IKEA VINDSTYRKA E2112

Air quality sensor

A USB-powered Zigbee air quality sensor with a display. It reports PM2.5 from 0 to 1000 µg/m³, a VOC index, temperature and relative humidity, and runs from a 5 V USB-C supply rather than batteries.

IKEA VINDSTYRKA E2112
  • Zigbee

Air quality sensor

Compatibility

Compatible with EpiSensor Edge over Zigbee.

Pair it with the Zigbee radio on an EpiSensor Gateway. Edge reads it locally on the Gateway.

Edge reads 4 values from it, listed under Interface.

Connect it with

Specifications

VINDSTYRKA is IKEA’s air quality sensor, type E2112. It measures fine particles (PM2.5), total volatile organic compounds, room temperature and relative humidity, and shows all four on its own display. The particle sensor covers 0 to 1000 µg/m³. On the display, IKEA colours PM2.5 green from 0 to 35 µg/m³, yellow from 35 to 120 µg/m³ and red above 120 µg/m³, and shows an arrow for whether VOC levels are rising, stable or falling.12

Power
DC supply. 5.0 V DC at up to 1.0 A through USB-C, drawing 0.5 W. The USB power adapter is not included, and the USB cable should be no longer than 3.0 m.1
Measurements
PM2.5, tVOC, temperature, relative humidity2
Particle detection range
0 to 1000 µg/m³1
PM2.5 display bands
Green 0 to 35 µg/m³, yellow 35 to 120 µg/m³, red above 120 µg/m³1
VOC reading over Zigbee
VOC index, 100 = learned average3
Operating temperature
0 to 40 °C1
Operating humidity
0 to 95 % RH1
Power input
5.0 V DC, 1.0 A, 0.5 W, USB-C1
Maximum USB cable length
3.0 m1
Radio
2400 to 2483.5 MHz, 8 dBm output power1
Radio range
10 m in open air1
Dimensions
52 × 59 × 87 mm (W × D × H)2
Enclosure
ABS plastic, indoor use only2
Firmware updates
Over the air3

Where it is used

  • PM2.5 and VOC trends in meeting rooms, small offices and classrooms, next to temperature and humidity.

    Indoor environmental monitoring
  • Checking whether ventilation schedules keep particle levels down in occupied rooms, alongside HVAC energy data.

    HVAC energy monitoring for commercial buildings
  • Particle peaks from nearby kitchens, print rooms or road traffic, in rooms with a socket close by.

Interface

Readings and settings, with units and ranges where IKEA publishes them.

Download
ReadingUnitRange or valuesAccess
Measurements 4
Temperature °C - Read only
Humidity % - Read only
PM2.5 µg/m³ - Read only
VOC index - - Read only

PM2.5 is set to report at least every 2 minutes, and no more often than once a minute, when it changes by 2 µg/m³ or more.4

Readings can be wrong for the first few minutes after power-up, with temperature often reading high, and settle without intervention.3

It cannot join an IKEA TRÅDFRI gateway. That does not affect a Zigbee coordinator such as the EpiSensor Gateway.23

Setup

  1. Open pairing in Edge

    In Edge, open pairing on the Gateway’s Zigbee network. Place the sensor within 10 m of the Gateway or a mains-powered Zigbee router for the join.1

  2. Power it

    Connect a 5 V, 1 A USB power supply to the USB-C socket with a cable no longer than 3.0 m.1

  3. Reset it into pairing

    Quick-press the pairing button 4 times. This factory resets the sensor, and the link icon on the display blinks while it looks for a network.1

  4. Confirm the join

    The link icon stops blinking when the sensor has joined. Check that Edge identifies it as IKEA E2112.3

  5. Check the readings

    Wait a few minutes for the readings to settle, then compare PM2.5, temperature and humidity in Edge with the sensor’s own display.3

Common questions

Does VINDSTYRKA need an IKEA hub to work with Edge?
No. IKEA says it works on its own or connected to a hub, and it joins a standard Zigbee coordinator directly. It pairs with the Zigbee radio on an EpiSensor Gateway without DIRIGERA or the IKEA Home smart app.13
What does the VOC index mean?
It is a relative index, not a concentration. 100 is the sensor’s learned average; lower values mean fewer volatile organic compounds than usual and higher values mean more. Use it to see changes in one room over time.3
How often does it report PM2.5?
At least every 2 minutes, and sooner when PM2.5 changes by 2 µg/m³ or more, but not more often than once a minute. Values are whole numbers.34
Does it run on batteries?
No. It needs a 5 V, 1 A USB supply on its USB-C socket, which IKEA sells separately. It draws 0.5 W.12
Where should it not be installed?
IKEA rates it for indoor use at 0 to 40 °C. Keep it away from wet, damp or very dusty areas, direct sunlight and heat sources, and do not block the air intake and outlet on the back.1