SMA Solar Technology Sunny Tripower X 25
Commercial PV inverter
A 25 kW three-phase PV inverter with three MPPTs and an integrated system manager. Read its own device values separately from whole-system measurements.
- Modbus TCP
Commercial PV inverter
Compatibility
Compatible through Modbus TCP
SMA publishes a model-specific register package and the ennexOS Modbus server interface. The worked read uses the SMA profile and the inverter’s own device scope, not a system aggregate or a borrowed SunSpec register address.
Sunny Tripower X 25, type STP 25-50 (non-US), using the model-specific parameter package for firmware 03.16.xx.R. Operating manual version 1.4 covers firmware 3.06.15.R and later, but the worked register definitions here are pinned to 03.16.xx.R. STP 25-US-50, Sunny Tripower X 60 and Sunny Tripower Hybrid X are outside this guide.
Connect it with
-
Gateway ZGW-20From €899 ex VAT Configure Gateway
For the inverter’s own SMA-profile measurement registers
- Modbus
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| STP 25-50, non-US | 25 kW PV inverter, three MPPTs, Ethernet | Read the exact 03.16.xx.R device map using SMA profile unit ID 3. |
| STP 25-50 as System Manager | System and subordinate-device coordination | Unit 2 exposes system scope; unit 3 remains this inverter. Assigned downstream IDs of 10 and above are separate endpoints. |
| STP 25-US-50 / X 60 / Hybrid X | Different regional or product generation scope | Use the matching manual and map; do not infer compatibility from the Sunny Tripower name. |
Specifications
The current operating manual allows configuration as a System Manager or as a subordinate device. In System Manager mode it describes a maximum system size of 135 kVA and up to five additional devices, with device-type limits applying. The inverter can also sit below a separate SMA Data Manager. This guide leaves the existing management role intact and adds only a bounded read of the inverter’s own values. It does not change country settings, power limits, protection functions or the ownership of site-level control.13
- Exact type
- STP 25-50, Sunny Tripower X 25, non-US1
- Nominal AC output
- 25 kW, three-phase1
- PV topology
- Three MPP trackers; PV inverter, not Hybrid X1
- Register scope
- Parameter package for firmware 03.16.xx.R2
- Default server transport
- Modbus TCP, port 502; interface disabled by default1
- Device versus system
- Unit 3: device values; unit 2: system values; unit 1: product information3
- Selected identity
- 30053, U32 TAGLIST; code 9488 identifies Sunny Tripower X 252
- Selected active power
- 30775, S32 FIX0, W, unit ID 32
- Total yield
- 30513, U64 FIX0, Wh, unit ID 32
- Environment
- IP65; -25 to +60 °C installation temperature range1
Interface
Documented measurements and integration boundaries for Sunny Tripower X 25.
- Device type code and other documented identity fields.
- Instantaneous active power from the individual inverter, in watts.
- Total yield as an unsigned 64-bit watt-hour counter.
- Model-supported AC and DC measurements, each with its own data width and format.
Assessment
Sunny Tripower X 25, type STP 25-50 (non-US), using the model-specific parameter package for firmware 03.16.xx.R. Operating manual version 1.4 covers firmware 3.06.15.R and later, but the worked register definitions here are pinned to 03.16.xx.R. STP 25-US-50, Sunny Tripower X 60 and Sunny Tripower Hybrid X are outside this guide.
- InteroperabilitySupported with conditions
- The exact firmware map and ennexOS interface define local TCP reads; unit IDs and product scope must match.23
- AccuracySupported with conditions
- The map defines individual inverter power and energy formats, separate from system totals. It does not establish billing-meter accuracy.2
- SecurityNot yet assessed
- The manual gives network exposure precautions, but the Modbus path does not establish authenticated or encrypted telemetry.13
- ReliabilityNot yet assessed
- No measured availability or automatic historical backfill contract is established for these instantaneous reads.3
- RuggednessSupported with conditions
- The operating manual specifies IP65 and -25 to +60 °C, subject to installation and operating limits.1
Setup
Identify STP 25-50, then read its power
The firmware-specific SMA map assigns device type 30053 to U32 TAGLIST and active power 30775 to S32 FIX0. The device measurement endpoint is unit ID 3.
- Identity PDU
- 03 75 65 00 02: FC03, literal address 30053, quantity 2, unit ID 3 in the TCP header.
- Synthetic identity data
- 00 00 25 10 is unsigned 9488, the map’s code for Sunny Tripower X 25.
- Power PDU
- 03 78 37 00 02: FC03, literal address 30775, quantity 2, on the same unit ID 3.
- Synthetic power data
- 00 00 61 A8 is signed 25000; FIX0 gives 25000 W. This illustrates decoding, not an observed operating result.
- Unavailable value
- 80 00 00 00 is the S32 unavailable sentinel; do not plot it as negative power.
Acceptance: Accept the identity only when the exact model and firmware match. Accept power only after a complete response and comparison with the inverter. System unit ID 2, SunSpec models and subordinate endpoints are separate measurement scopes.
-
Match the model and firmware
Sunny Tripower X 25, type STP 25-50 (non-US), using the model-specific parameter package for firmware 03.16.xx.R. Operating manual version 1.4 covers firmware 3.06.15.R and later, but the worked register definitions here are pinned to 03.16.xx.R. STP 25-US-50, Sunny Tripower X 60 and Sunny Tripower Hybrid X are outside this guide.
-
Preserve the existing system role
Record whether this inverter is System Manager or subordinate. Do not change that role to obtain a measurement. Keep the inverter, whole-system and downstream-device identities separate in the point names and client configuration.
-
Enable the local server deliberately
The interface is disabled by default. Use the documented local configuration with an authorised installer or administrator, then verify the configured port, normally 502. Keep access on the intended site network; the operating manual says not to use port forwarding for Modbus.
-
Select the individual inverter endpoint
Use SMA profile unit ID 3 for the worked device registers. Unit 1 identifies the product, unit 2 is system scope, and assigned IDs of 10 and above address connected devices. Do not apply the older generic SMA SunSpec unit-ID offset rule to this ennexOS configuration.
-
Read identity before measurements
Read FC03 at literal decimal address 30053, quantity 2. A U32 TAGLIST value of 9488 identifies Sunny Tripower X 25 in this firmware package. Then read 30775 as two registers for signed active power, or 30513 as four registers for total yield. Read each multi-register item together.
-
Validate the data and pace requests
Use big-endian order and each entry’s documented format. FIX0 requires no decimal scaling. Treat S32 0x80000000 and U64 all-ones as unavailable, not as real measurements. The ennexOS interface recommends at least one second between transfers and no more than five parameters or measured values simultaneously. Compare the result with the inverter’s own live display.
Common questions
- Why is unit ID 2 wrong for this worked read?
- The ennexOS interface reserves unit 2 for system parameters and measurements. The exact device map assigns active power and total yield to unit 3. Mixing the two scopes can produce the wrong site interpretation even when a response is syntactically valid.23
- Can I use fixed SunSpec addresses instead?
- SMA also documents SunSpec for ennexOS. Its supported models are included dynamically and are traversed using each model’s ID and length. That is a separate configuration and discovery path; the literal addresses in this guide belong to the SMA profile.34
- Does the register range mean this model is rated 50 kW?
- No. A register’s allowed numeric range is not the inverter nameplate rating. The STP 25-50 operating manual gives a 25 kW rated AC output; a broader range in the register definition does not change that rating.12
- Can this monitoring client change export limits?
- Not through the read-only procedure here. Grid management and control registers have additional operating and permission requirements. The Modbus document also warns that repeated writes to persistent settings can damage flash memory.3
- Does a communication failure mean zero production?
- No. Missing replies and unavailable sentinels must remain distinguishable from a valid zero-watt value. Otherwise outages in data collection can appear as genuine generation changes.3
Sources
- Sunny Tripower X 25 operating manual, version 1.4 (opens in a new tab) (PDF)
- STP xx-50 parameters and measured values, firmware 03.16.xx.R (opens in a new tab)
- SMA Modbus interface ennexOS, internal revision 13 (opens in a new tab) (PDF)
- SunSpec Modbus ennexOS, version 1.0 (opens in a new tab) (PDF)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.