Danfoss VLT HVAC Drive FC 102
HVAC variable frequency drive
An FC 102 on the building’s serial network may already provide motor current, frequency and an energy counter. Before pricing an option card, ask whether the drive uses native BACnet on its main control board or an installed MCA 109.
Compatibility
Compatible with Edge through a BACnet router
The FC 102 native BACnet interface uses MS/TP. Edge collects exposed drive objects through a site BACnet router.
Identify the installed interface, MS/TP trunk and Device instance before comparing a read with the local display.
Connect it with
For the commissioned MS/TP interface
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| FC 102 native BACnet | RS-485 on main control board terminals 68 and 69. | Use the native object table for the commissioned interface. |
| FC 102 with MCA 109 | Optional BACnet fieldbus card. | Record the fitted card and request its own point schedule before assigning object instances. |
Interface
Documented measurements and integration boundaries for VLT HVAC Drive FC 102.
- On the native interface, AV 5 is motor current in amperes, AV 25 is frequency in Hz and AV 23 is the energy counter in kWh.
- The native table expresses output speed (AV 3) as a percentage. Use AV 25 when the requested trend is frequency.
Assessment
Danfoss VLT HVAC Drive FC 102 on a routed MS/TP network.
- InteroperabilitySupported with conditions
- The manufacturer documents the MS/TP interface.1
- AccuracySupported with conditions
- On the native interface, AV 5 is motor current in amperes, AV 25 is frequency in Hz and AV 23 is the energy counter in kWh.1
- SecurityNot yet assessed
- Access to the IP-side router depends on the installation.1
- ReliabilityNot yet assessed
- The operating manual describes serial network commissioning.1
- RuggednessNot yet assessed
- The enclosure and plant-room conditions depend on the installation.1
- ScalabilityNot yet assessed
- Additional units need individual Device instances and sufficient trunk capacity.1
- LifecycleNot yet assessed
- The option matrix identifies the MCA 109.2
Setup
-
Confirm the installed drive is using native BACnet.
Identify the motor and note the time and drive operating condition.
-
Read Present_Value and Units from Analog Value 5.
Compare the result in amperes with motor current on the drive display during steady operation.
-
For consumption reporting, compare the change in AV 23 with the change in the drive’s kWh counter over the same interval.
Sources
- VLT HVAC Drive native BACnet operating instructions, MG.14.C1.02 (opens in a new tab) (PDF)
- VLT FC series options and compatibility, AU310741645108en-000201 (opens in a new tab) (PDF)