue 26 is publicly available. Chapter 13 specifies PC 3.x and covers PCC3300V1/V2; use only the applicable rows. Its holding-register references follow the 4xxxx convention: reference 40018 corresponds to zero-based wire offset 17. A client using one-based offsets uses 18. Start with a small FC03 read and compare with the HMI.

  3. Separate monitoring from operation

    Have the generator controls owner define a read-only point allowlist and protected communications segment. Exclude all start, stop, reset, breaker, synchronising, load-share, transfer, setpoint, parameter and output writes.

  4. Read voltage and power

    Start with voltage and power. For L1-N voltage use FC03, wire offset 17, quantity 1, PDU 03 00 11 00 01; synthetic 00 E6 gives 230 V. Total power uses wire offset 33, quantity 1: synthetic FF F6 decodes as signed -10 kW. Frequency reference 40044 uses wire offset 43: raw 500 gives 50 Hz using the row’s explicit Modbus multiplier 0.1, not the 0.01 shown for the other data link. Compare stable readings with the HMI.

Common questions

Can Edge read a PowerCommand 3.3 over Modbus RTU?
Yes. Cummins documents the RS-485 Modbus RTU interface, and the public PC 3.x map gives the holding-register rows, address convention and quality codes. Connect the port through a ZMB-31 or a Gateway serial interface, then compare voltage and power with the local HMI.234
Does this guide allow remote generator or breaker control?
No. PowerCommand 3.3 integrates generator, breaker, synchronising, load-share and transfer functions, but this guide authorises no operational write. Any control project requires a separate engineered, interlocked and physically witnessed acceptance process.13
Is the Masterless Load Demand s-CAN network an Edge interface?
No. Cummins describes s-CAN as a controls network that shares information among MLD-capable generator sets. Edge reads the control over its RS-485 Modbus RTU port instead.1