Cold room and cold store temperature monitoring

Probes at the warm and cold points a mapping study found, one in the product zone, and alarms that carry a delay so a door opening is not an incident.

TES-22 Probe Temperature Sensor
TES-22Waterproof probes
ZGW-20 Gateway
ZGW-20Gateway with Edge
Measure
The mapped warm and cold locations, the product zone, and the refrigeration plant's electricity
Good practice
Map the space before choosing permanent positions WHO mapping guide
Sensors
TES-22 waterproof probes, ±0.2 °C in the normal range, down to −40 °C at ±0.5 °C Probe Temperature Sensor datasheet
On site
ZGW-20 Gateway, alarms, records and up to 250 wireless devices Gateway datasheet

Mapping comes before monitoring

A temperature mapping study finds the warmest and coldest parts of a space under loaded, empty, defrost and door-opening conditions. Permanent probes then go where the map says, not where the cable is easiest. Without the map, a probe beside the thermostat reports the thermostat.

Hardware for cold room temperature monitoring

Two probes for the extremes of each space, one for the product zone, and the plant's electricity when the cause matters as much as the effect.

If plant behaviour has to be explained, not only recorded

If the controller has a published register map

Where the probes go in a cold store

Each probe answers a question the mapping study asked. Write the question beside the probe, so a later change of layout can be judged against it.

From field measurement to Edge

Each field signal reaches its named EpiSensor interface, reports through the site Gateway and is handled locally in Edge.

  • Wired
  • Zigbee
  • Edge
  • Platforms
Field measurement
Interface
Gateway
Local Edge
Optional output
Mapped warm location
Mapped cold location
Product zone
Refrigeration electricity
Controller state
TES-22Probe Temperature Sensor
TES-21Probe Temperature Sensor
ZEM-65Wireless 3-Phase Electricity Monitor
ZMB-31Modbus Interface
ZGW-20Gateway
EdgeLocal data, monitoring and rules
Customer platformOptional onward data
Probe measurement
Zigbee mesh
Voltage + CT inputs
Modbus RTU · RS-485
Runs locally
Configured MQTTS / HTTPS
Customer platformOptional onward data
EdgeLocal data, monitoring and rules
ZGW-20Gateway
TES-22Probe measurement
Mapped warm location
Mapped cold location
TES-21Probe measurement
Product zone
ZEM-65Voltage + CT inputs
Refrigeration electricity
ZMB-31Modbus RTU · RS-485
Controller state
Configured MQTTS / HTTPS
Runs locally
Zigbee mesh
Sending data on to a customer platform is optional; Edge keeps working on site without one.
Where the probes go in a cold store
PositionWhat it tells youReferenceSensor
Mapped warm location The worst case the stored product sees Chosen from a documented mapping study, under representative conditions WHO mapping guide TES-22 (on this page), probe 1
Mapped cold location Whether anything is being over-cooled or frozen From the same study, usually in the evaporator's discharge WHO mapping guide TES-22 (on this page), probe 2
Product zone What the load is doing, which lags the air Say whether the probe reads air, a buffer or a product simulation TES-21 (on this page)
Refrigeration electricity Whether a temperature rise came with the plant running or with it stopped One meter on the refrigeration board Wireless 3-Phase Electricity Monitor datasheet ZEM-65 (on this page)
Controller state Defrost and setpoint changes that explain a scheduled excursion Controller registers, with the model and firmware recorded Modbus Interface datasheet ZMB-31 (on this page)
  • Probe the product zone. Air temperature moves in minutes and a pallet moves in hours. A door-opening spike in the air may mean nothing to the load, which is why the alarm carries a delay.

  • Record the defrost state. Keep the controller's defrost state so a regular rise can be recognised instead of investigated every time.

  • Allow ±0.5 °C below −20 °C. Below −20 °C the probe holds ±0.5 °C rather than ±0.2 °C. In a freezer, that is part of the measurement plan.

Alarms and records for a cold store

The rules run on the Gateway, so an alarm does not depend on somebody watching a dashboard.

A temperature outside its limits
A limit rule per probe, with a hold time agreed with the person responsible for the product, so a door opening does not raise an incident.
A probe that stops reporting
A no-data rule flags a silent sensor within a set time, from one minute to a day, because a missing reading is not a good reading.
Who is told, and when
Email, SMS, a webhook or an alert in Edge, with the recipients set per rule. Email and SMS need the Gateway's own settings and a connection.
The record survives the network
Each sensor holds up to 70,000 readings in its own memory. During a bounded outage, that buffer can retain readings for later recovery; retention depends on the reporting interval, outage length and available capacity.

Commissioning checks

Do these before the record is relied on, and repeat the mapping check after any material change.

  • Each probe matches the study

    Photograph every fitted probe and mark its position on the mapping study's drawing.

    Pass when every permanent probe is at a position the study identified.

  • Probes agree with a reference

    Compare each installed probe with a traceable reference instrument at the operating temperature.

    Pass when the differences are inside the tolerance the quality process accepts, and recorded per probe.

  • High, low and silent all alarm

    Force each state in turn: warm one probe, cool another, and remove a battery.

    Pass when all three reach the named recipient, who acknowledges them.

  • The delay is right for the product

    Open the door for a normal loading period and watch whether the rule fires.

    Pass when routine work does not raise an alarm, and a real excursion still does.

  • Time and retention are set

    Check the Gateway's clock, the reporting interval and how long the record is kept.

    Pass when the retention period matches what the quality process requires.

Limits of this measurement

Installing a probe does not turn an unvalidated room into a qualified cold chain.

  • The mapping study, the qualification of the space and the quality process that owns them.
  • The limits themselves: what is acceptable comes from the product and its regulator, not from the sensor.
  • Calibration records, retention periods and the response procedure when an alarm fires.
  • A controller reading is context. It does not replace an independent monitoring point where one is required.

Turn a mapping study into permanent probe positions

An engineer can place the permanent probes against the study, and size the sensors and Gateway for the site.

Build this system