RTD lead resistance error calculator

Work out how far lead resistance shifts a Pt100 or Pt1000 reading for 2-wire, 3-wire and 4-wire connections, from the cable or the measured lead resistance.

Sensors and signals Updated Free, no sign-up

Example values
Connection
Wires
Sensor
Sensor
°C

At the operating temperature

Ω/°C
Leads
Lead resistance from
mm²
Ω

Difference between the leads

Ω

Reading error, high

8.982°C

Lead resistance the reading sees
3.448 Ω
Resistance of one lead
1.724 Ω
Pt100 sensitivity at 60 °C
0.3839 Ω/°C

Both leads add to the sensor resistance, so the reading is high.

How it’s calculated
  1. Rlead = ρ × L ÷ A=0.01724 × 50 ÷ 0.5=1.724 Ω
  2. ΔT = 2 × Rlead ÷ S=2 × 1.724 ÷ 0.3839=8.982 °C

A 2-wire Pt100 with 3.448 Ω of lead loop reads 8.982 °C high.

Tip: On a 2-wire Pt100 every ohm of lead loop reads about 2.6 °C high. Three wires cancel most of it; four remove it.

How to work out RTD lead error

An RTD measures temperature by its resistance, so the resistance of the wires to it adds to the reading. On a 2-wire Pt100, every ohm of lead resistance reads about 2.6 °C high. Twenty metres of 0.5 mm² copper, out and back, adds 1.379 Ω and a 3.55 °C error at room temperature.

2-wire

ΔT = 2 × Rlead ÷ S

Both leads are in series with the sensor. S is the sensor’s sensitivity: about 0.385 Ω/°C for a Pt100 and 3.85 Ω/°C for a Pt1000 near room temperature, from the IEC 60751 curve. The error is always high.

3-wire

ΔT = ΔRmismatch ÷ S

The third wire lets the instrument measure one lead and subtract it. Equal leads cancel; only the difference between them remains, from length, joints or terminal resistance.

4-wire

ΔT ≈ 0

Two wires carry the current and two separate wires sense the voltage at the sensor, so lead resistance drops out of the measurement.

Lead resistance for copper is its resistivity, 0.01724 Ω·mm²/m at 20 °C, times the length, divided by the cross-section. It rises about 0.4% per degree with the cable’s own temperature, which is one reason a 2-wire error drifts with the weather.

RTD lead error examples

A 2-wire Pt100 on 20 m of cable

Each 20 m lead of 0.5 mm² copper is 0.6896 Ω, so the loop is 1.379 Ω. At a sensitivity of 0.3885 Ω/°C that reads 3.55 °C high, more than ten times the Class A tolerance at 20 °C.

Reading error, high 3.55 °C Open in the calculator

The same cable with a Pt1000

A Pt1000 has ten times the sensitivity, so the same 1.379 Ω reads only 0.355 °C high. That is why 2-wire connections are usually made with Pt1000 sensors.

Reading error, high 0.355 °C Open in the calculator

A 3-wire Pt100 with a 0.1 Ω mismatch

On a 50 m run the leads are 1.724 Ω each, but only the 0.1 Ω difference between them affects a 3-wire reading: 0.1 ÷ 0.3839 = 0.2605 °C. A loose terminal can add more than that, so check connections at commissioning.

Reading error 0.2605 °C Open in the calculator

2-wire RTD error by cable length

Reading error in °C at 20 °C for 2-wire connections on copper cable, leads out and back.

2-wire RTD error by cable length, values in °C
Cable length (m)Pt100, 0.5 mm² (°C)Pt100, 1.5 mm² (°C)Pt1000, 0.5 mm² (°C)
10.17750.059170.01775
20.3550.11830.0355
50.88750.29580.08875
101.7750.59170.1775
203.551.1830.355
508.8752.9580.8875
10017.755.9171.775

Download this table (CSV)

Questions about RTD lead resistance error

Is 2-wire, 3-wire or 4-wire better?

4-wire is the most accurate, 3-wire is the usual industrial compromise and 2-wire suits short runs or Pt1000 sensors. The instrument decides which it supports.

Why use a Pt1000 instead of a Pt100?

The same lead resistance is ten times smaller relative to the sensor, so lead and connection errors shrink by ten. The trade-off is slightly more susceptibility to leakage and noise at the higher resistance.

Can I correct a 2-wire error in software?

Only for the lead resistance at the temperature you measured it. The cable’s resistance changes with its own temperature, so a fixed offset is right on the day and drifts afterwards.

Limits of this result

  • A 3-wire connection cancels equal leads; the mismatch you enter is what remains.
  • A 4-wire connection removes lead resistance, but not the instrument’s own offset or thermoelectric effects.
  • Add the sensor tolerance, the transmitter accuracy and self-heating separately.

Log the signal continuously

TES sensors use 10 kΩ NTC thermistor probes with the cable fitted at the factory. At 10 kΩ, the resistance of the probe cable is a negligible share of the reading.

Related guides

Sources

  1. RTD measurement system design essentials (opens in a new tab) Analog Devices, technical article, 2016-06-15
  2. IEC 60751 industrial platinum resistance thermometers (opens in a new tab) IEC, IEC 60751:2022 catalogue record