Voltage THD on a 230 V supply
A power quality meter shows 2.3 V of 3rd, 6.9 V of 5th and 4.6 V of 7th harmonic on a 230 V fundamental. The harmonic content is 8.606 V, a voltage THD of 3.742%. That one reading is below the 8% low-voltage figure in EN 50160, but does not establish conformity: the standard applies at supply terminals over a defined week of 10-minute values, includes harmonics through order 40 and checks individual harmonics too. IEEE 519 assesses the point of common coupling under its own measurement rules.
Voltage THD 3.742 % Open in the calculator