Phoenix Contact EEM-MA370

Three-phase energy meter

The EEM-MA370 is a display energy meter for external 1 A or 5 A current transformers. Phoenix Contact documents Modbus/TCP, REST and firmware-dependent MQTT, plus a configurable Modbus process-data map. Direct Edge monitoring remains unverified until the complete register table and installed firmware contract are retained and commissioned.

  • Modbus TCP
  • HTTP
  • MQTT

Three-phase energy meter

Compatibility

Direct Edge integration not yet verified

Phoenix Contact's exact-model documentation identifies Modbus/TCP and publishes an example of the configurable process-data map. The retained pages do not contain the complete register table, supported function-code contract or unavailable-value rules required for a released Edge point set.

EEM-MA370 order number 2907983 only. Obtain and retain the complete firmware-matched register table, confirm the server role and read semantics, and validate the installed CT and voltage configuration before proposing an Edge route. Do not apply this guide to EEM-MA370-R, EEM-MA371 or EEM-MA390 variants.

Models

Download
ModelsInterfaceRoute into Edge
EEM-MA370, order number 2907983Display model for external 1 A or 5 A current transformers; Modbus/TCP over RJ45; REST from firmware 1.1.0 and MQTT from firmware 1.7.0Hold direct integration until the complete firmware-matched Modbus register table is retained and commissioned.
EEM-MA370-R, order number 2907980Related display model with Modbus/TCP and Modbus RTUTreat as a separate model. The serial interface on the -R variant is not present on the EEM-MA370 covered here.
EEM-MA371 and EEM-MA391 variantsRelated models for Rogowski or low-voltage current-transformer inputsDo not reuse the EEM-MA370 current-input assumptions or point configuration.

Specifications

Phoenix Contact identifies order number 2907983 as the EEM-MA370 display model with current-transformer inputs and Modbus/TCP. The -R and 24 V DC variants have different interface or supply contracts and must be identified separately.1

Measurement
Three-phase voltage and external 1 A or 5 A CT current inputs; continuous simultaneous acquisition2
Voltage range
18 to 690 V AC phase-phase and 11 to 400 V AC phase-neutral2
Current range
External CT primary from 1 A to 20,000 A with 1 A or 5 A secondary2
Energy accuracy
Active energy class 0.5 S under IEC 62053-22; reactive energy class 2 under IEC 62053-232
Ethernet
100Base-TX RJ45 with Modbus/TCP, REST API and firmware-dependent MQTT12
Environment
-25 to +70 degrees Celsius; IP20 housing and IP40 display; up to 2,000 m altitude2

Interface

Documented measurements and integration boundaries for EEM-MA370.

  • Potential voltage, current, frequency, active-power and energy points require the complete firmware-matched register table before publication.
  • Keep raw meter values, CT configuration, derived intervals and any upstream settlement totals as separate records.
  • The configurable 125-register process-data area is a device mapping feature, not proof that every source register is safe or available on the installed firmware.
  • No relay output, MQTT command, configuration register or reset operation is approved by this guide.

Assessment

Exact EEM-MA370 order number 2907983 pending the complete firmware-matched Modbus register table and site commissioning.

InteroperabilityLimited
The exact Ethernet model and Modbus/TCP role are published, but the complete read contract is not retained.13
AccuracySupported with conditions
Electrical ranges, acquisition and accuracy are documented; the point-level data contract and installed CT configuration remain conditions.2
SecurityLimited
The published Modbus/TCP path has no stated peer authentication or encryption, and the device exposes writable configuration areas.3
ReliabilityNot yet assessed
The retained pages do not define stale, unavailable or exception behavior for the complete point set.3
RuggednessSupported with conditions
Temperature, enclosure and altitude limits are published for a suitable electrical panel installation.2
ScalabilitySupported with conditions
A configurable contiguous process map can reduce requests, subject to controlled mapping, network design and a bounded polling plan.3
LifecycleSupported with conditions
Phoenix Contact publishes dated exact-model online documentation; a project must retain the register table and firmware used for commissioning.12

Setup

  1. Confirm the exact article

    Record EEM-MA370 and order number 2907983 from the device. Capture firmware, serial number, supply variant and Ethernet configuration.

  2. Record the measurement circuit

    Document voltage wiring, CT primary and secondary ratings, CT polarity and phase assignment. Verify the configured values against the installation drawings.

  3. Obtain the complete interface contract

    Retain the firmware-matched Phoenix Contact register table with supported function codes, addresses, data types, units and invalid-value behavior.

  4. Keep the allocation area outside monitoring

    The configurable process map uses a writable allocation block. Do not let the monitoring client alter mapping, network, meter or output configuration.

  5. Prove a bounded read path

    Validate identity and one electrical value against the simultaneous display before expanding the point set. Reconcile power and energy under a known load.

Common questions

Can Edge read the EEM-MA370 over Modbus TCP?
The exact model publishes Modbus/TCP and a configurable process-data map, but this guide does not release a direct Edge path. The complete firmware-matched register table and read contract still need to be retained and commissioned.13
Is the EEM-MA370-R the same integration?
No. The -R variant adds Modbus RTU, while order number 2907983 covered here is the Modbus/TCP display model. Identify the exact order number before designing the network.1
Does class 0.5 S make the Edge record suitable for billing?
No. The meter specification describes the instrument. A copied or calculated Edge series does not inherit an approved revenue or settlement role.2
Can Edge configure the 125-register mapped area?
This guide excludes all writes. Phoenix Contact separates the read-only mapped area from its writable allocation area. Any mapping change belongs to a controlled commissioning process outside the monitoring client.3