Yaskawa HV305

HVAC variable frequency drive

A compact HV305 in a fan cabinet can join an existing serial trunk without an option card. If the panel specification calls for a separate Ethernet drop, include the MB variant of the BACnet/IP option in the quote.

Yaskawa HV305 compact drive with its display and operator keypad
  • BACnet MS/TP
  • BACnet/IP

HVAC variable frequency drive

Ask an engineer

Compatibility

Compatible with Edge over BACnet

HV305 has an embedded MS/TP port. A BACnet router carries its objects to the IP network used by Edge.

Confirm JOHB-SMP3-MB in CN5 if the quote assumes direct BACnet/IP.

Connect it with

Route into Edge

For a drive on an existing serial network

  • BACnet
  • Edge
  • Platforms
HVAC variable frequency drive
Interface
Gateway
Edge
Output
HV305HV305
BACnet routerRoutes the field segment to the building IP network.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Obtain the router network number, drive Device instance and serial settings from the controls contractor. The customer-platform output is optional; Edge remains the local system of record.

For a drive fitted with JOHB-SMP3-MB

  • Wired
  • Edge
  • Platforms
HVAC variable frequency drive
Interface
Gateway
Edge
Output
HV305HV305 with JOHB-SMP3-MB
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeProtocol client + point model
Customer platformMQTT · API · files
Ethernet
Protected Ethernet
Runs locally
Optional onward data
Record the card in CN5 and the assigned BACnet/IP network details. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
HV305Embedded BACnet MS/TP.BTL lists HV305 at software 2.01 for the serial connection.
HV305 with JOHB-SMP3-MBBACnet/IP option in CN5.Allow for an Ethernet connection to the drive panel.

Interface

Documented measurements and integration boundaries for HV305.

  • Use the actual output frequency for fan duty. The frequency reference represents the requested value.
  • Read the Device object’s Model_Name and Firmware_Revision and keep them with the point list for this asset.

Assessment

HV305 in a building automation network.

InteroperabilityWell supported
The listing identifies the embedded MS/TP interface at software 2.01.3
AccuracyNot yet assessed
The project point schedule and operating mode determine which feedback represents the motor.2
SecurityNot yet assessed
Site network access controls require a separate review.2
ReliabilityNot yet assessed
The listing covers protocol operation.3
RuggednessNot yet assessed
Select the enclosure for the panel location.1
ScalabilitySupported with conditions
Several drives can share a routed serial network. Include trunk capacity in the site survey.1
LifecycleSupported with conditions
Retain the tested software version and installed interface with the asset record.3

Setup

  1. Record the nameplate, equipment tag, Device instance and connection used.

  2. Read Object_List from the Device object.

    Match the required feedback object to the installer’s point schedule and read its Present_Value.

  3. For a fan duty trend, compare actual output frequency with the local monitor during stable operation.

    Record the units shown on the keypad.

Sources

  1. BACnet connections by drive series (opens in a new tab) Yaskawa
  2. HV305 protocol implementation conformance statement (opens in a new tab) (PDF) Yaskawa
  3. HV305 MS/TP listing, software 2.01 (opens in a new tab) (PDF) BACnet Testing Laboratories

Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.