Equipment performance

Pump performance monitoring

Motor electrical input, delivered flow and the pressure either side of the pump, so a drop in power can be explained rather than guessed at.

ZEM-65 Wireless 3-Phase Electricity Monitor
ZEM-65Electricity metering
ZIO-22 Analogue Signal Sensor
ZIO-22Analogue inputs
ZGW-20 Gateway
ZGW-20Gateway with Edge
Measure
Motor electrical input, flow, suction and discharge pressure, speed and valve state
Calculate
Pump specific energy in kWh per cubic metre, and differential head
Sensors
ZIO-22, two 4-20 mA loops on one device, 0.001 mA resolution ZIO-2X datasheet (PDF, opens in a new tab)
On site
ZGW-20 Gateway, the calculation, with every input kept beside it ZGW-20 datasheet (PDF, opens in a new tab)

Hardware for pump energy monitoring

One electricity meter at the motor supply, the instruments that are already in the pipework, and the drive if it will talk.

If the drive has a published register map

If temperature is part of the condition picture

ZIO-22, ZMB-31 and TES-21 share one enclosure with different terminals inside, so the ordering code is what you specify.

What separates a control change from a fault

Power on its own cannot tell you why it fell. These four measurements can.

What separates a control change from a faultSuction and discharge pressure have to be measured at known elevations, because the difference between them becomes head. Pump or compressor Inlet Discharge PT PT FM Flow meter Drive or starter Board ZGW-20 GatewayEdge on site ZEM-65 ZIO-22 · suction ZIO-22 · discharge ZMB-31 What separates a control change from a faultSuction and discharge pressure have to be measured at known elevations, because the difference between them becomes head. Pump or compressor Inlet PT Discharge PT FM Drive or starter Board ZGW-20 GatewayEdge on site ZEM-65 ZIO-22 · suction ZIO-22 · discharge ZMB-31
Suction and discharge pressure have to be measured at known elevations, because the difference between them becomes head.
Sensor positions for what separates a control change from a fault
PositionWhat it tells youReferenceSensor
Motor supply Input power, energy, starts and running hours Declare whether the supply feeds anything besides this pump ZEM-63 datasheet (PDF, opens in a new tab) ZEM-65 (on this page)
Suction and discharge pressure The differential pressure the pump is producing Transmitter range, units and elevation recorded per instrument ZIO-2X datasheet (PDF, opens in a new tab) ZIO-22 (on this page)
Flow The volume actually delivered, which is the denominator of specific energy Flow meter's own range, zero behaviour and installation requirements ZIO-22 (on this page), second channel
Speed and valve state Whether the duty point moved because somebody moved it A commanded speed is not proof of an achieved speed ZMB-3X datasheet (PDF, opens in a new tab) ZMB-31 (on this page)
  • Pressure is not head until the fluid is named. Converting bar to metres needs the fluid's density at its operating temperature, and the elevation of each tapping.

  • A shared feeder is not a pump measurement. If the supply also feeds a second pump or the auxiliaries, the ratio includes them. Say so, or meter closer to the motor.

How to calculate pump specific energy

Specific energy is the honest comparison between two periods: how much electricity it took to move a cubic metre.

specific energy = P ÷ Q
H = (pd − ps) × 10.2 ÷ SG
P
electrical input power, kW
Q
delivered flow, cubic metres per hour
pd, ps
discharge and suction pressure, bar
H
differential head, metres of the fluid
SG
fluid specific gravity at the operating temperature

Worked example

A pump drawing 22.0 kW while delivering 140 m³ per hour uses 0.157 kWh per cubic metre. With suction at 1.2 bar and discharge at 4.6 bar on water, the differential head is (4.6 − 1.2) × 10.2 = 34.7 metres.

In Edge

A calculated sensor divides power by flow, with a guard so a stopped pump does not divide by zero, and a second one takes the pressure difference. Keep the run state as its own point so stopped periods can be excluded on purpose.

Commissioning checks

Commission the instruments first: the ratio is only as good as its flow signal.

  • The meter is on this motor

    Start and stop the pump and watch the electrical measurement.

    Pass when the power follows the pump, and the standing consumption when it is off is explained.

  • Transmitters are zeroed and scaled

    Follow each transmitter's own zero and span procedure, then compare its display with the value in Edge.

    Pass when both agree at two points, and 4 mA reads as the transmitter's zero rather than as zero flow.

  • Two speeds, one story

    Run at two known speeds or valve positions and record power, flow and pressure at each.

    Pass when every signal moves in the direction and the order the hydraulics predict.

  • A lost signal is not a low reading

    Disconnect one transmitter loop.

    Pass when the value is withheld or marked, and specific energy stops rather than rising.

  • The baseline is described

    Write down the impeller, fluid, control mode and system condition the baseline period ran in.

    Pass when a later comparison can say whether it is comparing like with like.

What this measurement does not tell you

Specific energy is evidence for a question, not the answer to it.

  • Affinity laws describe a similar operating point. Where static head or efficiency changes matter, they stop predicting the duty point.
  • Monitoring does not replace NPSH, cavitation, minimum-flow or mechanical assessment.
  • A changed ratio is a reason to investigate, not proof of a fault or of a saving.
  • A flow meter installed against its own requirements produces a confident number that is still wrong.

Sources and related guides

Sources

Related

Reviewed by EpiSensor Engineering on . Revision 4.

Explain a pump's power draw instead of guessing at it

We will check the signals are usable, size the meter and the CTs, and write the calculation with you.

Contact us