A 300 kW load from 0.8 to 0.95
tan(cos−1 0.8) = 0.75 and tan(cos−1 0.95) = 0.329, so the bank needs 300 × (0.75 − 0.329) = 126.4 kvar. At 400 V the line current falls from 541.3 A to 455.8 A.
Capacitive reactive power to add 126.4 kvar Open in the calculator