Zero-export solar monitoring

Measure the point of common coupling with an independent electricity monitor, retain the controller state beside it, and prove whether low PV output was curtailment or a fault.

ZEM-65 Wireless 3-Phase Electricity Monitor
ZEM-65PCC evidence
ZMB-31 Modbus Interface
ZMB-31Controller context
ZGW-20 Gateway
ZGW-20Gateway with Edge
Measure
Import and export at the point of common coupling, PV output, active export limit and controller state
Calculate
Export-limit margin, curtailed intervals and the residual between connection flow, generation and site demand
Sensors
ZEM-65, for independent measurement on a suitable low-voltage connection Wireless 3-Phase Electricity Monitor datasheet
On site
ZGW-20 Gateway, keeps the owner record in Edge without joining the export-control loop Gateway datasheet

Choose an evidence point outside the control loop

Place the owner meter at the same electrical boundary as the agreed import and export limit, while keeping it independent of the controller's own sensor. If the point of common coupling is medium voltage or outside the ZEM-65 rating, acquire a documented read-only value from an approved plant meter instead.

Export limit monitoring hardware

Use one independent connection measurement, read-only controller context and one Gateway. Meter PV feeders separately only when the site record does not already establish generation at the required boundary.

Use an approved plant meter interface where the connection is outside this rated boundary

Only with a documented register map and an available single-master RS-485 bus

Measurements for solar curtailment monitoring

Declare one sign convention before comparing systems. This guide uses import as positive and export as negative. Keep the raw directional quantities as well as any signed net value so a changed convention cannot silently reverse the result.

Keep monitoring beside the certified scheme

This is an owner-side, read-only record. It observes the point of common coupling and the plant controller without becoming a controller, protection function, DSO channel or settlement path.

  • Wired
  • Zigbee
  • Edge
  • Platforms
Field measurement
Interface
Gateway
Local Edge
Optional output
Grid connection
Approved plant controller
ZEM-65Wireless 3-Phase Electricity Monitor
ZMB-31Modbus Interface
ZGW-20Gateway
EdgeOwner history, checks and alerts
Owner's platformOptional onward data
Voltage + CT inputs
Zigbee mesh
Approved Modbus RTU / RS-485
Runs locally
Configured MQTTS / HTTPS
Owner's platformOptional onward data
EdgeOwner history, checks and alerts
ZGW-20Gateway
ZEM-65Voltage + CT inputs
Grid connection
ZMB-31Approved Modbus RTU / RS-485
Approved plant controller
Configured MQTTS / HTTPS
Runs locally
Zigbee mesh
The approved export-limiting scheme retains its own measurement and fail-safe path. The independent owner meter and read-only interface feed Edge separately.
Measurements for solar curtailment monitoring
PositionWhat it tells youReferenceSensor
Point of common coupling Independent import and export evidence against the agreed connection limit Confirm CT direction during a known import and an approved export test ENA G100 ZEM-65 (on this page), owner evidence meter
Export-limiting controller Active limit, operating state, requested reduction, sensor health and alarms Read only documented values; the certified scheme keeps its own sensor and authority NGED ZMB-31 (on this page), documented registers
PV plant output Whether all inverters reduced together, one unit failed or generation stayed below the active limit Use aligned inverter or feeder totals and retain the operating state and alarms IEC 61724-1 ZMB-31 (on this page), plant total and equipment state
  • Zero export is a limit, not a zero reading. Measurement uncertainty, controller deadband, response time and changing site load can leave a small signed exchange. Compare excursions with the approved scheme tolerance and commissioning record.

  • A flat export trace can be healthy curtailment. If connection export holds at the active limit while irradiance remains available and all inverter groups reduce together, the pattern supports curtailment. One inverter falling against its peers, an alarm or export well inside the limit points towards a fault or another constraint.

  • Residuals locate missing evidence. Compare connection flow, PV output and measured site demand over aligned intervals. A residual can come from unmetered loads, storage, transformer loss, timing, CT ratios or different electrical boundaries; investigate it before assigning lost energy.

Diagnose curtailment without joining the control loop

Use aligned connection, plant and controller data to classify events. Preserve the source readings, data age and active limit beside every conclusion.

Test the export-limit margin
Compare fresh connection power with the active limit using the declared sign convention. Record the limit source and effective time; a configured value that arrived late cannot explain an earlier event.
Separate curtailment from equipment faults
Classify an interval as supported curtailment only when the connection is at the limit, available solar remains, plant groups reduce coherently and the controller state agrees. Otherwise retain the event as unexplained or fault-related.
Suppress conclusions from stale inputs
Expose source age and expected-input completeness. If the connection meter or controller data is stale, withhold the curtailment classification instead of carrying the previous state forward as current.
Trend the balance residual
Calculate the aligned difference between connection flow, generation and measured site demand. Alert on a persistent change in the residual, then check timing, scale, direction and missing assets before blaming the controller.

Commissioning checks

Commission the owner record with the site's authorised electrical and controls teams, using the approved export-limitation test plan.

  • The PCC boundary is documented

    Trace the independent meter on the single-line diagram and compare its location with the connection agreement and controller sensor.

    Pass when the owner meter observes the agreed boundary without sharing or altering the controller's measurement path.

  • Direction and scale are proven

    Compare each phase during a known import condition and an approved export condition, then verify CT ratios, units and signed totals.

    Pass when import and export signs, phase order, ratios and energy registers agree with the declared convention.

  • Limit response is time-aligned

    During the approved scheme commissioning test, compare active limit, controller state, plant output and independent PCC power on one clock.

    Pass when the record preserves request, plant response and connection result with enough timing detail for the approved test.

  • Stale data fails visibly

    In an approved test environment, interrupt one monitoring input without disturbing the certified control path.

    Pass when the source becomes stale, the classification is withheld and no old value appears as fresh evidence.

  • Curtailment and faults remain distinct

    Review a limit event and an inverter alarm or outage against irradiance, peer output and the residual.

    Pass when the record explains the evidence for each classification and leaves ambiguous intervals unresolved.

What owner monitoring does not replace

This design supplies independent operational evidence around an approved export-limitation scheme. It has no authority over that scheme.

  • EpiSensor is not the certified export-limiting controller, its fail-safe sensor, interface protection or loss-of-mains protection.
  • The independent owner record does not replace the DSO-approved commissioning procedure, connection agreement, locked settings or required witness tests.
  • It does not become DSO or TSO operational telemetry, a revenue or settlement meter, or proof of market-service delivery.
  • Monitoring alone cannot calculate curtailed energy without a declared counterfactual method and fresh irradiance, availability, limit and plant-state evidence.
  • Any write path to an inverter, EMS or power plant controller requires a separate approved controls design. This guide establishes no EpiSensor write path.

Sources

  1. Engineering Recommendation G100 Issue 2 Amendment 2 (opens in a new tab) Energy Networks Association
  2. Customer Export Limitation Schemes (opens in a new tab) (opens in a new tab) National Grid Electricity Distribution
  3. IEC 61724-1:2021 Photovoltaic system performance, Part 1: Monitoring (opens in a new tab) (opens in a new tab) International Electrotechnical Commission
  4. VDE-AR-N 4105 generation plants on the low-voltage network (opens in a new tab) (opens in a new tab) VDE FNN
  5. Wireless 3-Phase Electricity Monitor datasheet (opens in a new tab) EpiSensor. Specifications, ranges and ordering codes.

Bring the connection agreement and commissioning record

An engineer can map the independent evidence points, check the available read-only interfaces and keep the monitoring path outside the approved control scheme.

Build this system