A 32 A three-phase circuit at 400 V
A machine draws the full 32 A rating at a power factor of 0.95: 1.732 × 400 × 32 × 0.95 ÷ 1000 = 21.06 kW. The apparent power is 22.17 kVA and the reactive power 6.92 kvar. The cable and the breaker carry 5% more current than a 21.06 kW load at unity power factor, so size the circuit on amps, not kW.
Active power, total 21.06 kW Open in the calculator