Vertiv IS-UNITY-DP

Equipment communications interface

An IntelliSlot card publishes points for the equipment it discovers. For a cooling or UPS monitoring quote, include the host model and controller revision as well as the card label. Two units with the same card can expose different measurements.

Liebert IntelliSlot card with IS-UNITY-DP marked on its front plate
  • BACnet/IP
  • BACnet MS/TP

Equipment communications interface

Ask an engineer

Compatibility

Compatible with Edge over BACnet/IP

Edge can read the card directly on BACnet/IP or through a router when it uses MS/TP.

Match the host, controller revision and active network interface before selecting an object table.

Connect it with

Route into Edge

For a commissioned Ethernet connection

  • BACnet
  • Edge
  • Platforms
Equipment communications interface
Interface
Gateway
Edge
Output
IS-UNITY-DPIS-UNITY-DP
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet/IP
Protected Ethernet
Runs locally
Optional onward data
Identify the card Device instance and the attached equipment tag. The customer-platform output is optional; Edge remains the local system of record.

For an IS-UNITY-DP on RS-485

  • BACnet
  • Edge
  • Platforms
Equipment communications interface
Interface
Gateway
Edge
Output
IS-UNITY-DPIS-UNITY-DP
BACnet routerRoutes the field segment to the building IP network.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Use the router serving the card’s serial segment. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
IS-UNITY-DPEthernet for BACnet/IP or RS-485 for BACnet MS/TP.Request the object list for each monitored host. The card creates its objects when it discovers the managed equipment.
IS-UNITY-DPBTL B-SA profile.The listing names software version 6.0. Record the installed version alongside the point list.

Interface

Documented measurements and integration boundaries for IS-UNITY-DP.

  • For a Liebert CRV with iCOM v4, table 5.31 lists read-only supply air temperature as Analog Value 1 in °C and return air temperature as Analog Value 2 in °C.
  • The same CRV table offers the Fahrenheit equivalents at AV 10001 and AV 10002. Select one unit per measurement to avoid counting a second copy.

Assessment

IS-UNITY-DP on the commissioned BACnet interface.

InteroperabilityWell supported
The BTL listing identifies the exact model and software version.3
AccuracySupported with conditions
For a Liebert CRV with iCOM v4, table 5.31 lists read-only supply air temperature as Analog Value 1 in °C and return air temperature as Analog Value 2 in °C.2
SecurityNot yet assessed
Site access controls depend on the installed network.2
ReliabilityNot yet assessed
The listing covers BACnet interoperability.3
RuggednessNot yet assessed
Confirm installation conditions for the host enclosure.2
ScalabilityNot yet assessed
Point coverage depends on the connected equipment and its commissioned configuration.2
LifecycleNot yet assessed
Record the installed software with the commissioning schedule.2

Setup

  1. For a CRV, confirm the equipment uses iCOM v4 before applying table 5.31.

    Use the corresponding host table for other equipment.

  2. Read Present_Value and Units from Analog Value 2 and compare the °C reading with return air temperature on the CRV display during steady operation.

  3. Record the equipment tag, controller revision, card Device instance and object identifier with the accepted measurement.