Johnson Controls CVM03050 / CVE03050

Building automation controller

For a variable-air-volume terminal, note the full CV model before promising damper feedback. All three variants have an actuator and differential pressure transducer. Only the two P variants in the model table include a feedback potentiometer.

Three CVM03050 and CVE03050 controller variants in the centre of the front row
  • BACnet MS/TP
  • BACnet/IP

Building automation controller

Ask an engineer

Compatibility

Compatible with Edge over routed MS/TP or BACnet/IP

CVM uses a BACnet MS/TP field bus in this configuration. CVE can expose points directly to Edge on BACnet/IP.

Record the installed order code, commissioned protocol and Device instance. Confirm the controller’s network mode before selecting the Ethernet route.

Connect it with

Route into Edge

For a CVM commissioned on BACnet MS/TP

  • BACnet
  • Edge
  • Platforms
Building automation controller
Interface
Gateway
Edge
Output
CVM03050 / CVE03050CVM03050
BACnet routerRoutes the field segment to the building IP network.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Record the field network number and router serving this controller. The customer-platform output is optional; Edge remains the local system of record.

For a CVE commissioned on BACnet/IP

  • BACnet
  • Edge
  • Platforms
Building automation controller
Interface
Gateway
Edge
Output
CVM03050 / CVE03050CVE03050
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet/IP
Protected Ethernet
Runs locally
Optional onward data
Request the active BACnet/IP settings. The manufacturer also documents BACnet/SC, which is a different network configuration. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
M4-CVM03050-0 and M4-CVM03050-0PBACnet MS/TP via a site router.BTL listing 31509 names M4-CVM03050-0 and M4-CVM03050-0P at 12.0.1.34.
M4-CVE03050-0PBACnet/IP over Ethernet. Confirm that the site uses BACnet/IP for this route.BTL listing 31517 names M4-CVE03050-0P at 12.0.1.34.

Interface

Documented measurements and integration boundaries for CVM03050 / CVE03050.

  • Identify the application object for measured airflow, the damper command and any position feedback separately. Damper position alone cannot establish the air volume delivered to the room.

Assessment

Metasys CV 03050 series on the installed network.

InteroperabilityWell supported
Separate listings identify the serial and Ethernet model variants.23
AccuracyNot yet assessed
The point table describes the available hardware. The installed application determines the BACnet measurement.1
SecurityNot yet assessed
Network mode and access controls are site-specific.1
ReliabilityNot yet assessed
The listings cover protocol operation.23
RuggednessNot yet assessed
Identify the installed enclosure and terminal or panel location.1
ScalabilitySupported with conditions
Match the I/O schedule to the hardware model before adding equipment.1
LifecycleSupported with conditions
Record model suffix, application version and commissioned connection with the point list.1

Setup

  1. Trace the required measurement from the panel or terminal to its project-assigned BACnet object.

  2. Compare the airflow object with a local balancing measurement under the same operating condition.

    Record the airflow unit. If damper position is required, check the P suffix and the feedback object independently.

  3. Record the Device instance, object identifier, timestamp, Present_Value and applicable units in the handover.