Johnson Controls CVM03050 / CVE03050
Building automation controller
For a variable-air-volume terminal, note the full CV model before promising damper feedback. All three variants have an actuator and differential pressure transducer. Only the two P variants in the model table include a feedback potentiometer.
Compatibility
Compatible with Edge over routed MS/TP or BACnet/IP
CVM uses a BACnet MS/TP field bus in this configuration. CVE can expose points directly to Edge on BACnet/IP.
Record the installed order code, commissioned protocol and Device instance. Confirm the controller’s network mode before selecting the Ethernet route.
Connect it with
For a CVM commissioned on BACnet MS/TP
- BACnet
- Edge
- Platforms
For a CVE commissioned on BACnet/IP
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| M4-CVM03050-0 and M4-CVM03050-0P | BACnet MS/TP via a site router. | BTL listing 31509 names M4-CVM03050-0 and M4-CVM03050-0P at 12.0.1.34. |
| M4-CVE03050-0P | BACnet/IP over Ethernet. Confirm that the site uses BACnet/IP for this route. | BTL listing 31517 names M4-CVE03050-0P at 12.0.1.34. |
Interface
Documented measurements and integration boundaries for CVM03050 / CVE03050.
- Identify the application object for measured airflow, the damper command and any position feedback separately. Damper position alone cannot establish the air volume delivered to the room.
Assessment
Metasys CV 03050 series on the installed network.
- AccuracyNot yet assessed
- The point table describes the available hardware. The installed application determines the BACnet measurement.1
- SecurityNot yet assessed
- Network mode and access controls are site-specific.1
- RuggednessNot yet assessed
- Identify the installed enclosure and terminal or panel location.1
- ScalabilitySupported with conditions
- Match the I/O schedule to the hardware model before adding equipment.1
- LifecycleSupported with conditions
- Record model suffix, application version and commissioned connection with the point list.1
Setup
-
Trace the required measurement from the panel or terminal to its project-assigned BACnet object.
-
Compare the airflow object with a local balancing measurement under the same operating condition.
Record the airflow unit. If damper position is required, check the P suffix and the feedback object independently.
-
Record the Device instance, object identifier, timestamp, Present_Value and applicable units in the handover.
Sources
- Metasys CV controller model table, Release 13.0 (opens in a new tab)
- BTL listing 31509 for Metasys CVM (opens in a new tab) (PDF)
- BTL listing 31517 for Metasys CVE (opens in a new tab) (PDF)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.