Integration and instrumentation

4-20 mA remote monitoring for process instruments

Current-loop and voltage instruments read by a mains-powered analogue signal sensor, with the range, the scaling and the fault current recorded beside the value.

ZIO-22 Analogue Signal Sensor
ZIO-22Current loops
ZGW-20 Gateway
ZGW-20Gateway with Edge
Measure
4-20 mA transmitters, 0-10 V signals, process and ambient temperature, and the machine states beside them
Rule
Industrial process monitoring keeps the raw signal beside the engineering value
Sensors
ZIO-22, two current loops, 0 to 20 mA at 0.001 mA, up to 36 V DC ZIO-2X datasheet (PDF, opens in a new tab)
On site
ZGW-20 Gateway, scaling, quality rules and onward integration ZGW-20 datasheet (PDF, opens in a new tab)

Hardware for 0-10 V signal monitoring and current loops

One interface per signal type. Both are mains powered, because a loop input cannot also run on a battery.

Where temperature is part of the measurement

If the states come from a controller rather than a contact

ZIO-22, TES-21 and ZMB-31 share one enclosure with different terminals inside, so the ordering code is what you specify.

What travels with an analogue signal

A current is not a measurement until its range, its scaling and its fault behaviour are written down with it.

What travels with an analogue signalEach transmitter keeps its own loop supply. The interface reads the current, and the engineering value is calculated once, on the Gateway. Pump or compressor Inlet Discharge PT PT FM Flow meter Drive or starter Board ZGW-20 GatewayEdge on site ZIO-22 · pressure ZIO-22 · flow TES-21 ZMB-31 What travels with an analogue signalEach transmitter keeps its own loop supply. The interface reads the current, and the engineering value is calculated once, on the Gateway. Pump or compressor Inlet PT Discharge PT FM Drive or starter Board ZGW-20 GatewayEdge on site ZIO-22 · pressure ZIO-22 · flow TES-21 ZMB-31
Each transmitter keeps its own loop supply. The interface reads the current, and the engineering value is calculated once, on the Gateway.
Sensor positions for what travels with an analogue signal
PositionWhat it tells youReferenceSensor
Loop-current instruments Pressure, flow, level and anything else on 4-20 mA Loop supply, total burden and whether the arrangement sources or sinks ZIO-2X datasheet (PDF, opens in a new tab) ZIO-22 (on this page)
Voltage-output instruments Signals that arrive as 0 to 10 V Common reference, input impedance and whether zero volts is a valid reading or a fault ZIO-2X datasheet (PDF, opens in a new tab) ZVO-20 (on this page)
Temperature points Process, vessel, pipe or ambient temperature at a declared position Probe construction, immersion and response time matched to the process TES-2X datasheet (PDF, opens in a new tab) TES-21 (on this page)
Machine and controller states What the plant was doing when the analogue value moved Documented contacts or verified registers, with the state map recorded ZMB-3X datasheet (PDF, opens in a new tab) ZMB-31 (on this page)
  • Under-range is not zero. A transmitter that fails low reports a current below 4 mA, which is a fault indication and not a reading of zero. Keep it as a fault.

  • The loop needs the voltage to go round. Transmitter minimum, receiver and cable drops all take a share of the supply. Add them up before you find out on site.

Settings that belong with every analogue point

Each of these is a number from the instrument's datasheet, recorded once and used everywhere.

Settings that belong with every analogue point
SettingTypical valueWhere to check
Loop supply 24 V DC, externalThe loop's own power supply. The interface reads the current and does not power the loop.
Voltage budget Supply minus transmitter minimum and every dropThe transmitter's minimum terminal voltage and the total cable resistance, before installation.
Range 4 mA and 20 mA endpoints in engineering unitsThe transmitter's configuration, not the process's expected range.
Scaling Linear between the endpointsThe value in Edge against the transmitter's display at two points.
Fault current Below 3.6 mA or above 21 mAThe transmitter's namur or fault setting, and what Edge does with it.
Reporting interval 1 to 15 minutesEdge sensor settings, chosen for how fast the process actually moves.
Stale threshold 5 minutes by defaultThe calculated-sensor settings, where this signal feeds a calculation.

Commissioning checks

Every one of these is about making a plausible number provable.

  • Each channel is traced end to end

    Follow every signal from the instrument tag to the point name and unit in Edge.

    Pass when the tag, the wire, the channel and the point name all agree.

  • Two known values are read back

    Use the transmitter's simulation mode, or a known process condition, at two points in the range.

    Pass when the raw current and the scaled value are both right, with the rounding understood.

  • The loop has headroom

    Add up the transmitter minimum, the receiver and the cable drops at 20 mA.

    Pass when the supply covers all of them with margin, calculated before installation.

  • A fault reads as a fault

    Force the documented fault current, or disconnect the loop.

    Pass when Edge shows a fault or a gap rather than an ordinary minimum or maximum reading.

  • Stale data is withheld

    Break one signal path for longer than the stale threshold.

    Pass when the value stops rather than repeating, and anything calculated from it stops too.

What this measurement does not tell you

The interface reads a signal faithfully. Everything upstream of it is still the instrument's responsibility.

  • Monitoring does not certify instrument suitability, hazardous-area protection, functional safety or process containment.
  • A protocol or signal type in common does not prove compatibility with a particular model, wiring option or register map.
  • Scaling cannot recover accuracy lost to a poor sensor position, an unsuitable range or an unquantified installation error.
  • An analogue value carries no quality flag of its own: the fault behaviour has to be configured deliberately.

Sources and related guides

Sources

Related

Reviewed by EpiSensor Engineering on . Revision 5.

Get the loop budgets and the scaling right first time

We will check the loop budgets, pick the interfaces, and write the scaling down with you.

Contact us