Yaskawa HV305
HVAC variable frequency drive
A compact HV305 in a fan cabinet can join an existing serial trunk without an option card. If the panel specification calls for a separate Ethernet drop, include the MB variant of the BACnet/IP option in the quote.
Compatibility
Compatible with Edge over BACnet
HV305 has an embedded MS/TP port. A BACnet router carries its objects to the IP network used by Edge.
Confirm JOHB-SMP3-MB in CN5 if the quote assumes direct BACnet/IP.
Connect it with
For a drive on an existing serial network
- BACnet
- Edge
- Platforms
For a drive fitted with JOHB-SMP3-MB
- Wired
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| HV305 | Embedded BACnet MS/TP. | BTL lists HV305 at software 2.01 for the serial connection. |
| HV305 with JOHB-SMP3-MB | BACnet/IP option in CN5. | Allow for an Ethernet connection to the drive panel. |
Interface
Documented measurements and integration boundaries for HV305.
- Use the actual output frequency for fan duty. The frequency reference represents the requested value.
- Read the Device object’s Model_Name and Firmware_Revision and keep them with the point list for this asset.
Assessment
HV305 in a building automation network.
- InteroperabilityWell supported
- The listing identifies the embedded MS/TP interface at software 2.01.3
- AccuracyNot yet assessed
- The project point schedule and operating mode determine which feedback represents the motor.2
- SecurityNot yet assessed
- Site network access controls require a separate review.2
- ReliabilityNot yet assessed
- The listing covers protocol operation.3
- RuggednessNot yet assessed
- Select the enclosure for the panel location.1
- ScalabilitySupported with conditions
- Several drives can share a routed serial network. Include trunk capacity in the site survey.1
- LifecycleSupported with conditions
- Retain the tested software version and installed interface with the asset record.3
Setup
-
Record the nameplate, equipment tag, Device instance and connection used.
-
Read Object_List from the Device object.
Match the required feedback object to the installer’s point schedule and read its Present_Value.
-
For a fan duty trend, compare actual output frequency with the local monitor during stable operation.
Record the units shown on the keypad.
Sources
- BACnet connections by drive series (opens in a new tab)
- HV305 protocol implementation conformance statement (opens in a new tab) (PDF)
- HV305 MS/TP listing, software 2.01 (opens in a new tab) (PDF)