ABB ACH550

HVAC variable frequency drive

For an existing ACH550-UH fan or pump, ask which router serves the serial trunk. Record any bypass panel separately. A fan running on bypass can draw current while the drive reports zero output frequency.

ABB ACH550 HVAC drive family in several enclosure sizes
  • BACnet MS/TP

HVAC variable frequency drive

Ask an engineer

Compatibility

Compatible with Edge over BACnet

ACH550 supports BACnet MS/TP through a site router.

Use the ACH550-UH object list for the worked check. Identify a bypass controller separately.

Connect it with

For a drive on an existing serial network

  • BACnet
  • Edge
  • Platforms
HVAC variable frequency drive
Interface
Gateway
Edge
Output
ACH550ACH550
BACnet routerRoutes the field segment to the building IP network.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Obtain the router network number, drive Device instance and serial settings from the controls contractor. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
ACH550Embedded BACnet MS/TP.BTL lists this serial interface at software 0511.

Interface

Documented measurements and integration boundaries for ACH550.

  • In the ACH550-UH manual, AV1 reports output frequency in Hz and AV4 reports output current in amperes. These values describe the drive output.

Assessment

ACH550 monitoring on a building network.

InteroperabilityWell supported
BTL identifies the embedded MS/TP route at software 0511.2
AccuracyNot yet assessed
ABB defines the feedback quantity and unit.1
SecurityNot yet assessed
Site network access controls require a separate review.1
ReliabilityNot yet assessed
The listing covers protocol operation.2
RuggednessNot yet assessed
Select the enclosure for the panel location.1
ScalabilitySupported with conditions
Several drives can share a routed serial network. Include trunk capacity in the site survey.2
LifecycleSupported with conditions
Retain the tested software version and installed interface with the asset record.2

Setup

  1. Record the equipment tag, Device instance, interface and load served.

  2. On the ACH550-UH serial interface, read Present_Value at AV1 and compare Hz with drive parameter 0103.

    Record the drive or bypass operating mode with the result.

  3. Save the object identifier, units and timestamp alongside the local reading.

Sources

  1. ACH550-UH user manual, revision E, BACnet analog values (opens in a new tab) (PDF) ABB
  2. ACH550 serial interface listing, software 0511 (opens in a new tab) (PDF) BACnet Testing Laboratories