Grundfos MAGNA3

HVAC circulator pump

A MAGNA3 can report both electrical demand and cumulative consumption. For a retrofit quote, photograph the fitted communications module and identify the pump head on the plant schedule. The CIM 500 uses building Ethernet in BACnet/IP mode. The CIM 300 needs a routed serial trunk.

Grundfos MAGNA3 flanged single-head circulator
  • BACnet/IP
  • BACnet MS/TP

HVAC circulator pump

Ask an engineer

Compatibility

Compatible with Edge through the Grundfos BACnet module

Edge reads the CIM 500 over BACnet/IP or the CIM 300 through a BACnet router.

Confirm the module label, configured protocol and BACnet Device instance for the pump head.

Connect it with

Route into Edge

For a CIM 500 in BACnet/IP mode

  • Wired
  • Edge
  • Platforms
HVAC circulator pump
Interface
Gateway
Edge
Output
MAGNA3MAGNA3 with CIM 500
Protected EthernetSegmented LAN
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeProtocol client + point model
Customer platformMQTT · API · files
Ethernet
Protected Ethernet
Runs locally
Optional onward data
Use the BACnet Device instance assigned to the pump module. The customer-platform output is optional; Edge remains the local system of record.

For a CIM 300 on a routed trunk

  • BACnet
  • Edge
  • Platforms
HVAC circulator pump
Interface
Gateway
Edge
Output
MAGNA3MAGNA3 with CIM 300
BACnet routerRoutes the field segment to the building IP network.
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeBACnet/IP client + object map
Customer platformMQTT · API · files
BACnet MS/TP
BACnet/IP
Runs locally
Optional onward data
Identify the trunk network number and match the pump module to its Device instance. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
MAGNA3 with CIM 500Ethernet with selectable industrial protocol.The Grundfos profile assigns rotary switch position 2 to BACnet/IP. Check the recorded setting with the installer.
MAGNA3 with CIM 300BACnet MS/TP on RS-485.Ask which BACnet router serves the pump trunk and whether the pump is already visible from the building network.

Interface

Documented measurements and integration boundaries for MAGNA3.

  • Analog Input 13 reports the pump’s total electrical power in W. Analog Input 30 reports cumulative electrical energy in kWh. Use the change in AI 30 over a reporting interval for pump consumption.
  • Analog Input 93 reports pressure difference across the pump flanges in bar. A remote pressure sensor has a separate object, AI 16. Identify the pressure taps before comparing trends.

Assessment

MAGNA3 pump objects through a CIM 300 or CIM 500.

InteroperabilityWell supported
BTL lists CIM/CIU 500 version 1.05 and CIM/CIU 300 version 04.02.00 as B-ASC devices.23
AccuracySupported with conditions
The profile distinguishes electrical demand in W from electrical energy in kWh.1
SecurityNot yet assessed
Site access controls depend on the installed network.1
ReliabilityNot yet assessed
The module listings do not quantify pump or network availability.1
RuggednessNot yet assessed
Enclosure suitability depends on the installation.1
ScalabilityNot yet assessed
The profile does not establish the available capacity of the site network.1
LifecycleNot yet assessed
The functional profile identifies the module and pump combinations.1

Setup

  1. Record the fitted module, pump identifier and Device instance.

    For twin-head systems record which head or system the point list represents.

  2. Read Present_Value and Units from Analog Input 13.

    Compare the value in W with the pump power shown locally during steady operation and retain the timestamp.

  3. For energy reporting, read Analog Input 30 at the start and end of an agreed interval.

    Match the kWh change to the pump’s local energy counter over the same interval.

Sources

  1. BACnet for Grundfos pumps, functional profile 97572650 (opens in a new tab) (PDF) Grundfos
  2. BTL listing 24159 for the CIM/CIU 500 (opens in a new tab) (PDF) BACnet Testing Laboratories
  3. BTL listing 24189 for the CIM/CIU 300 (opens in a new tab) (PDF) BACnet Testing Laboratories

Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.