STIEBEL ELTRON WPL 25 AC
Air-source heat pump
Monitor the WPL 25 AC through a compatible ISG connected to its WPM controller. STIEBEL ELTRON publishes separate WPMsystem and WPM 3 register tables with outside, flow and return temperatures. Start with an outside-temperature comparison, then add available operating values. Measure delivered heat and the full electrical boundary separately for site COP.
Compatibility
Compatible with EpiSensor Edge over Modbus TCP through an ISG
The May 2026 ISG compatibility table includes WPL 15/20/25 A(C)(S) with WPMsystem and WPM 3. The current Modbus software document explicitly covers ISG Connect, web and plus and supplies controller-specific read tables. ISG Connect includes Modbus software at the factory.
Match the installed WPM and ISG to the compatibility row, including manufacturing-date/software conditions. Use the published map as a best-effort starting point, compare the first read with the WPM display and handle unavailable objects. This procedure covers monitoring; preserve the existing SG Ready and output-control design.
Connect it with
WPL 25 AC is paired with a supported WPM and an ISG Connect meeting the manufacturer compatibility row
- Wired
- Edge
- Platforms
Models
| Models | Interface | Route into Edge |
|---|---|---|
| WPL 25 AC, order 236645 | Outdoor air-to-water heat pump for heating and cooling; WPM listed as required accessory | Use the installed WPM controller and a compatible ISG as the monitoring endpoint. |
| WPMsystem with compatible ISG | ISG compatibility table marks WPL 15/20/25 A(C)(S) and building automation over Modbus | Select the WPMsystem table and compare read-only outside temperature 507 with the WPM display before adding more points. |
| WPM 3 with compatible ISG | The 2026 table also lists WPM 3, including a specific WPL 15/25 row from July 2015 with WPM 390.03 and FES 417.02 | Check the listed date/software condition and use the WPM 3 table. Outside temperature 507 is available in that table as well. |
| WPL 25 ACS, WPL 25 A and WPL-A generations | Related but different outdoor variants or product generations | Do not transfer thermal ratings, wiring or controller compatibility to WPL 25 AC. |
Specifications
STIEBEL ELTRON identifies the WPL 25 AC as an outdoor air-to-water heat pump, order 236645, for heating and cooling. The current product page gives 7.84 kW at A7/W35, 12.86 kW at A-7/W35 and SCOP 4.76 at 35°C; these are different test conditions, not a continuous output range. A WPM wall-mounted heat-pump manager is required equipment.1
Interface
Documented measurements and integration boundaries for WPL 25 AC.
- The ISG is the local Modbus TCP endpoint. Its CAN connection communicates with the WPM; the outdoor unit X43 label belongs to the internal heat-pump circuit.
- The current map lists outside temperature at one-based input address 507 for WPMsystem and WPM 3. Use FC04, one 16-bit word, signed type 2 with a 0.1 multiplier to obtain °C. Try zero-based client address 506 and compare the value with the controller.
- Input addresses 515 and 516 give actual flow and return temperatures, and 522 gives actual DHW temperature, where the sensor/object is available. These are signed type-2 values scaled by 0.1 °C. The separate heat-pump-1 rows include return temperature 542 and flow temperature 543; choose the point that matches the system display.
- The substitute value 32768 (0x8000) means an object is unavailable. Check it before signed conversion, omit that sample and retain its unavailable status rather than displaying -3276.8 °C.
- The software document says ISG addresses are one-based and a client offset of one may be needed. Keep the published address, client convention, type and multiplier with each point; type 7 uses a 0.01 multiplier, unlike type 2.
- WPL 25 AC is labelled SG Ready. WPMsystem input contacts and ISG Modbus control registers support separately commissioned functions. Establish monitoring first and preserve existing heating, DHW and frost-protection settings.
- For site COP, meter delivered heat and the complete electrical input over matching periods. Controller operating values help explain performance; independent meters define the measured boundary.
Assessment
WPL 25 AC order 236645 with WPMsystem or WPM 3 and compatible ISG, using the published controller-specific read map.
- InteroperabilitySupported with conditions
- The official compatibility table lists the WPL 15/20/25 A(C)(S) family with WPMsystem or WPM 3 and ISG Modbus TCP, subject to installed controller software.235
- AccuracySupported with conditions
- The public map supplies signed temperature and operating values with per-point types and multipliers. Sensor availability depends on the installation; independent heat/electricity meters are needed for site COP.15
- SecuritySupported with conditions
- The ISG Connect manual advises against a direct internet connection; a restricted site network is needed for any BMS access.3
- ReliabilityLimited
- ISG documents a 5-10 minute WPM initialisation and status LEDs. The map explicitly returns 0x8000 for unavailable objects; readers need timestamps and missing-value handling.35
- RuggednessNot yet assessed
- The heat pump is an outdoor unit and ISG is a separately installed indoor network accessory. Match each device to its documented environment.34
- ScalabilityNot yet assessed
- The permitted BMS polling load and concurrent-client capacity have not been established for the installed ISG.
Setup
Read WPM outside temperature through ISG
The current ISG map lists outside temperature as read-only input address 507 in both the WPMsystem and WPM 3 tables. Its one-based convention and signed type-2 scaling give this best-effort first read.
- Target
- ISG local IP, standard Modbus TCP port 502; use the commissioned site network address
- Function
- FC04 Read Input Registers
- PDU start
- Try 506 decimal (0x01FA) for the published one-based address 507; a one-based client displays 507
- Length
- 1 register
- Decode
- First reject 0x8000 as unavailable. Otherwise signed 16-bit × 0.1 °C; raw 203 (0x00CB) means 20.3 °C
- Acceptance
- Compare with the WPM outside-temperature display at the same moment
Acceptance: If the value is implausible, check the client address offset and controller table. Mark unavailable values as missing. Once this read matches, add the installed system’s flow, return and DHW points and compare each with its local display.
-
Identify the installed system
Record WPL 25 AC order 236645, WPM type, manufacturing date and ISG model. Match the manufacturer compatibility row; the July 2015 WPM 3 row names WPM 390.03 and FES 417.02 minimum versions.
-
Connect the ISG
For ISG Connect, use the supplied CAN cable on the commissioned WPM bus, LAN cable to the site network and USB-C power adapter. Allow the documented 5-10 minute WPM initialisation and check the left LED is steady green.
-
Find its local address
Use SERVICEWELT or the router DHCP list to identify the ISG IP. The documented direct-connection address is 192.168.0.126. Keep the Modbus service inside the protected site network.
-
Read outside temperature
Start with FC04, one register, trying zero-based address 506 for the map’s one-based address 507. Reject 0x8000 as unavailable; otherwise decode signed 16-bit and multiply by 0.1 °C. Compare with the WPM outside-temperature display.
-
Add available points
Use the table for WPMsystem or WPM 3. Try actual flow 515, return 516 and DHW 522 using the same type-2 scaling, then compare each with its matching display value. Save only useful points that the installed system reports.
-
Meter performance and preserve controls
Meter delivered heat and full electrical input separately for COP. Record valid-read timestamps and unavailable samples. Leave SG Ready, output reduction and mode/setpoint writes in the commissioned heat-pump design.
Common questions
- Does WPL 25 AC have a direct Modbus TCP server?
- Use a compatible ISG connected to the WPM. ISG Connect has a local Modbus TCP service and the current software document supplies separate WPMsystem and WPM 3 tables. Start with the published outside-temperature address 507, using FC04 and signed 0.1 °C scaling.235
- Does the SG Ready label mean Edge may dispatch the heat pump?
- SG Ready provides control functions through the installed WPM/ISG and commissioned input wiring. Plan permitted modes, override and fallback separately from monitoring, then measure the electrical response.13
- Can WPM 3 and WPMsystem use the same setup?
- Both appear in the manufacturer’s WPL 15/20/25 A(C)(S) compatibility table. The WPM 3 row for units from July 2015 names specific WPM 390.03 and FES 417.02 versions; confirm the installed row instead of assuming the controllers are interchangeable.2
- Can the product SCOP be used as measured site COP?
- No. SCOP 4.76 is a standardised 35°C rating. A site COP needs independently metered delivered heat and complete electrical consumption over matching intervals.1
Sources
- WPL 25 AC product 236645 and required WPM accessory (opens in a new tab)
- ISG Connect, web and plus compatibility overview, 21 May 2026 (opens in a new tab) (PDF)
- ISG Connect operation and installation manual (opens in a new tab) (PDF)
- WPL A/AC/AS/ACS operation and installation manual (opens in a new tab) (PDF)
- ISG Modbus TCP/IP software documentation A 321798-47824-0146 (opens in a new tab) (PDF)
Further reading
Product names and trademarks belong to their owners. Publication does not imply endorsement or a commercial relationship.