CT ratio and burden calculator

Check an existing current transformer: its secondary current at the measured load, and whether the meter and the secondary wiring stay within its rated burden.

Metering and CTs Updated Free, no sign-up

250through a400CT with a5 Asecondary

gives3.125on the secondary, 62.5% of its rated 5 A

020040060020%120%A

Primary current against the rating

62.5

In the range the accuracy class covers

Leads:16.6of 2.5 mm² each way, or0.3loop, and a meter of1on a CT rated5

Burden at the rated 5 A

3.5 VA over the rating
  • Meter 1 VA
  • Leads 7.5 VA 0.3 Ω loop
  • Over 3.5 VA

Longest lead run each way, copper at 75 °C, within 5 VA

  • 1.5 mm²5.44 m136 m at 1 A
  • 2.5 mm²8.88 m222 m at 1 A
  • 4 mm²14.3 m357 m at 1 A
  • 6 mm²21.4 m534 m at 1 A
CT ratio
A
Rated secondary current
A
Burden

At the rated secondary current

VA
Secondary leads

Out and back, at operating temperature

Ω

From the CT to the meter

m
VA
More options
Lead temperature

Secondary current

3.125A

Ratio
400/5
Lead burden at rated current
7.5 VA
Connected impedance
0.34 Ω
Longest 2.5 mm² lead run, each way
8.878 m
  • Fail: Burden over the CT ratingShorten the leads, use a larger cross-section, a 1 A CT or a CT with a higher rated burden.3.5 VA over
  • Pass: Primary current in the accurate range20% to 120% of the rating62.5%

Meter and lead burden are added as magnitudes, which errs on the safe side. Never open a CT secondary while the primary carries current.

How it’s calculated
  1. Is = Ip × Is,rated ÷ Ip,rated=250 ÷ 80=3.125 A
  2. VAleads = Is,rated² × Rloop=5² × 0.3=7.5 VA
  3. VAtotal = VAmeter + VAleads=1 + 7.5=8.5 VA

Choose a meter for these CTs.

Build a system

A 400/5 CT carrying 250 A gives 3.125 A on its secondary. The meter and leads use 8.5 VA of its 5 VA rated burden, which is too much.

Tip: With a 5 A secondary, the leads use burden 25 times faster than with 1 A: a long run to the meter is where 1 A CTs earn their place.

How to calculate CT secondary current and burden

A current transformer’s burden is everything connected to its secondary: the meter input, the wiring out and back, and the terminals. Each is a load in VA at the rated secondary current, and together they must stay within the CT’s rated burden, or the CT loses accuracy. The calculator gives the secondary current at your load and checks the burden, including the leads.

Secondary current

Is = Ip × Is,rated ÷ Ip,rated

A 100/5 CT has a ratio of 20. At 60 A in the primary it delivers 60 ÷ 20 = 3 A.

Lead burden

VAleads = Is,rated2 × Rloop

Rloop is the resistance of the whole secondary loop, out and back. It is worked out at the rated secondary current, the point the CT’s rating refers to.

Total burden

VAtotal = VAmeter + VAleads ≤ VArated

Add the meter burden from its datasheet. Adding the two as plain numbers slightly overstates the total, which errs on the safe side.

Because burden goes with the square of the current, a 5 A CT puts 25 times the load on the same leads as a 1 A CT. On long runs between the CT and the meter, 1 A secondaries are the usual answer.

CT burden examples

A 100/5 CT close to its meter

At 60 A the CT gives 3 A. A short lead loop of 0.1 Ω uses 5² × 0.1 = 2.5 VA and the meter 1 VA, so 3.5 VA of the 5 VA rating is used.

Secondary current 3 A Open in the calculator

A 400/5 CT on a long run

The meter is 20 m away on 2.5 mm² copper, a loop of about 0.3 Ω. At 5 A the leads alone use 7.5 VA, so with the meter the burden is 8.5 VA, well over a 5 VA rating. The CT gives 3.125 A at 250 A, but its accuracy class no longer holds.

Secondary current 3.125 A Open in the calculator

The same run with a 1 A CT

With a 400/1 CT the same leads use 1² × 0.3 = 0.3 VA. With a 0.5 VA meter input the total is 0.8 VA, comfortably within 5 VA. At 250 A the secondary carries 0.625 A.

Secondary current 0.625 A Open in the calculator

CT lead burden by loop resistance

The burden the secondary wiring adds at rated current. For the loop resistance, take the conductor resistance per metre times twice the one-way length: 2.5 mm² copper is about 7.4 mΩ per metre at 20 °C, and the conductor resistance calculator works out others.

CT lead burden by loop resistance, values in VA
Loop resistance (Ω)5 A secondary (VA)1 A secondary (VA)
0.020.50.02
0.051.250.05
0.12.50.1
0.153.750.15
0.250.2
0.37.50.3
0.512.50.5
0.7518.750.75
1251
1.537.51.5
2502

Download this table (CSV)

Questions about CT burden

What is CT burden?

The load on the CT’s secondary, in VA at the rated secondary current. It includes the meter or relay input, the wiring and the connections. A CT meets its accuracy class only while the burden is within its rating.

Should I use a 1 A or a 5 A CT?

For short runs inside a panel, either works. For long runs, 1 A: the wiring burden is 25 times lower for the same cable. Match the secondary to the meter input.

What happens if the burden is too high?

The CT needs more voltage to drive its current through the load. Its ratio and phase errors grow, and at high currents it can saturate and under-read.

Why must a CT secondary never be left open?

A current-output CT forces its current into whatever is connected. With the secondary open and the primary carrying current, the voltage across the terminals can rise to dangerous levels and damage the CT. Short the secondary with the shorting link before disconnecting the meter.

Limits of this result

  • For conventional current-output CTs with an external burden. This tool is not for voltage-output CTs or Rogowski coils.
  • Ratio and rated burden do not establish accuracy class, saturation, fault duty, insulation rating or aperture fit.
  • Enter the resistance of the complete outgoing-and-return secondary lead loop at its operating temperature.
  • A cable run uses the IEC 60228 maximum resistance of stranded copper (class 2) at the chosen lead temperature, so a real cable usually uses slightly less burden than shown.
  • Enter instrument burden at the selected rated secondary current. For unchanged impedance, burden at another current scales with the square of current.
  • Adding instrument VA magnitude and resistive lead VA is a conservative arithmetic sum, not an exact complex-impedance calculation.

Measure it continuously

A ZEM ships with its CTs connected and calibrated to the meter, and Class 0.5S describes the whole measurement, so there is no burden to work out on site.

Related guides

Sources

  1. What is required when selecting a VT or CT? (opens in a new tab) Schneider Electric, last reviewed 2026-09-14
  2. What if the rated CT burden is inadequate? (opens in a new tab) Schneider Electric, modified 2026-06-23
  3. Can current transformer secondary windings be open-circuited? (opens in a new tab) Schneider Electric, accessed 2026-09-14
  4. IEC 60228:2023 Conductors of insulated cables (opens in a new tab) International Electrotechnical Commission, Edition 4.0, 2023-12