For a pump set with one ACH580 per motor, label each drive with its pump duty and panel location. Price the connection using the interface already fitted. Several drives on one serial segment can share a BACnet router.
Compatibility
Compatible with Edge over BACnet
ACH580 supports BACnet MS/TP through a site router. ABB also specifies the FBIP-21 adapter for BACnet/IP.
Record the fitted option and the serial network or Ethernet connection.
Connect it with
For a drive on an existing serial network
- BACnet
- Edge
- Platforms
For an installed FBIP-21
- Wired
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| ACH580 | Embedded BACnet MS/TP. | BTL lists this serial interface at software 19.00. |
| ACH580 with FBIP-21 | BACnet/IP over Ethernet. | Use the adapter object table in ABB manual revision D for the example below. |
Interface
Documented measurements and integration boundaries for ACH580.
- On the FBIP-21, Analog Value 4 reports output current in amperes. Current can show a change in motor load, while input energy consumption requires a separate measurement.
Assessment
ACH580 monitoring on a building network.
- InteroperabilityWell supported
- BTL identifies the embedded MS/TP route at software 19.00.3
- AccuracyNot yet assessed
- ABB defines the feedback quantity and unit.1
- SecurityNot yet assessed
- Site network access controls require a separate review.1
- ReliabilityNot yet assessed
- The listing covers protocol operation.3
- RuggednessNot yet assessed
- Select the enclosure for the panel location.1
- ScalabilitySupported with conditions
- Several drives can share a routed serial network. Include trunk capacity in the site survey.3
- LifecycleSupported with conditions
- Retain the tested software version and installed interface with the asset record.3
Setup
-
Record the equipment tag, Device instance, interface and load served.
-
With the FBIP-21 fitted, read Present_Value at AV4 during steady pump operation.
Compare amperes with motor current on the drive display and retain the pump tag with the reading.
-
Save the object identifier, units and timestamp alongside the local reading.
Sources
- FBIP-21 adapter user manual, revision D (opens in a new tab) (PDF)
- FBIP-21 compatible drives (opens in a new tab)
- ACH580 serial interface listing, software 19.00 (opens in a new tab) (PDF)