Phoenix Contact EEM-MA370
Three-phase energy meter
Connect the EEM-MA370 Ethernet meter to Edge over Modbus TCP. Start with frequency, compare it with the display, then add electrical readings. Configure external 1 A or 5 A CTs for the installation.
Compatibility
Compatible with EpiSensor Edge over Modbus TCP
Phoenix Contact documents FC03/FC04 reads and 32-bit float encoding for its public process-data example. This is a source-documented starting procedure, not a physical Edge test.
Best-effort starting map for EEM-MA370 order 2907983. Compare readings with the display and record firmware; adjust the point configuration if needed. Monitoring only.
Connect it with
EEM-MA370 is configured on the local network
- Modbus
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| EEM-MA370, order number 2907983 | Display model for external 1 A or 5 A current transformers; Modbus/TCP over RJ45; REST from firmware 1.1.0 and MQTT from firmware 1.7.0 | Ethernet Modbus TCP to Gateway running Edge. Start with the frequency read below. |
| EEM-MA370-R, order number 2907980 | Related display model with Modbus/TCP and Modbus RTU | Treat as a separate model. The serial interface on the -R variant is not present on the EEM-MA370 covered here. |
| EEM-MA371 and EEM-MA391 variants | Related models for Rogowski or low-voltage current-transformer inputs | Do not reuse the EEM-MA370 current-input assumptions or point configuration. |
Specifications
Phoenix Contact identifies order number 2907983 as the EEM-MA370 display model with current-transformer inputs and Modbus/TCP. The -R and 24 V DC variants have different interface or supply contracts and must be identified separately.1
- Measurement
- Three-phase voltage and external 1 A or 5 A CT current inputs; continuous simultaneous acquisition2
- Voltage range
- 18 to 690 V AC phase-phase and 11 to 400 V AC phase-neutral2
- Current range
- External CT primary from 1 A to 20,000 A with 1 A or 5 A secondary2
- Energy accuracy
- Active energy class 0.5 S under IEC 62053-22; reactive energy class 2 under IEC 62053-232
- Environment
- -25 to +70 degrees Celsius; IP20 housing and IP40 display; up to 2,000 m altitude2
Interface
Documented measurements and integration boundaries for EEM-MA370.
- Frequency: address 32780, 2 registers, Hz.
- System current: 32825; system conductor voltage: 32829; total active power: 32790. Each uses 2 registers.
- The optional mapped read area starts at 57600 and holds 125 registers, not 125 measurements. Its content depends on the web configuration.
- Keep configuration and resets outside the monitoring client.
Assessment
EEM-MA370 order 2907983, using the published starting map and display checks.
- InteroperabilitySupported with conditions
- Documented Modbus TCP reads, encoding and example electrical addresses support a practical starting point.345
- AccuracySupported with conditions
- Electrical ranges and accuracy are documented. Correct CT configuration and display comparisons establish the installation measurement scale.2
- SecurityLimited
- The published Modbus/TCP path has no stated peer authentication or encryption, and the device exposes writable configuration areas.3
- ReliabilityNot yet assessed
- Point-specific unavailable-value codes are not established in the retained documentation.3
- RuggednessSupported with conditions
- Temperature, enclosure and altitude limits are published for a suitable electrical panel installation.2
- ScalabilitySupported with conditions
- A configurable contiguous process map can reduce requests, subject to controlled mapping, network design and a bounded polling plan.3
Setup
First read: supply frequency
Use the published process-data example for a best-effort initial read. Check the result against the local display.
- Function
- FC03 (FC04 returns the same registers)
- Start address
- 32780 decimal (0x800C). Use the raw address; a client using one-based register labels may display 32781.
- Length
- 2 registers
- Decode
- 32-bit IEEE 754 float, low word first (CDAB wire-byte order). Phoenix calls this little-endian byte swap.
- Example
- Words 0x0000, 0x4248 reconstruct 0x42480000 = 50.0 Hz. This is a decoding example, not a measured device response.
Acceptance: Accept a finite value matching the display. If it differs, check the client address convention and word order. Mark failed reads as missing.
-
Confirm the exact article
Record EEM-MA370 and order number 2907983 from the device. Capture firmware, serial number, supply variant and Ethernet configuration.
-
Record the measurement circuit
Document voltage wiring, CT primary and secondary ratings, CT polarity and phase assignment. Verify the configured values against the installation drawings.
-
Read frequency first
Use FC03 at address 32780 for 2 registers. FC04 returns the same data. Start with the published address and compare with the display.
-
Decode and expand
Decode a 32-bit IEEE 754 float with the low word first. Compare current, voltage and power with the display before adding them to monitoring.
-
Use the mapped block when useful
The web configuration can group readings for fewer requests. Record the mapping before polling it; retain individual addresses for troubleshooting.
Common questions
- Can Edge read the EEM-MA370 over Modbus TCP?
- Yes, use the documented Modbus TCP read path and the first-read procedure below. Compare with the display before expanding the point set.1345
- Is the EEM-MA370-R the same integration?
- No. The -R variant adds Modbus RTU, while order number 2907983 covered here is the Modbus/TCP display model. Identify the exact order number before designing the network.1
- Does class 0.5 S make the Edge record suitable for billing?
- No. The meter specification describes the instrument. A copied or calculated Edge series does not inherit an approved revenue or settlement role.2
- Can Edge configure the 125-register mapped area?
- Configure the optional map in the meter web interface, then read it from Edge. Keep allocation writes outside the monitoring client.3
Sources
- EMpro product overview for rail-mounted meters with display (opens in a new tab)
- EEM-MA370 technical data (opens in a new tab)
- EMpro Modbus mapping (opens in a new tab)
- EMpro Modbus read functions (opens in a new tab)
- EMpro data types and word order (opens in a new tab)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.