Pixii PowerShaper XL 60/225
Commercial battery energy storage system
This outdoor PowerShaper XL combines 60 kW conversion with 225.1 kWh installed LFP capacity. Eniris documents a tested Modbus TCP connection to a PowerShaper XL, and Reduxi publishes Pixii Gateway TCP and RTU setup steps for PowerShaper systems. A read-only trial is practical to plan, subject to the installed firmware, point map and site control ownership; Edge integration remains unverified.
- Modbus TCP
- Modbus RTU
- MQTT
Commercial battery energy storage system
Compatibility
Third-party Modbus monitoring precedent; Edge point map to confirm
Pixii publishes a PowerShaper register map with cabinet and plant monitoring points. Use it as a best-effort starting point with the existing Gateway endpoint; compare the installed version and live readings once. A published map does not establish an Edge-tested installation or permission to change service modes or issue writes.
Exact PowerShaper XL 60 kW / 225 kWh fan-filter LFP variant only. Record the complete order identity, battery block, PixiiBox, Pixii Gateway and firmware versions. Do not infer a path for air-conditioned, indoor, cabinet-only, PowerBase or XLP variants.
Models
| Models | Interface | Route into Edge |
|---|---|---|
| PowerShaper XL 60 kW / 225 kWh, fan-filter, LFP | Ethernet LAN, RS-485, digital I/O, Wi-Fi access point and optional 4G; published protocols include Modbus TCP/RTU and MQTT | Scope a read-only trial at the commissioned Pixii Gateway Modbus endpoint; exact 60/225 firmware map and Edge behaviour remain unverified. |
| PowerShaper XL 60 kW / 225 kWh, air-conditioned | Different thermal package and physical specification | Treat as a separate variant and use its current product record. |
| PowerShaper XL Indoor, PowerBase XL and PowerShaper XLP | Different cabinet, power, energy and deployment scope | Do not transfer the 60/225 specifications or interface assumptions. |
Specifications
The current exact-variant page specifies 60 kW continuous AC power, 225.1 kWh installed and 202.6 kWh usable LFP capacity, with 18 PixiiBoxes and 14 battery blocks in an outdoor IP55 cabinet. Published values are nominal and may be constrained by state of charge, state of health and thermal conditions.1
- AC rating
- 60 kW continuous, 60 kVA apparent, 400 V three-phase with neutral1
- Battery capacity
- 225.1 kWh installed and 202.6 kWh usable; LFP chemistry1
- Battery architecture
- 14 battery blocks, 16.08 kWh each; 18 PixiiBoxes; nominal DC around 48 V1
- Published interfaces
- Ethernet LAN, RS-485, digital I/O, Wi-Fi access point and optional 4G1
- Published protocols
- CAN bus and Modbus TCP/RTU are described as internal; MQTT is described as external1
- Third-party monitoring precedent
- Eniris tested PowerShaper XL over Modbus TCP; Reduxi documents Gateway TCP port 502 and RS-485 COM4 setup for PowerShaper systems34
- Enclosure
- Outdoor IP55 cabinet; -20 to +45 °C operating range; fan and heater thermal management1
- Grid and generator scope
- On-grid operation, off-grid support requiring a separate controller and local load-priority modification, plus published generator-backup support1
Interface
Documented measurements and integration boundaries for PowerShaper XL 60/225.
- For a first integration trial, enable only the approved Pixii Gateway Modbus endpoint and identify one documented status and one power or energy value in the current OEM map. Compare fresh readings with the Pixii web interface before adding other points.
- For a single cabinet, the map recommends SOC at 40132 with signed scale factor 40177, battery events at 40147 and vendor status at 40191. For multiple cabinets, use the master Gateway’s plant registers: actual power at 39912 in kW uses the generator sign convention, and average battery SOC is at 39915. Keep cabinet and plant measurements distinct.
- Potential AC power, import and export energy, state of charge, state of health and available charge or discharge power must retain source, sign, unit, freshness and quality.
- Battery-block, PixiiBox, cabinet and site-meter values are different measurement boundaries and must not be merged under one generic BESS point.
- No charge, discharge, power-factor, islanding, generator or market command is approved by this guide.
Assessment
Exact PowerShaper XL 60 kW / 225 kWh fan-filter LFP product record; no released Edge path, writes or grid-compliance claim.
- InteroperabilityLimited
- Pixii publishes FC03 monitoring addresses, decoding and cabinet/plant scope. Validate readings against the local Gateway display; direct Edge qualification and control remain separate.1345
- AccuracySupported with conditions
- The public U8022_06ENG revision 2.20 map documents read-only cabinet power with its sign and dynamic scale factor, plus separate plant scope. Compare a first FC03 reading with the Gateway display and feeder meter; operational readings do not establish settlement accuracy.5
- SecuritySupported with conditions
- Pixii states encrypted communications, secure remote access and current RED cybersecurity alignment; exact local interface authentication and role configuration still require commissioning.1
- ReliabilityNot yet assessed
- Redundancy and automated recovery are described at product-family level, but third-party client recovery and data retention are not established for an Edge path.1
- RuggednessSupported with conditions
- IP55, temperature, humidity, altitude and thermal-management limits are published for the exact outdoor variant.1
- ScalabilityNot yet assessed
- The system is modular, but external client count, polling capacity and multi-cabinet point ownership are not established.2
Setup
-
Confirm the exact system
Capture the full PowerShaper XL variant, order identity, serials, Pixii Gateway version, PixiiBox versions, battery-block identity, firmware and installed communications options.
-
Draw every control layer
Separate the site meter, switchgear, Pixii Gateway, PixiiBoxes, battery blocks, fire and thermal systems, generator controller and any higher-level EMS or market platform.
-
Choose the monitored Gateway endpoint
Check the Pixii Gateway web interface with the installer. Reduxi documents Menu → Communication → Modbus, Enabled and TCP/IP with port 502 by default; its alternative serial route uses Gateway COM4. Confirm those menus and the chosen route on this exact cabinet and firmware before connecting Edge.
-
Read one cabinet power value
Use the public U8022_06ENG revision 2.20 map, sections 2 and 4.1. For one cabinet, read FC03 at wire address 40083, length 2: signed int16 AC power followed by signed int16 scale factor at 40084, big-endian. Do not subtract 40001; Pixii lists the addresses sent on the wire. Calculate W = raw power × 10^scale factor. Illustrative values 2500 and 1 yield 25000 W, or 25 kW. Positive means battery charging. Read the scale factor with the value because scaling is dynamic, then compare with the Gateway web display.
-
Keep control out of the first phase
Commission identity, state, power, energy and alarm reads before considering writes. Do not use a published protocol label as authority to charge, discharge, island, synchronise or operate a generator.
-
Define any later command as a safety case
For each approved command, document ownership, range, ramp, interlocks, timeout, local override, rejection feedback, safe fallback and measured response at the connection point.
Common questions
- Does the PowerShaper XL publish Modbus?
- Yes. Pixii's product table names Modbus TCP/RTU but labels it internal. Eniris reports a tested Modbus TCP integration with PowerShaper XL, and Reduxi documents Gateway setup for PowerShaper TCP/RTU. Confirm the installed Gateway settings and firmware-matched map before treating either route as an Edge endpoint.134
- What can an installer check before requesting a point map?
- Inspect Menu → Communication → Modbus on the Pixii Gateway web interface. Reduxi documents an Enabled setting, TCP/IP mode and default port 502, with COM4 as a separate serial route. Record the actual configuration and existing controller roles; Eniris tested a PowerShaper XL over TCP. The current Pixii register map is still needed for a meaningful read-only point test.34
- Can Edge command charge and discharge from this guide?
- No. A control path needs the exact writable object, units, limits, ramp, interlocks, timeout, feedback and safe fallback approved by Pixii and the site owner. This selection guide publishes none.12
- Is the usable capacity 225.1 kWh?
- No. Pixii lists 225.1 kWh installed and 202.6 kWh usable for this exact variant. Actual performance may also be constrained by state of charge, state of health and thermal conditions.1
- Does off-grid support mean the cabinet can form an island by itself?
- No. The exact product page states that single-cabinet off-grid operation requires an off-grid control system and local modification for load prioritisation. Project-specific switching, protection, earthing and generator coordination remain separate.1
Sources
- PowerShaper XL 60 kW / 225 kWh, fan-filter, LFP (opens in a new tab)
- PowerShaper XL product family (opens in a new tab)
- Eniris SmartgridOne PowerShaper XL Modbus TCP integration guide (opens in a new tab)
- Reduxi PowerShaper and Home Modbus setup article, official JSON export (opens in a new tab)
- PowerShaper Modbus mapping U8022_06ENG revision 2.20 (opens in a new tab) (PDF)
Further reading
- ApplicationBattery demand response
- GuideBESS, BMS, EMS and PCS roles
- ToolBattery autonomy calculator
- ToolModbus register address converter
- ToolModbus data decoder
- ToolRS-485 termination and bias
- GuideModbus RS-485 commissioning
- ProtocolModbus devices and register maps
- CategoryBattery systems and controls
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.