Samsung EHS Mono HT Quiet 8 kW

Air-to-water heat pump

AE080BXYDEG/EU is Samsung's single-phase 8 kW EHS Mono HT Quiet outdoor unit, paired with a MIM-E03EN/CN control kit or ClimateHub. With a compatible MIM-B19N module fitted, it is compatible with EpiSensor Edge over Modbus RTU: Samsung's EHS register table provides water temperatures and operating status. Compare those reads with the controller and meter heat and electricity separately for COP.

Samsung EHS Mono HT Quiet AE080BXYDEG/EU outdoor heat-pump unit
  • Modbus RTU

Air-to-water heat pump

Ask an engineer

Compatibility

Compatible with EpiSensor Edge through a Samsung MIM-B19N Modbus module

Samsung documents the outdoor/control-kit pairing and a separate MIM-B19N/B19NT EHS register table on Modbus RTU. Edge reads the module through a ZMB-31 or the Gateway’s serial interface: communication status, unit type, water-in, water-out and hot-water temperatures. An EpiSensor ZEM on the unit’s supply provides the electrical input for COP.

Check accessory fit and wiring with the Samsung installer, then record the installed controller, MIM-B19N revision and tracked EHS device address. The following addresses are best-effort candidates from DB68-07538A-03 and should be compared with the local controller. PV, Smart Grid Ready and other control writes require their own commissioned design.

Connect it with

Route into Edge

When a MIM-B19N/B19NT module is fitted and tracks the controller as an EHS device

  • Wired
  • Edge
  • Platforms
Air-to-water heat pump
Interface
Gateway
Edge
Output
EHS Mono HT Quiet 8 kWAE080BXYDEG/EU with its Samsung controller
Samsung MIM-B19N/B19NTTracks the EHS unit on the Samsung R1/R2 bus and serves its table over Modbus RTU
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeModbus client + register map
Customer platformMQTT · API · files
Samsung R1/R2 bus
Modbus RTU · RS-485, A/B
Runs locally
Optional onward data
The module joins the Samsung R1/R2 bus and serves the EHS table on its A/B side. Wire A/B to a ZMB-31 or the Gateway’s serial interface at 9600 baud, 8E1, and use the module’s slave address. Read status and temperatures with FC04 from base address 50 + 50 × IU for the tracked EHS address. Read only. The customer-platform output is optional; Edge remains the local system of record.

For the electrical input to a COP calculation, with or without a Modbus module

  • Wired
  • Edge
  • Platforms
Air-to-water heat pump
Interface
Gateway
Edge
Output
EHS Mono HT Quiet 8 kWAE080BXYDEG/EU single-phase supply
EpiSensor ZEMMeasures the supply with its own CTs and reports over the EpiSensor wireless network
ZGW-20 GatewayHosts Edge locally
EpiSensor EdgeProtocol client + point model
Customer platformMQTT · API · files
CT on the single-phase supply
EpiSensor wireless
Runs locally
Optional onward data
Fit a ZEM CT on the outdoor unit’s single-phase supply, and on any booster heater, backup heater and pump feeds inside the COP boundary. The ZEM reports over the EpiSensor wireless network. Delivered heat still needs a hydronic heat meter. The customer-platform output is optional; Edge remains the local system of record.

Models

Download
ModelsInterfaceRoute into Edge
AE080BXYDEG/EU outdoor unitSingle-phase 230 V-class R32 monobloc with water-side connections and Samsung indoor/control-kit communicationRecord the actual paired controller and independent thermal/electrical meter boundary before data integration.
MIM-E03EN or MIM-E03CN control kitSamsung-listed space-heating-only pairing for this outdoor unitRecord its Samsung bus connection and any fitted MIM-B19N/B19NT. The additional module is the Modbus endpoint; use its tracked EHS device address for the point calculation.
ClimateHub optionSamsung lists AE200RNWMEG/EU and AE260RNWMEG/EU combinations for this outdoor modelConfirm the installed ClimateHub model and hydronic arrangement rather than assuming the control-kit path.

Specifications

Samsung's 2026 installation manual distinguishes the single-phase AE080BXYDEG from the three-phase AE080BXYDGG and higher-capacity models. For the 8 kW unit it specifies 220-240 V, 50 Hz supply, 2.7 kg R32, 1-inch water connections, 126 kg net mass and a 1,270 × 1,018 × 530 mm enclosure.1

Exact outdoor model
AE080BXYDEG/EU, single-phase 8 kW R32 monobloc13
Electrical supply
1-phase 220-240 V, 50 Hz; installation manual lists MCA 26 A and MFA 28.6 A1
Leaving-water range
Heating 15-70 °C; cooling 5-25 °C, subject to operating conditions1
Ambient range
Heating -30 to +43 °C; cooling +10 to +46 °C1
Control-kit pairing
MIM-E03EN or MIM-E03CN for the listed space-heating-only configuration1
Other listed pairing
AE200RNWMEG/EU or AE260RNWMEG/EU ClimateHub in the manual's certification table1
PV and grid contacts
PV contact and Smart Grid Ready functions shown for the MIM-E03EN kit; contact behavior requires the installed kit manual2
Dimensions and mass
1,270 × 1,018 × 530 mm; 126 kg net1

Interface

Documented measurements and integration boundaries for EHS Mono HT Quiet 8 kW.

  • The February 2026 outdoor manual lists AE080BXYDEG as 1-phase 220-240 V, 50 Hz, using 2.7 kg of R32. It lists MIM-E03EN and MIM-E03CN control kits; its certification table ties AE080BXYDEG/EU to both kits for space heating only.
  • Samsung's product brochure shows a PV contact and Smart Grid Ready function with the MIM-E03EN kit. These are installer-configured control contacts, not a live PV production meter, heat meter or published software dispatch API.
  • The MIM-B19N/B19NT manual gives Modbus RTU settings of 9600 baud, 8 data bits, even parity and one stop bit. Its Samsung R1/R2 side uses the proprietary Control Layer Protocol; the A/B side serves Modbus. The installer must establish the correct Samsung bus attachment for the fitted system.
  • For tracked EHS device address IU, the module's table uses a base PDU address of 50 + 50 × IU. Water-in temperature is base + 15, water-out is base + 16 and hot-water temperature is base + 25. Read-only temperature values are expressed as Celsius × 10. For IU 3, these candidates are 215, 216 and 225; a raw positive value of 400 represents 40 °C.
  • Communication status is base + 0: bits 0, 1 and 2 indicate present, correct type and ready, while bit 3 indicates a communication error. Unit type at base + 1 has EHS codes 115-117 in its lower byte. The manual says registers start at zero and retain their last value after a lost Samsung link, so check tracking and freshness before interpreting temperatures.
  • SmartThings operation is optional and requires Samsung's supported controller, Wi-Fi kit, network and account. An app connection is not evidence of a local third-party data endpoint.
  • An 8 kW nameplate and a nominal COP do not establish measured heat delivery or seasonal performance. Use a hydronic heat meter and electricity metering that includes every compressor, pump, booster and backup load inside the stated COP boundary.

Assessment

AE080BXYDEG/EU with its installed Samsung controller. The MIM-B19N EHS map is the read-only starting point for an installer-fitted, tracking module; it does not specify a VPP dispatch design.

InteroperabilityLimited
Samsung publishes an EHS-class Modbus module and read map. Accessory fit and tracking on the installed controller are the site check for that route.124
AccuracyLimited
The product data states nominal operating points. Delivered thermal energy and inclusive electrical input need independent meters for site COP.12
SecurityNot yet assessed
Samsung’s documents do not describe access control or permissions for the module’s Modbus port.14
ReliabilityLimited
The module exposes ready/error status but retains last values if the Samsung link stops. Monitoring must use status and its own timestamps to identify stale values.4
RuggednessSupported with conditions
The outdoor manual gives temperature ranges, water-side requirements and installation clearances; frost protection and metering placement depend on the installed hydronic design.1
ScalabilityNot yet assessed
The module manual does not describe a multi-unit polling topology for this exact pairing.14
LifecycleSupported with conditions
Samsung publishes a current exact outdoor manual with MIM-E03EN/CN and ClimateHub combinations. Preserve part and firmware identities as accessories are revised.13

Setup

  1. Identify the whole Samsung system

    Read the outdoor AE080BXYDEG/EU nameplate and the actual MIM-E03EN/CN or ClimateHub controller label. Capture firmware, optional Wi-Fi and any auxiliary heater arrangement.

  2. Trace the hydronic and electrical boundaries

    Record flow and return circuits, circulation pumps, domestic-hot-water storage, booster/backup heater feeds and the point of grid connection. Decide which loads and heat flows a performance metric will include.

  3. Check the fitted Modbus module

    Have the Samsung installer check MIM-B19N/B19NT accessory fit and its bus connection. Record the module's DIP/rotary slave address, tracked EHS address and revision. Configure the read client for 9600 baud, 8E1 and inspect module tracking before selecting points.

  4. Try the published EHS read candidates

    Use the table's base address 50 + 50 × IU for the actual tracked EHS address. Start with communication status and unit type, then water-in at base + 15 or water-out at base + 16 using FC04. Compare temperatures divided by 10 with the Samsung controller. If a point is absent, check tracking, the device address and controller configuration rather than guessing a different equipment map.

  5. Meter heat and power independently

    Install or identify suitable thermal and electrical meters at the chosen boundary. Align intervals and sign conventions; use controller temperatures or operating states to explain operation, not to substitute for measured delivered heat.

  6. Preserve commissioned controls

    Keep PV contact, Smart Grid Ready, frost protection, hot-water priority and heater operation under the approved system design. A flexibility proposal needs documented permissions, limits and fail-safe behavior before control.

Common questions

Where should I start with Modbus monitoring?
Start at a compatible, installer-fitted MIM-B19N/B19NT module that tracks the controller as EHS. Samsung's table provides status, unit type and temperature candidates using the tracked device address. This guide gives that best-effort starting map; compare it with the controller before saving the monitoring configuration.14
Does the PV contact report solar generation?
No. The brochure shows a PV contact as a control input on the MIM-E03EN system. A separate PV inverter or meter supplies generation data, and the contact's commissioned meaning needs its kit instructions.2
Does Smart Grid Ready make the heat pump dispatch-ready for a VPP?
The brochure names Smart Grid Ready, but does not establish remote commands, acknowledgement, override priority or fail-safe behavior for this installation. A VPP design needs those controls specified and accepted separately.2
Can Samsung's nominal COP prove operating efficiency?
No. The brochure's nominal COP is a laboratory operating-point figure. A site COP needs delivered heat and the included electrical inputs measured across the same period and a declared boundary.12