Pump performance monitoring
Motor electrical input, delivered flow and the pressure either side of the pump, so a drop in power can be explained rather than guessed at.
- Measure
- Motor electrical input, flow, suction and discharge pressure, speed and valve state
- Calculate
- Pump specific energy in kWh per cubic metre, and differential head
- Sensors
- ZIO-22, two 4-20 mA loops on one device, 0.001 mA resolution ZIO-2X datasheet (PDF, opens in a new tab)
- On site
- ZGW-20 Gateway, the calculation, with every input kept beside it ZGW-20 datasheet (PDF, opens in a new tab)
Hardware for pump energy monitoring
One electricity meter at the motor supply, the instruments that are already in the pipework, and the drive if it will talk.
The motor or starter supply, which is the input side of the ratio
- Choose the CT rating for the motor supply: 120 A split-core, or 300 A, 1 kA and 3 kA Rogowski coils
Class 0.5S to IEC 62053-22 with its CTs, 0.1 A to 3 kA
Suction and discharge pressure transmitters, or pressure and flow
0 to 20 mA at 0.001 mA resolution, up to 36 V DC, externally powered loops
Calculates specific energy and head on site, and keeps the raw signals
If the drive has a published register map
Speed, torque estimate and run state from the variable-speed drive
If temperature is part of the condition picture
Bearing housing or fluid temperature beside the electrical trend
±0.2 °C from 0 to 70 °C, ±0.5 °C from −40 to 105 °C
ZIO-22, ZMB-31 and TES-21 share one enclosure with different terminals inside, so the ordering code is what you specify.
What separates a control change from a fault
Power on its own cannot tell you why it fell. These four measurements can.
| Position | What it tells you | Reference | Sensor |
|---|---|---|---|
| Motor supply | Input power, energy, starts and running hours | Declare whether the supply feeds anything besides this pump ZEM-63 datasheet (PDF, opens in a new tab) | ZEM-65 (on this page) |
| Suction and discharge pressure | The differential pressure the pump is producing | Transmitter range, units and elevation recorded per instrument ZIO-2X datasheet (PDF, opens in a new tab) | ZIO-22 (on this page) |
| Flow | The volume actually delivered, which is the denominator of specific energy | Flow meter's own range, zero behaviour and installation requirements | ZIO-22 (on this page), second channel |
| Speed and valve state | Whether the duty point moved because somebody moved it | A commanded speed is not proof of an achieved speed ZMB-3X datasheet (PDF, opens in a new tab) | ZMB-31 (on this page) |
Pressure is not head until the fluid is named. Converting bar to metres needs the fluid's density at its operating temperature, and the elevation of each tapping.
A shared feeder is not a pump measurement. If the supply also feeds a second pump or the auxiliaries, the ratio includes them. Say so, or meter closer to the motor.
How to calculate pump specific energy
Specific energy is the honest comparison between two periods: how much electricity it took to move a cubic metre.
specific energy = P ÷ Q
H = (pd − ps) × 10.2 ÷ SG
- P
- electrical input power, kW
- Q
- delivered flow, cubic metres per hour
- pd, ps
- discharge and suction pressure, bar
- H
- differential head, metres of the fluid
- SG
- fluid specific gravity at the operating temperature
Worked example
A pump drawing 22.0 kW while delivering 140 m³ per hour uses 0.157 kWh per cubic metre. With suction at 1.2 bar and discharge at 4.6 bar on water, the differential head is (4.6 − 1.2) × 10.2 = 34.7 metres.
In Edge
A calculated sensor divides power by flow, with a guard so a stopped pump does not divide by zero, and a second one takes the pressure difference. Keep the run state as its own point so stopped periods can be excluded on purpose.
Commissioning checks
Commission the instruments first: the ratio is only as good as its flow signal.
-
The meter is on this motor
Start and stop the pump and watch the electrical measurement.
Pass when the power follows the pump, and the standing consumption when it is off is explained.
-
Transmitters are zeroed and scaled
Follow each transmitter's own zero and span procedure, then compare its display with the value in Edge.
Pass when both agree at two points, and 4 mA reads as the transmitter's zero rather than as zero flow.
-
Two speeds, one story
Run at two known speeds or valve positions and record power, flow and pressure at each.
Pass when every signal moves in the direction and the order the hydraulics predict.
-
A lost signal is not a low reading
Disconnect one transmitter loop.
Pass when the value is withheld or marked, and specific energy stops rather than rising.
-
The baseline is described
Write down the impeller, fluid, control mode and system condition the baseline period ran in.
Pass when a later comparison can say whether it is comparing like with like.
What this measurement does not tell you
Specific energy is evidence for a question, not the answer to it.
- Affinity laws describe a similar operating point. Where static head or efficiency changes matter, they stop predicting the duty point.
- Monitoring does not replace NPSH, cavitation, minimum-flow or mechanical assessment.
- A changed ratio is a reason to investigate, not proof of a fault or of a saving.
- A flow meter installed against its own requirements produces a confident number that is still wrong.
Sources and related guides
Sources
- Improving pumping system performance (opens in a new tab) US Department of Energy. Pump-system boundaries, flow control and the limits of an assessment based on electrical input alone.
- ZEM-63 Wireless 3-Phase Electricity Monitor datasheet (opens in a new tab) EpiSensor. Specifications, ranges and ordering codes.
Related
- Compressed air energy monitoring Application guide Compressor electricity, delivered flow and header pressure on one reference basis, so specific energy can be compared between periods honestly.
- 4-20 mA remote monitoring for process instruments Application guide Bring current-loop, voltage and temperature signals onto the network with their range, scaling and fault behaviour intact, and prove each one on site.
- Equipment performance monitoring boundaries Knowledge Base Define input, useful output, operating state and time boundaries for pumps, compressors, boilers, chillers and heat pumps.
- 4–20 mA loop voltage and headroom calculator Engineering tool Check a 4–20 mA loop has enough supply voltage at its design current.
Reviewed by EpiSensor Engineering on . Revision 4.
Explain a pump's power draw instead of guessing at it
We will check the signals are usable, size the meter and the CTs, and write the calculation with you.

