12 AWG in mm²
A 12 AWG solid conductor is 2.053 mm across, which gives an area of 3.309 mm². The nearest metric size is 4 mm². A 2.5 mm² cable is smaller than 12 AWG, so it is not a like-for-like swap.
Conductor area 3.309 mm² Open in the calculator
Convert between American Wire Gauge, square millimetres and kcmil, with the nearest standard size in each system.
Conductor area
2.081mm²
Check the values to see a result.
Nearest sizes are for comparison, not substitution.
d = 0.005 in × 92(36 − n) ÷ 39A = π × d² ÷ 41 kcmil = 0.5067 mm²
14 AWG is 2.081 mm² (4.107 kcmil), with a solid diameter of 1.628 mm. The nearest metric size is 2.5 mm².
Tip: A metric cable is not a drop-in for the nearest AWG size: check its current rating and the terminal range of the equipment.
American Wire Gauge (AWG) numbers a conductor by its diameter: the larger the number, the thinner the wire. Metric cables are sold by cross-sectional area in mm², and North American sizes above 4/0 AWG are given in kcmil, thousands of circular mils. The calculator converts between the three and shows the nearest standard size in each system.
d = 0.005 in × 92(36 − n) ÷ 39
The gauge is defined by two fixed points: 36 AWG is 0.005 in across and 4/0 AWG is 0.46 in, with 39 equal ratio steps between them. The sizes 1/0 to 4/0 are gauges 0 to −3 in the formula.
A = π × d² ÷ 4
Convert the diameter to millimetres (1 in = 25.4 mm) and take the area of the circle. 14 AWG is 1.628 mm across, so its area is 2.081 mm².
1 kcmil = 0.5067 mm²
A circular mil is the area of a circle one thousandth of an inch in diameter. 250 kcmil is 250 × 0.5067 = 126.7 mm².
Two rules of thumb follow from the definition. Every three gauges the area roughly doubles, and every ten gauges it changes about tenfold.
Metric sizes work differently. IEC 60228 names a nominal area (2.5 mm², 16 mm²) and defines each size by its maximum resistance, so the real copper area can differ slightly from the name.
A 12 AWG solid conductor is 2.053 mm across, which gives an area of 3.309 mm². The nearest metric size is 4 mm². A 2.5 mm² cable is smaller than 12 AWG, so it is not a like-for-like swap.
Conductor area 3.309 mm² Open in the calculator
16 mm² is 31.58 kcmil, which falls between 6 AWG (13.3 mm²) and 4 AWG (21.15 mm²). Its equivalent gauge is 5.204 AWG and the nearest gauge is 5 AWG, a size that is seldom stocked, so in practice the choice is 4 AWG.
Nearest AWG size 5 AWG Open in the calculator
250 kcmil is 250 × 0.5067 = 126.7 mm². The nearest metric size is 120 mm², which has slightly less copper; the next size up is 150 mm².
Conductor area 126.7 mm² Open in the calculator
Standard metric sizes from IEC 60228 with their area in kcmil and the nearest AWG size. Above 4/0 AWG, North American cable is sized in kcmil.
| Metric size (mm²) | kcmil | Nearest AWG |
|---|---|---|
| 0.5 | 0.9868 | 20 |
| 0.75 | 1.48 | 18 |
| 1 | 1.974 | 17 |
| 1.5 | 2.96 | 15 |
| 2.5 | 4.934 | 13 |
| 4 | 7.894 | 11 |
| 6 | 11.84 | 9 |
| 10 | 19.74 | 7 |
| 16 | 31.58 | 5 |
| 25 | 49.34 | 3 |
| 35 | 69.07 | 2 |
| 50 | 98.68 | 1/0 |
| 70 | 138.1 | 2/0 |
| 95 | 187.5 | 3/0 |
| 120 | 236.8 | 4/0 |
| 150 | 296 | Above 4/0 |
| 185 | 365.1 | Above 4/0 |
| 240 | 473.6 | Above 4/0 |
| 300 | 592.1 | Above 4/0 |
Solid round conductor geometry from the AWG definition (NBS Handbook 100). Stranded conductors of the same gauge have a slightly larger overall diameter.
| AWG | Diameter (mm) | Area (mm²) | kcmil | Nearest metric (mm²) |
|---|---|---|---|---|
| 4/0 | 11.68 | 107.2 | 211.6 | 95 |
| 3/0 | 10.4 | 85.03 | 167.8 | 95 |
| 2/0 | 9.266 | 67.43 | 133.1 | 70 |
| 1/0 | 8.251 | 53.48 | 105.5 | 50 |
| 1 | 7.348 | 42.41 | 83.69 | 35 |
| 2 | 6.544 | 33.63 | 66.37 | 35 |
| 3 | 5.827 | 26.67 | 52.63 | 25 |
| 4 | 5.189 | 21.15 | 41.74 | 25 |
| 5 | 4.621 | 16.77 | 33.1 | 16 |
| 6 | 4.115 | 13.3 | 26.25 | 16 |
| 7 | 3.665 | 10.55 | 20.82 | 10 |
| 8 | 3.264 | 8.366 | 16.51 | 10 |
| 9 | 2.906 | 6.634 | 13.09 | 6 |
| 10 | 2.588 | 5.261 | 10.38 | 6 |
| 11 | 2.305 | 4.172 | 8.234 | 4 |
| 12 | 2.053 | 3.309 | 6.53 | 4 |
| 13 | 1.828 | 2.624 | 5.178 | 2.5 |
| 14 | 1.628 | 2.081 | 4.107 | 2.5 |
| 15 | 1.45 | 1.65 | 3.257 | 1.5 |
| 16 | 1.291 | 1.309 | 2.583 | 1.5 |
| 17 | 1.15 | 1.038 | 2.048 | 1 |
| 18 | 1.024 | 0.823 | 1.624 | 0.75 |
| 19 | 0.9116 | 0.6527 | 1.288 | 0.75 |
| 20 | 0.8118 | 0.5176 | 1.022 | 0.5 |
| 21 | 0.7229 | 0.4105 | 0.8101 | 0.5 |
| 22 | 0.6438 | 0.3255 | 0.6424 | 0.5 |
| 23 | 0.5733 | 0.2582 | 0.5095 | 0.5 |
| 24 | 0.5106 | 0.2047 | 0.404 | 0.5 |
| 25 | 0.4547 | 0.1624 | 0.3204 | 0.5 |
| 26 | 0.4049 | 0.1288 | 0.2541 | 0.5 |
| 27 | 0.3606 | 0.1021 | 0.2015 | 0.5 |
| 28 | 0.3211 | 0.08098 | 0.1598 | 0.5 |
| 29 | 0.2859 | 0.06422 | 0.1267 | 0.5 |
| 30 | 0.2546 | 0.05093 | 0.1005 | 0.5 |
| 31 | 0.2268 | 0.04039 | 0.0797 | 0.5 |
| 32 | 0.2019 | 0.03203 | 0.06321 | 0.5 |
| 33 | 0.1798 | 0.0254 | 0.05013 | 0.5 |
| 34 | 0.1601 | 0.02014 | 0.03975 | 0.5 |
| 35 | 0.1426 | 0.01597 | 0.03152 | 0.5 |
| 36 | 0.127 | 0.01267 | 0.025 | 0.5 |
| 37 | 0.1131 | 0.01005 | 0.01983 | 0.5 |
| 38 | 0.1007 | 0.007967 | 0.01572 | 0.5 |
| 39 | 0.08969 | 0.006318 | 0.01247 | 0.5 |
| 40 | 0.07987 | 0.00501 | 0.009888 | 0.5 |
2.081 mm². The metric sizes on either side are 1.5 mm² and 2.5 mm².
Neither. 2.5 mm² sits between 14 AWG (2.081 mm²) and 12 AWG (3.309 mm²), at an equivalent of 13.21 AWG.
The number began as a count of how many times wire was drawn through a die to make it thinner. More passes gave a higher number and a smaller diameter.
They are the sizes larger than 1 AWG, read “one aught” to “four aught”. In the formula they are gauges 0, −1, −2 and −3. Past 4/0 (107.2 mm²), sizes are given in kcmil.
Not without checking. Current ratings come from the cable standard and the installation method, not from area alone, and equipment terminals accept a stated range of sizes. Use the conversion to find candidates, then check the rating tables that apply to the installation.