KACO new energy blueplanet 92.0/105/125 TL3
Commercial PV inverter
KACO documents a SunSpec Modbus TCP server for the blueplanet 87.0 to 165 TL3 family. This guide covers the 92.0, 105 and 125 TL3 ratings and read-only monitoring. Write access stays disabled. The separate RS-485 KACO protocol and string-combiner port are not Modbus routes.
- Modbus TCP
- SunSpec Modbus
- KACO RS-485 protocol
Commercial PV inverter
Compatibility
Compatible through documented SunSpec Modbus TCP
The current exact-family manual documents a Modbus TCP server based on SunSpec and a dedicated menu that permits write access to remain disabled.
blueplanet 92.0, 105 or 125 TL3 under the retained manual from firmware 03.59 onward. Use Modbus TCP for read-only monitoring and leave write access disabled.
Connect it with
-
Modbus Interface ZMB-3XFrom €399 ex VAT Configure Modbus Interface
-
Gateway ZGW-20From €899 ex VAT Configure Gateway
-
Evaluation Gateway on a Raspberry Pi Edge with one device licensedFree Set up Evaluation Gateway on a Raspberry Pi
For read-only monitoring over the permitted plant LAN
- Modbus
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| blueplanet 92.0 TL3 | 92 kVA class for 400 V grids | Record exact type code and firmware before discovery. |
| blueplanet 105 TL3 | 105 kVA class for 380/400/415 V grids | Use only its installed SunSpec model set. |
| blueplanet 125 TL3 | 125 kVA class for 600 V grids | Do not apply 400 V electrical limits. |
| Other 87.0-165 TL3 ratings | Covered by the family manual but outside this guide | Confirm separately before use. |
Specifications
The retained manual covers the blueplanet 87.0 through 165 TL3 platform from firmware 03.59. The 92.0, 105 and 125 TL3 have different grid ratings, so the full type code remains part of the point record.1
Interface
Documented measurements and integration boundaries for blueplanet 92.0/105/125 TL3.
- Inverter identity, firmware and implemented SunSpec models.
- AC and DC measurements, energy and operating state where returned by the installed SunSpec profile.
- Fault and status values where documented for the matching firmware interface.
Assessment
blueplanet 92.0, 105 or 125 TL3 from firmware 03.59, using SunSpec Modbus TCP with writes disabled.
- InteroperabilitySupported with conditions
- SunSpec Modbus TCP is documented, subject to installed firmware and the matching KACO interface specification.1
- AccuracySupported with conditions
- The family manual identifies inverter measurements and ratings; the implemented model set must be discovered for the exact firmware.1
- SecurityLimited
- Modbus TCP lacks transport protection, although the inverter provides a write-access control that can remain disabled.1
- ReliabilitySupported with conditions
- Operating limits and diagnostics are published; polling recovery and coexistence with site systems require commissioning tests.1
- RuggednessSupported with conditions
- Enclosure and environmental installation limits are published for the exact family.12
- ScalabilitySupported with conditions
- Dual Ethernet and network configuration support plant integration, while client count, polling and addressing need a site design.1
Setup
Discover SunSpec and read inverter power
A best-effort start using the TL3 manual’s conventional SunSpec support and the public SunSpec model definition. Discover the returned models once. The power example applies when model 103 is returned; its address and payload are synthetic.
- Endpoint
- Enable Network / Modbus TCP / Operation mode, or Network services / Modbus TCP / Operation mode in the device menu/web interface. Retain the configured port (default 502) and unit ID. Leave write access disabled. Use Ethernet on the protected plant LAN; the RS-485 string-combiner link is not this Modbus TCP endpoint.
- Signature request
- FC03 PDU 03 9C 40 00 02 reads wire address 40000, quantity 2. SunSpec also defines alternate bases 0 and 50000; continue only at the base returning the signature.
- Synthetic header
- 00 01 00 42 means common model 1 with 66 following data registers. At wire header 40002, the next model begins at 40002 + 2 + 66 = 40070. For each subsequent header, next = H + L + 2. Continue until ID 65535; record the header of model 103 if present.
- Representation check
- 00 67 means model 103; 00 71 means model 113. Their layouts differ. Use the model actually returned, not the synthetic header as a fixed layout.
- Conditional power request
- For returned SunSpec model 103 only, let H be its discovered header address. FC03 at H + 14, quantity 2, reads signed int16 W and signed W_SF. If H = 40070, read wire address 40084 (0x9C94), PDU 03 9C 94 00 02. This is an example header position; models 113/203/213 use their own layouts.
- Signed scaling example
- Synthetic bytes 30 39 FF FF decode to W = 12345 and W_SF = -1: 12345 × 10^-1 = 1234.5 W. These are two signed integer registers, not Float32. Value 0x8000 means unavailable, not zero. Compare decoded power with the inverter interface.
- Signed scaling example
- For model 103, frequency is H+16 and its signed scale factor H+17. Compare identity, fresh AC power and frequency with the inverter interface before expanding voltage/current/energy points. If another model is returned, decode that model’s own layout. Keep inverter production distinct from site import/export.
Acceptance: Use discovery and a display comparison as the first commissioning check. The firmware-specific KACO files help expand vendor points, but standard model discovery provides a starting read without waiting for them. No control writes or physical Edge test are claimed.
-
Confirm type and firmware
Record the full nameplate type, grid voltage, serial number and firmware. This guide begins at firmware 03.59 and does not cover similarly named North American variants.
-
Keep writes disabled
In the Modbus TCP menu, enable only the server operation needed for monitoring. Leave write access disabled and preserve power-control, grid and protection settings.
-
Use the Ethernet route
Connect through the permitted protected plant LAN and configured TCP port. Do not repurpose the RS-485 string-combiner connection or describe the KACO serial protocol as Modbus RTU.
-
Discover the installed models
A best-effort start using the TL3 manual’s conventional SunSpec support and the public SunSpec model definition. Discover the returned models once. The power example applies when model 103 is returned; its address and payload are synthetic.
-
Verify a live read
For model 103, frequency is H+16 and its signed scale factor H+17. Compare identity, fresh AC power and frequency with the inverter interface before expanding voltage/current/energy points. If another model is returned, decode that model’s own layout. Keep inverter production distinct from site import/export.
Sources
- blueplanet 87.0-165 TL3 operating manual, Q2 2026 (opens in a new tab)
- blueplanet 87.0 TL3 to 125 TL3 product page (opens in a new tab)
- SunSpec three-phase inverter model 103 definition (opens in a new tab)