Yaskawa Z1000

HVAC variable frequency drive

The Z1000 and Z1000 Bypass both have embedded BACnet MS/TP. Identify which unit serves each point before pricing fan monitoring. The drive and the bypass have separate BACnet listings and can represent different operating conditions.

Yaskawa Z1000 standalone HVAC drive with front keypad and ventilated side panel
  • BACnet MS/TP

HVAC variable frequency drive

Ask an engineer

Compatibility

Compatible with Edge over BACnet

Z1000 has an embedded MS/TP port. A BACnet router carries its objects to the IP network used by Edge.

Identify the panel that publishes bypass status and the router serving its trunk.

Connect it with

For a drive on an existing serial network

  • BACnet
  • Edge
  • Platforms
HVAC variable frequency drive
Interface
Gateway
Edge
Output
Z1000Z1000
BACnet routerRoutes the field segment to the building IP network.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Obtain the router network number, drive Device instance and serial settings from the controls contractor. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
Z1000Embedded BACnet MS/TP.BTL lists Z1000 at software 1.7 for the serial connection.
Z1000 BypassEmbedded BACnet MS/TP.BTL lists Z1000 Bypass at software 1.2 for the serial connection.

Interface

Documented measurements and integration boundaries for Z1000.

  • Track bypass operating mode alongside the drive feedback to distinguish a stopped motor from one powered through the bypass.
  • Read the Device object’s Model_Name and Firmware_Revision and keep them with the point list for this asset.

Assessment

Z1000 in a building automation network.

InteroperabilityWell supported
The listing identifies the embedded MS/TP interface at software 1.7.3
AccuracyNot yet assessed
The project point schedule and operating mode determine which feedback represents the motor.2
SecurityNot yet assessed
Site network access controls require a separate review.2
ReliabilityNot yet assessed
The listing covers protocol operation.3
RuggednessNot yet assessed
Select the enclosure for the panel location.1
ScalabilitySupported with conditions
Several drives can share a routed serial network. Include trunk capacity in the site survey.1
LifecycleSupported with conditions
Retain the tested software version and installed interface with the asset record.3

Setup

  1. Record the nameplate, equipment tag, Device instance and connection used.

  2. Read Object_List from the Device object.

    Match the required feedback object to the installer’s point schedule and read its Present_Value.

  3. For a bypass panel, ask for operating mode alongside drive output frequency.

    Use a recorded interval in bypass to check whether the status captures motor operation during that interval.