Vertiv IS-UNITY-DP
Equipment communications interface
An IntelliSlot card publishes points for the equipment it discovers. For a cooling or UPS monitoring quote, include the host model and controller revision as well as the card label. Two units with the same card can expose different measurements.
Compatibility
Compatible with Edge over BACnet/IP
Edge can read the card directly on BACnet/IP or through a router when it uses MS/TP.
Match the host, controller revision and active network interface before selecting an object table.
Connect it with
For a commissioned Ethernet connection
- BACnet
- Edge
- Platforms
For an IS-UNITY-DP on RS-485
- BACnet
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| IS-UNITY-DP | Ethernet for BACnet/IP or RS-485 for BACnet MS/TP. | Request the object list for each monitored host. The card creates its objects when it discovers the managed equipment. |
| IS-UNITY-DP | BTL B-SA profile. | The listing names software version 6.0. Record the installed version alongside the point list. |
Interface
Documented measurements and integration boundaries for IS-UNITY-DP.
- For a Liebert CRV with iCOM v4, table 5.31 lists read-only supply air temperature as Analog Value 1 in °C and return air temperature as Analog Value 2 in °C.
- The same CRV table offers the Fahrenheit equivalents at AV 10001 and AV 10002. Select one unit per measurement to avoid counting a second copy.
Assessment
IS-UNITY-DP on the commissioned BACnet interface.
- InteroperabilityWell supported
- The BTL listing identifies the exact model and software version.3
- AccuracySupported with conditions
- For a Liebert CRV with iCOM v4, table 5.31 lists read-only supply air temperature as Analog Value 1 in °C and return air temperature as Analog Value 2 in °C.2
- SecurityNot yet assessed
- Site access controls depend on the installed network.2
- ReliabilityNot yet assessed
- The listing covers BACnet interoperability.3
- RuggednessNot yet assessed
- Confirm installation conditions for the host enclosure.2
- ScalabilityNot yet assessed
- Point coverage depends on the connected equipment and its commissioned configuration.2
- LifecycleNot yet assessed
- Record the installed software with the commissioning schedule.2
Setup
-
For a CRV, confirm the equipment uses iCOM v4 before applying table 5.31.
Use the corresponding host table for other equipment.
-
Read Present_Value and Units from Analog Value 2 and compare the °C reading with return air temperature on the CRV display during steady operation.
-
Record the equipment tag, controller revision, card Device instance and object identifier with the accepted measurement.
Sources
- IntelliSlot Unity BACnet protocol implementation conformance statement (opens in a new tab) (PDF)
- IntelliSlot Modbus and BACnet protocols, SL-28170 revision 33 (opens in a new tab) (PDF)
- BTL listing 24498 (opens in a new tab) (PDF)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.