SATEC EM133
Three-phase energy meter
The EM133 is SATEC's DIN-rail multifunction and time-of-use energy meter, measuring three-phase voltage, current, power, energy and harmonics through 5 A or 1 A CTs, SATEC HACS sensors or direct 63 A inputs. The order code sets the current input, the calibration frequency, the resolution and the power supply: an EM133-5A-60HZ-ACDC is the 5 A CT input, calibrated at 60 Hz, with the 40 to 300 V AC/DC supply and the default low resolution. Every EM133 has an RS-485 port, COM1, running Modbus RTU, and an Ethernet module adds a Modbus TCP server on port 502. SATEC numbers its registers in decimal and sends 32-bit values low word first, in units set by the device resolution and the energy decimal places.
Compatibility
Compatible with EpiSensor Edge over Modbus RTU or Modbus TCP
The EM133 is compatible with EpiSensor Edge over Modbus RTU on its built-in COM1 RS-485 port, read through a ZMB-31 Modbus Interface or a Gateway serial port, and over Modbus TCP on port 502 when the Ethernet module is fitted. SATEC publishes the register map with decimal addresses, data types, low-word-first word order, units and worked conversions.
EM133, EM133-XM and EM133-MID with any current input, using the EM133 Modbus reference guide BG0530 Rev. A4 with manual BG0491 Rev. A15. Site check: read the device resolution at register 2390 and the energy decimal places at register 2393, then compare the first voltage read with the display. The EM133-R and EM133-XM-AR residential versions, DNP3, IEC 60870-5, PROFIBUS, CANopen and SATEC ASCII are outside this guide. Read-only monitoring: no writes to setup, password, relay or reset registers.
Connect it with
For a meter in a distribution board where a wireless link avoids running a data cable back to the Gateway
- Modbus
- Wireless
- Edge
- Platforms
When the Gateway sits near the meter, or several meters share one wired RS-485 bus
- Modbus
- Edge
- Platforms
When the meter has the ETHD Ethernet module, or a 12DIOR module with its Ethernet port, as COM2
- Modbus
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| EM133-5A-60HZ-ACDC | EM133 with the 5 A CT input (order option 5: In 5 A, Imax 10 A), calibrated at 60 Hz (60HZ) and powered by the 40 to 300 V AC/DC auxiliary supply (ACDC). No H in the string, so the default low resolution applies: 1 V and 1 A. No protocol suffix, so Modbus and DNP3. Expansion modules are ordered separately and do not appear in this string. | Read COM1 with Modbus RTU through a ZMB-31 or a Gateway serial port. Expect volts in 1 V and amps in 1 A until register 2390 says otherwise. Readings are in primary units, scaled by the PT ratio and CT primary current set in the meter. |
| EM133, EM133-XM, EM133-MID | EM133 standard; EM133-XM with over 40 times the log memory, an internal temperature sensor and three data recorders; EM133-MID, MID certified with the 5 A input. All share COM1 RS-485 and the BG0530 map. | Same read path. Summary energy registers 5 to 12 (14768 to 14783) and the temperature register 2568 are XM only. |
| Current input options 5, 1, 63, 100, RS5, HACS, HACS-SPDR | 5 A or 1 A CT secondaries, direct 63 A or 100 A, the RS5 input for 5 A split-core HACS and the 40 mA input for SATEC HACS sensors | The register map is the same for every input. The CT primary current set at register 2306 scales the current and power readings. |
| Power supply options ACDC, SE, 21DC | ACDC: 40 to 300 V AC/DC auxiliary supply. SE: self-energised from the measured voltages (120 to 277 V L-N). 21DC: 12/24 V DC. | No effect on the Modbus map. An SE meter is powered from the measured voltages, so it stops answering when they are lost. |
| COM2 modules ETHD, RS232, RS232D, PRO, LTEx-y, 12DIOR-ETH, 12DIOR-485 | ETHD: 10/100BaseT with Modbus TCP on port 502. RS232: RS-232 or RS-422/485 with Modbus RTU; RS232D: RS-232. PRO: PROFIBUS DP. LTE modem with Modbus TCP. 12DIOR with an Ethernet or RS-485 port. | ETHD or 12DIOR-ETH give the Modbus TCP route; RS232 or 12DIOR-485 give a second Modbus RTU port. PROFIBUS and the cellular modem are not used for a local Edge read; use COM1 instead. |
Specifications
The EM133 is a three-phase multifunction and time-of-use energy meter for DIN-rail mounting, with a 2 × 16 character backlit LCD, an anti-tamper enclosure and an embedded controller with 16 setpoints. It measures true RMS voltage, current, power, power factor, neutral current, unbalance and frequency at 25, 50, 60 or 400 Hz, four-quadrant energy, and harmonics to the 40th order. One expansion module can be fitted: digital inputs and relays, analog outputs, or a second communication port.23
- Models
- EM133 standard; EM133-XM extended memory, over 40 times the standard capacity, with an internal temperature sensor and three data recorders; EM133-MID, MID certified (5 A).3
- Order string
- Current input (5, 1, 63, 100, RS5, HACS, HACS-SPDR), calibration frequency (25HZ, 50HZ, 60HZ, 400HZ), resolution (blank low 1 A and 1 V, H high 0.01 A and 0.1 V), power supply (ACDC 40 to 300 V AC/DC, SE self-energised, 21DC 12/24 V DC), then seal, protocol and test options.3
- Inputs
- Voltage up to 690 V AC line-to-line direct, measurement range 15 to 480/828 V AC (L-N/L-L). Current through 5 A CTs (In 5 A, Imax 10 A) or 1 A CTs (In 1 A, Imax 2 A), direct 63 A, the RS5 split-core input or SATEC HACS sensors.23
- Accuracy
- Active energy class 0.5S to IEC 62053-22 and IEC 60688, ANSI C12.20 class 0.5, and EN 50470-3 class B or C on the 5 A version. Optional calibration to class 0.2/0.2S.3
- COM1
- Built-in two-wire RS-485, 3000 V AC optical isolation, up to 115.2 kbit/s and 1000 m. Factory settings: Modbus RTU, address 1, 19,200 bit/s, 8 data bits, no parity, 5 ms response delay.23
- Ethernet (COM2 module)
- Transformer-isolated 10/100BaseT on RJ45. Modbus TCP on port 502 and DNP3/TCP on port 20000, four connections in total (two Modbus TCP, two DNP3). Factory IP 192.168.0.203, mask 255.255.255.0, gateway 192.168.0.1.23
- Response time
- 13 ms typical at 9600 bit/s, 11 ms at 19200 bit/s and 9 ms at 57600 or 115200 bit/s.1
- Power supply
- ACDC option 40 to 300 V AC 50/60 Hz or 40 to 300 V DC, 5 VA; SE option self-energised from 1, 2 or 3 measured phases, 2 VA per phase; 12/24 V DC option.23
- Mounting
- 35 mm DIN rail to EN 50022; 125 × 90 × 75 mm; reinforced polycarbonate; IP20.3
- Environment
- Operating -25 to +60 °C, specified range -20 to +60 °C; storage -30 to +85 °C; damp heat below 95 % non-condensing at +40 °C.2
Interface
Documented measurements and integration boundaries for EM133.
- Addresses are decimal and go on the wire as printed: register 13952 is sent as 36 80. A client that wants Modicon numbers adds 40001, or 400001 above 9999, so 13952 becomes 413953. FC03 and FC04 return the same registers.
- 32-bit values are two registers, low-order word first, with the low word at an even address. They are long integers by default; register 246 can switch analog values, counters and energies to IEEE floats, which are also sent low register first. Read 246 before adding points.
- Units depend on the device resolution at register 2390 (0 low, the default; 1 high, order code H). Low resolution: volts in 1 V, amps in 1 A, power in 1 kW, kvar or kVA. High resolution: 0.1 V and 0.001 kW with a PT ratio of 1 (1 V and 1 kW above it), and 0.01 A.
- 1-second phase voltages V1, V2 and V3 at 13952, 13954 and 13956: UINT32 in volts. They are line-to-neutral in 4LN3, 3LN3 and 3BLN3 wiring and line-to-line otherwise. V12, V23 and V31 at 14012, 14014 and 14016.
- Currents I1, I2 and I3 at 13958, 13960 and 13962: UINT32 in amps. Neutral current at 14466 and frequency at 14468 (UINT32, 0.01 Hz).
- Per-phase kW at 13964, 13966 and 13968 and kvar at 13970, 13972 and 13974: INT32. kVA at 13976 to 13980: UINT32. Power factor L1 to L3 at 13982, 13984 and 13986: INT32, × 0.001. In 3-wire wiring the per-phase power and power factor read zero.
- Totals: kW at 14336 and kvar at 14338 (INT32), kVA at 14340 (UINT32), power factor at 14342 (INT32, × 0.001), kW import at 14348 and kW export at 14350 (UINT32), average current at 14360.
- Energy: kWh import at 14720, kWh export at 14722, kvarh import at 14728, kvarh export at 14730, kVAh total at 14736, kVAh import at 14742 and kVAh export at 14744. UINT32, 0 to 999,999,999. The unit is programmable from 0.0001 to 1 kWh: register 2393 holds the number of decimal places for energy registers (0 to 4, default 4).
- Per-phase kWh import L1 to L3 at 14848, 14850 and 14852 and kWh export L1 to L3 at 14866, 14868 and 14870, when phase energy calculation is enabled at register 2378.
- Voltage THD V1 to V3 at 13988, 13990 and 13992 and current THD I1 to I3 at 13994, 13996 and 13998: UINT32, 0.1 %, 3-second values.
- Registers 256 to 308 are a 16-bit basic set scaled 0 to 9999 between low and high engineering scales, with energies split modulo 10000. Prefer the 32-bit registers, which need no scale arithmetic.
- Identity: serial number at 46080 (UINT32), model ID at 46082, model name at 46084 to 46091 and firmware version at 46100. Wiring mode at 2304, PT ratio at 2305 (× 0.1) and CT primary current at 2306.
- Setup, password (2575), restart (2560), relay control (3244 to 3247), reset and clear registers (3404 to 3414) and the assignable map (0 to 239) accept writes. Keep them out of a monitoring poll.
Assessment
EM133, EM133-XM and EM133-MID with any current input, using the EM133 Modbus reference guide BG0530 Rev. A4 with manual BG0491 Rev. A15. Site check: read the device resolution at register 2390 and the energy decimal places at register 2393, then compare the first voltage read with the display. The EM133-R and EM133-XM-AR residential versions, DNP3, IEC 60870-5, PROFIBUS, CANopen and SATEC ASCII are outside this guide. Read-only monitoring: no writes to setup, password, relay or reset registers.
- InteroperabilityWell supported
- SATEC documents Modbus RTU on COM1 and Modbus TCP on port 502, the supported function codes and exception responses, decimal addresses with the Modicon offsets, data types, low-word-first word order with worked examples, and unit tables for each resolution.12
- AccuracySupported with conditions
- Class 0.5S active energy, MID certification on the 5 A version, per-phase and total power, four-quadrant energy and 1-second values. The units of every analog register depend on the resolution setting and PT ratio, and the energy unit on the decimal places at register 2393, so each point needs its scale confirmed once.13
- SecuritySupported with conditions
- Three configurable 8-digit passwords protect setups and accumulated data, the meter ships with protection enabled, and unauthorised writes get exception 01. Modbus RTU and Modbus TCP carry no encryption or authentication of reads, so keep the meter on a trusted network.12
- ReliabilitySupported with conditions
- The datasheet lists IEC 61000-4-2 to 4-8 immunity tests with their levels, including 4 kV fast transients and surge on the measuring circuits. The guide documents exception codes, response times of 9 to 15 ms and device diagnostics. Logs are kept in non-volatile memory. Treat failed reads as missing data.123
- RuggednessSupported with conditions
- Rated -25 to +60 °C operating, IP20, with IEC 60068-2-6 vibration and IEC 60068-2-27 shock tests and an anti-tamper sealable enclosure. DIN-rail mounting inside a cabinet.23
- ScalabilitySupported with conditions
- Modbus addresses 1 to 247, up to 115.2 kbit/s, and 120 user-assignable registers that can gather scattered points into one read. The Ethernet module allows only two Modbus TCP connections at a time.13
- LifecycleSupported with conditions
- Firmware can be upgraded through the serial or Ethernet ports and its version is readable at 46100. SATEC publishes the reference guide's revision history from 2020 to 2022 and a May 2025 datasheet. The warranty is 24 months from dispatch, capped at 36 months from production. No support period or end-of-sale date is stated.123
Setup
Read V1 voltage from decimal register 13952
EM133 Modbus reference guide BG0530 Rev. A4, section 3.4, lists the 1-second V1/V12 voltage at registers 13952 and 13953 as UINT32 with unit U1, and section 2.7.2 sends 32-bit values low word first. This example is an EM133-5A-60HZ-ACDC in 4LN3 wiring on a 277/480 V supply with no PTs. Use the map as the starting point and compare the result with the display.
- Request
- 01 03 36 80 00 02 CA 6B: Modbus address 1, FC03, register 13952 (0x3680), two registers, RTU CRC. Over Modbus TCP the same function, address and length go to port 502. To check the resolution first, 01 03 09 56 00 01 67 86 reads register 2390, and 01 03 09 59 00 01 57 85 reads the energy decimal places at register 2393.
- Address convention
- The guide's register numbers are the zero-based PDU addresses in decimal: send 13952, which is 0x3680. A client that numbers holding registers from one shows it as 413953. Do not send 13953 or 413953 as the address.
- Synthetic response
- 01 03 04 01 15 00 00 EA 0B: four data bytes, low word 01 15 first, then high word 00 00.
- Decode
- UINT32 with the low word first: 0 × 65536 + 0x0115 = 277. The order code has no H, so the default low resolution applies and U1 is 1 V: V1 is 277 V line-to-neutral. With high resolution and a PT ratio of 1 the same voltage arrives as 2770 (low word 0A D2) in 0.1 V. A client that takes the high word first reads 0x01150000 = 18,153,472.
- Acceptance
- Keep the point when it agrees with V1 on the meter display at the same time. If it does not, check the resolution at 2390, the 32-bit register type at 246, the word order and the wiring mode at 2304 before adding more points.
Acceptance: The response bytes are a synthetic decoder check, not a captured meter reply. A real reply must agree with the display before current, power and energy points are enabled.
-
Identify the meter
Read the order code from the meter label: current input, calibration frequency, resolution and supply, for example EM133-5A-60HZ-ACDC. Note any module fitted as COM2, and record the wiring mode, PT ratio and CT primary current from the basic settings.
-
Read the port settings
COM1 is factory set to Modbus RTU, address 1, 19,200 bit/s and 8 data bits with no parity. With an Ethernet module, the Net menu shows the IP address. Enter the same values in the Edge client and leave the meter's settings as they are.
-
Wire the connection
For RS-485, connect X+, X- and the shield to COM1, give each meter its own address and terminate both ends of the bus. For Modbus TCP, connect the module's RJ45 port to the site network.
-
Make three reads
Read register 2390 for the device resolution and register 2393 for the energy decimal places, one register each. Then read V1 at 13952 for two registers and decode it low word first, as in the worked read below. Compare the result with the V1 voltage on the display.
-
Add the points you need
Add currents, powers and the energy counters from 14720, scaled by the decimal places from register 2393. Check register 246 if any value looks like a float, and keep writes out of the polling configuration.
Common questions
- What does EM133-5A-60HZ-ACDC mean?
- It is an EM133 with the 5 A current input for CT secondaries (In 5 A, Imax 10 A), calibrated at 60 Hz, with the ACDC auxiliary supply of 40 to 300 V AC/DC. The string has no H, so the meter ships with low resolution: volts in 1 V and amps in 1 A over Modbus. Expansion modules are ordered separately, so check the back of the meter: without an Ethernet module, the built-in COM1 RS-485 port is the Modbus route.23
- Why does voltage read 2770 on one meter and 277 on another?
- The device resolution setting changes the units. Low resolution, the default, sends volts in 1 V and amps in 1 A; high resolution, order code H, sends 0.1 V and 0.01 A, and 0.001 kW for power when the PT ratio is 1. Read register 2390 (0 low, 1 high) and set the scale in Edge to match.13
- How do I scale the EM133 energy registers?
- The 32-bit energy registers from 14720 count in a unit set by the number of decimal places at register 2393, from 0 (1 kWh) to 4 (0.0001 kWh), default 4. Read 2393 once, divide the counter by 10 to that power and compare the kWh import reading with the display.1
- Why does a 32-bit value read as millions?
- The client is taking the high word first. The EM133 sends the low-order word in the first register and the high-order word in the second, for integers and floats alike. Swap the two registers in the Edge point definition.1
- Can Edge read the EM133 over Ethernet?
- Yes, when the ETHD Ethernet module, or a 12DIOR module with its Ethernet port, is fitted as COM2. The meter keeps a Modbus TCP server on port 502 permanently and allows two simultaneous Modbus TCP connections. The base meter has only the RS-485 COM1 port and the optical port.23
- Can Modbus writes change the meter's settings?
- Yes, but only with the password. The EM133 ships with the password preset to 9 and password protection enabled, and the password applies to the display and the communication ports. Every write must be preceded by the password at register 2575, or the meter answers with exception code 01. A monitoring configuration should read with FC03 only.12
Sources
- EM133, EM133-XM Multifunction Meter Modbus communications protocol reference guide, BG0530 Rev. A4 (September 2022) (opens in a new tab) (PDF)
- EM13x Series Smart Multifunction Meter installation and operation manual, BG0491 Rev. A15 (opens in a new tab) (PDF)
- EM133 datasheet, May 2025, with models and order string (opens in a new tab) (PDF)
Further reading
- ToolModbus register address translator
- ToolModbus data decoder
- GuideModbus commissioning over RS-485
- GuideCT-connected meters
- GuideSATEC PM135: the panel meter with the same register map
- ToolRS-485 termination and bias
- ManufacturerSATEC devices
- ProtocolModbus devices and register maps
- CategoryEnergy meters