Integration and instrumentation
4-20 mA remote monitoring for process instruments
Current-loop and voltage instruments read by a mains-powered analogue signal sensor, with the range, the scaling and the fault current recorded beside the value.
- Measure
- 4-20 mA transmitters, 0-10 V signals, process and ambient temperature, and the machine states beside them
- Rule
- Industrial process monitoring keeps the raw signal beside the engineering value
- Sensors
- ZIO-22, two current loops, 0 to 20 mA at 0.001 mA, up to 36 V DC ZIO-2X datasheet (PDF, opens in a new tab)
- On site
- ZGW-20 Gateway, scaling, quality rules and onward integration ZGW-20 datasheet (PDF, opens in a new tab)
Hardware for 0-10 V signal monitoring and current loops
One interface per signal type. Both are mains powered, because a loop input cannot also run on a battery.
Pressure, flow, level and other 4-20 mA transmitters
0 to 20 mA at 0.001 mA resolution, up to 36 V DC, 85 to 264 V AC supply, IP67
Instruments whose output is 0 to 10 V rather than a current loop
0 to 10 V DC at 0.001 V resolution
Scales each signal once, keeps the raw value beside it, and applies the quality rules
Where temperature is part of the measurement
Process, vessel or ambient temperature where a probe can reach it directly
1 waterproof probe, 1.5 m lead
±0.2 °C from −20 to 70 °C, ±0.5 °C from −40 to 105 °C
If the states come from a controller rather than a contact
Machine states and recipe or alarm registers from a controller
ZIO-22, TES-21 and ZMB-31 share one enclosure with different terminals inside, so the ordering code is what you specify.
What travels with an analogue signal
A current is not a measurement until its range, its scaling and its fault behaviour are written down with it.
| Position | What it tells you | Reference | Sensor |
|---|---|---|---|
| Loop-current instruments | Pressure, flow, level and anything else on 4-20 mA | Loop supply, total burden and whether the arrangement sources or sinks ZIO-2X datasheet (PDF, opens in a new tab) | ZIO-22 (on this page) |
| Voltage-output instruments | Signals that arrive as 0 to 10 V | Common reference, input impedance and whether zero volts is a valid reading or a fault ZIO-2X datasheet (PDF, opens in a new tab) | ZVO-20 (on this page) |
| Temperature points | Process, vessel, pipe or ambient temperature at a declared position | Probe construction, immersion and response time matched to the process TES-2X datasheet (PDF, opens in a new tab) | TES-21 (on this page) |
| Machine and controller states | What the plant was doing when the analogue value moved | Documented contacts or verified registers, with the state map recorded ZMB-3X datasheet (PDF, opens in a new tab) | ZMB-31 (on this page) |
Under-range is not zero. A transmitter that fails low reports a current below 4 mA, which is a fault indication and not a reading of zero. Keep it as a fault.
The loop needs the voltage to go round. Transmitter minimum, receiver and cable drops all take a share of the supply. Add them up before you find out on site.
Settings that belong with every analogue point
Each of these is a number from the instrument's datasheet, recorded once and used everywhere.
| Setting | Typical value | Where to check |
|---|---|---|
| Loop supply | 24 V DC, external | The loop's own power supply. The interface reads the current and does not power the loop. |
| Voltage budget | Supply minus transmitter minimum and every drop | The transmitter's minimum terminal voltage and the total cable resistance, before installation. |
| Range | 4 mA and 20 mA endpoints in engineering units | The transmitter's configuration, not the process's expected range. |
| Scaling | Linear between the endpoints | The value in Edge against the transmitter's display at two points. |
| Fault current | Below 3.6 mA or above 21 mA | The transmitter's namur or fault setting, and what Edge does with it. |
| Reporting interval | 1 to 15 minutes | Edge sensor settings, chosen for how fast the process actually moves. |
| Stale threshold | 5 minutes by default | The calculated-sensor settings, where this signal feeds a calculation. |
Commissioning checks
Every one of these is about making a plausible number provable.
-
Each channel is traced end to end
Follow every signal from the instrument tag to the point name and unit in Edge.
Pass when the tag, the wire, the channel and the point name all agree.
-
Two known values are read back
Use the transmitter's simulation mode, or a known process condition, at two points in the range.
Pass when the raw current and the scaled value are both right, with the rounding understood.
-
The loop has headroom
Add up the transmitter minimum, the receiver and the cable drops at 20 mA.
Pass when the supply covers all of them with margin, calculated before installation.
-
A fault reads as a fault
Force the documented fault current, or disconnect the loop.
Pass when Edge shows a fault or a gap rather than an ordinary minimum or maximum reading.
-
Stale data is withheld
Break one signal path for longer than the stale threshold.
Pass when the value stops rather than repeating, and anything calculated from it stops too.
What this measurement does not tell you
The interface reads a signal faithfully. Everything upstream of it is still the instrument's responsibility.
- Monitoring does not certify instrument suitability, hazardous-area protection, functional safety or process containment.
- A protocol or signal type in common does not prove compatibility with a particular model, wiring option or register map.
- Scaling cannot recover accuracy lost to a poor sensor position, an unsuitable range or an unquantified installation error.
- An analogue value carries no quality flag of its own: the fault behaviour has to be configured deliberately.
Sources and related guides
Sources
- Fundamentals of the 4-20 mA current loop (opens in a new tab) NI. Loop supply, receiver burden and the voltage budget a current loop needs.
- Modbus serial line protocol and implementation guide (opens in a new tab) Modbus Organization. Serial-line topology and the commissioning boundaries for a controller read over RS-485.
- ZIO-2X Analogue Signal Sensor datasheet (opens in a new tab) EpiSensor. Specifications, ranges and ordering codes.
Related
- Pump performance monitoring Application guide Electrical input, flow and differential pressure on the same clock, so a change in pump power can be read as speed, demand or degradation.
- Meter integration for a BMS or SCADA system Application guide What Edge reads, what it serves onward, and the settings both ends have to agree on before a register becomes a point in your BMS.
- Commissioning 4–20 mA and 0–10 V monitoring Knowledge Base A field method for loop power, voltage headroom, scaling, fault states, isolation, sampling and acceptance of analogue process signals.
- RTD lead-resistance error estimator Engineering tool Estimate the temperature error that lead resistance adds to a two-wire or three-wire RTD.
Reviewed by EpiSensor Engineering on . Revision 5.
Get the loop budgets and the scaling right first time
We will check the loop budgets, pick the interfaces, and write the scaling down with you.

